Plan Review Details - Permit 23020547
Plan Review Stops For Permit 23020547
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-05-15 Cont ID  
Sent By cpuell Date 2023-05-15 Time 16:03 Rev Time 0.00
Received By cpuell Date 2023-05-15 Time 16:03 Sent To  
Notes
2023-05-15 16:04:37THE BUILDING WILL HAVE 4 TENANT SPACES ADDRESSES
 ASSIGNED 885, 895, 905 AND 915 N RAILROAD AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-14 Cont ID  
Sent By cpuell Date 2023-02-14 Time 11:47 Rev Time 0.00
Received By cpuell Date 2023-02-14 Time 11:47 Sent To  
Notes
2023-02-14 11:48:06PARCEL NEEDS TO BE READDRESSED SO THAT THE ENTRANCES ON
 THE GROUND FLOOR FALLS IN LINE WITH THE CITY'S ROAD
 CENTER LINES. ADDRESSES THAT NEED TO BE ESTABLISHED
 WOULD BE FOR THE BUILDING ITSELF, THE GROUND FLOOR
 COMMERCIAL SPACE AND THE UNITS ON THE UPPER FLOORS.
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO
 WORK ON THE READDRESSING ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By swelter Date 2023-03-10 Time 13:04 Rev Time 0.00
Received By swelter Date 2023-03-10 Time 13:05 Sent To  
Notes
2023-03-10 13:05:19SEE MASTER PERMIT # 22120561

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-07 Cont ID  
Sent By rmcphers Date 2023-07-07 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2023-07-07 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By rmcphers Date 2023-05-09 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2023-05-09 Time 16:23 Sent To  
Notes
2023-05-09 16:27:02NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE BUILDING SET BACKS FROM THE PROPERTY
 LINES - FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 2) DRAWING A-502 DOES NOT SHOW IN ADOBE READER AS
 DIGITALLY SIGNED - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By rmcphers Date 2023-03-13 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2023-03-10 Time 14:36 Sent To  
Notes
2023-03-13 11:58:52NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING RISK CATEGORY IS SHOWN AS II - AN ASSEMBLY
 CLASSIFICATION WITH OVER 300 OCCUPANT LOAD WILL NEED TO
 SHOW A RISK CATEGORY OF III WITH DESIGN WIND SPEEDS OF
 180MPH - FBC 1604.5
  
 2) PLEASE SHOW ON THE SITE PLAN THE STORM WATER FLOW
 AWAY FROM THE BUILDING AND AWAY FROM ADJACENT PROPERTY
 OR PROVIDE A STORM WATER PLAN - FBC WPB 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
 3) EXTERIOR DOOR (110B) NEEDS TO BE 3/4 HOUR FIRE RATED
 - FBC 706.5 HORIZONTAL CONTINUITY.
 FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO
 EXTERIOR WALL AND SHALL EXTEND NOT LESS THAN 18 INCHES
 (457 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS.
 EXCEPTIONS: (1) FIRE WALLS SHALL BE PERMITTED TO
 TERMINATE AT THE INTERIOR SURFACE OF COMBUSTIBLE
 EXTERIOR SHEATHING OR SIDING PROVIDED THE EXTERIOR WALL
 HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR
 FOR A HORIZONTAL DISTANCE OF NOT LESS THAN 4 FEET (1220
 MM) ON BOTH SIDES OF THE FIRE WALL. OPENINGS WITHIN
 SUCH EXTERIOR WALLS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR.
  
 4) DRAWING (A.03) - STAIR HAND RAIL EXTENSIONS NEED TO
 CONTINUE IN THE DIRECTION OF THE STAIR - SHOULD NOT
 TURN UNLESS THE STAIR CONTINUES - FBC 1014.6 HANDRAIL
 EXTENSIONS.WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN
 FLIGHTS, THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT
 LESS THAN 12 INCHES (305 MM) BEYOND THE TOP RISER AND
 CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE
 BOTTOM RISER.
  
 5) PLEASE PROVIDE A SURVEY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By mpeterso Date 2023-07-13 Time 14:07 Rev Time 0.00
Received By mpeterso Date 2023-07-13 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-24 Cont ID  
Sent By mpeterso Date 2023-02-24 Time 14:56 Rev Time 0.00
Received By mpeterso Date 2023-02-22 Time 15:14 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-07-13 Cont ID  
Sent By cseifer Date 2023-07-13 Time 08:25 Rev Time 0.00
Received By cseifer Date 2023-07-13 Time 08:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By lquinone Date 2023-05-09 Time 13:54 Rev Time 0.00
Received By lquinone Date 2023-05-09 Time 13:54 Sent To  
Notes
2023-05-09 13:55:34WAITING ON PENDING ENGINEERING SUBMITTAL REVISION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By rrossano Date 2023-02-21 Time   Rev Time  
Received By rrossano Date 2023-02-21 Time   Sent To  
Notes
2023-02-21 12:50:33WAITING ON PENDING ENGINEERING REVISIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By pleduc Date 2023-05-08 Time   Rev Time 0.00
Received By pleduc Date 2023-05-08 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By pleduc Date 2023-02-15 Time   Rev Time 0.00
Received By pleduc Date 2023-02-14 Time 15:21 Sent To  
Notes
2023-02-14 15:25:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE REAR EXITS INDICATED ON THE LIFE SAFETY
 PLANS,
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 THERE MAY BE A SERVICE ROAD NEXT TO THE RR, HOWEVER, I
 BELIEVE A FENCE IS BEING PROPOSED THAT MAY
 LIMIT/RESTRICT PASSAGE IN EITHER DIRECTION.
  
 THERE MAY ALSO BE GATES ALONG THIS FENCE THAT NEEDS TO
 BE ACCESSIBLE.
  
 AN ADDITIONAL CONCERN IS THAT THERE MAY BE UNPROTECTED
 OPENINGS ALONG ALL THE VARIOUS OCCUPANCIES ALONG THE
 FENCE LINE THAT COULD EXPOSE PEDESTRIANS TO THE EFFECTS
 OF FIRE AND SMOKE.
  
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE REQUIRED
 CODE.
  
  
  
 2) THERE ARE INDICATIONS WITHIN THE DOOR SCHEDULE THAT
 DO NOT APPEAR TO MEET THE NFPA 101 CH 7, MEANS OF
 EGRESS & CH 12 NEW ASSEMBLY REQUIREMENTS FOR ASSEMBLY
 OCCUPANCIES.
  
 7.2.1.7* PANIC HARDWARE AND FIRE EXIT HARDWARE.
  
 7.2.1.7.1 WHERE A SIDE-HINGED OR PIVOTED-SWINGING DOOR
 ASSEMBLY IS
 REQUIRED TO BE EQUIPPED WITH PANIC OR FIRE EXIT
 HARDWARE, SUCH HARDWARE
 SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, WITH
 THE LENGTH OF THE
 ACTUATING PORTION OF THE CROSS BAR OR PUSH PAD NOT LESS
 THAN ONE-HALF
 OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND
 NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF
 (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND LATCHES
  
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAP TERS 22 AND 23, SHALL NOT BE EQUIPPED
 WITH ANY LOCKING DEVICE, SET SCREW,
 OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE OF THE
 LATCH WHEN PRESSURE
 IS APPLIED TO THE RELEASING DEVICE
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE. DELINEATE
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-05-08 Cont ID  
Sent By rwbrown Date 2023-05-08 Time 06:12 Rev Time 0.00
Received By rwbrown Date 2023-05-08 Time 06:12 Sent To  
Notes
2023-05-08 06:12:43WILL BE ON SEPARATE PERMIT PER NOTES ON PLANS ON PAGE
 P-100
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By rwbrown Date 2023-02-16 Time 10:43 Rev Time 0.00
Received By rwbrown Date 2023-02-16 Time 10:43 Sent To  
Notes
2023-02-16 10:43:171ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - I DID NOT SEE A GAS
 DETAIL. DO YOU PLAN TO ROUGH IN GAS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-05 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-31 Cont ID  
Sent By aoliver Date 2023-05-31 Time 07:43 Rev Time 0.00
Received By aoliver Date 2023-05-05 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By rmcphers Date 2023-03-13 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2023-02-13 Time 15:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By rmcphers Date 2023-03-13 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2023-03-13 Time 12:42 Sent To  
Notes
2023-03-13 12:57:27PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-07-17 Cont ID  
Sent By jbaker Date 2023-07-17 Time 11:40 Rev Time 0.00
Received By jbaker Date 2023-07-17 Time 11:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 14:44 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By medwards Date 2023-02-21 Time 10:05 Rev Time 0.00
Received By medwards Date 2023-02-21 Time 10:05 Sent To  
Notes
2023-04-03 09:51:51LS.101 INDICATES THE AREA SERVED BY THE MECHANICAL
 SYSTEM AHU-1 ON SHEET M-100 HAS RATED WALLS SHOW HOW
 THE DUCT PENETRATION IN THESE RATED WALLS WILL BE
 PROTECTED. FMC 607.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-07 Cont ID  
Sent By rwbrown Date 2023-07-07 Time 07:34 Rev Time 0.00
Received By rwbrown Date 2023-07-07 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By rwbrown Date 2023-05-08 Time 06:06 Rev Time 0.00
Received By rwbrown Date 2023-05-08 Time 06:06 Sent To  
Notes
2023-05-08 06:11:402ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THE ENGINEERING PERMITS DO NOT REPLACE THE
 REQUIREMENT FOR BUILDING DEPARTMENT PERMITS FOR THE
 GREASE TRAP AND BACKFLOW PERMITS ---
 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE AT
 THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. DONE
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 7. DONE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By rwbrown Date 2023-02-16 Time 10:37 Rev Time 0.00
Received By rwbrown Date 2023-02-16 Time 10:37 Sent To  
Notes
2023-02-16 10:42:351ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. 2020 FPC 607.1.1/613.1 - THE WATER HEATER AT THE
 JANITOR SINK SHALL HAVE A MIXING VALVE. ALL HOT WATER
 SHALL BE LIMITED BY SOMETHING OTHER THAN THE THERMOSTAT
 ON THE WATER HEATER. ADD A WATER HEATER DETAIL AS WELL
 AS ADD IT TO THE ISOMETRIC.
  
 3. 2020 FPC 901.2.1 - PROVIDE A VENT FOR THE JANITOR
 SINK AND DRINKING FOUNTAIN.
  
 4. 2020 FPC 906.1 - IT APPEARS T YOU NEED AT THE
 MINIMUM A 3" VENT STACK TO THE DOWNSTAIRS TENANT.THE
 VENT STACK SERVING A 6" BUILIDNG DRAIN CANNOT BE LESS
 THAN HALF ITS SIZE.
  
 5. 2020 FPC 1003.4 - PLEASE SHOW THE OIL ALARM OR OIL
 SEPARATOR FOR THE SUMP IN THE ELEVATOR SHAFT.
  
 6. 2020 FPC 712.3.2/906.5 - PLEASE DETAIL A VENT FOR
 THE SUMP PIT.
  
 7. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE ADD A DETAIL
 AND SIZE FOR THE SCUPPERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By rmcphers Date 2023-03-13 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2023-03-13 Time 12:58 Sent To  
Notes
2023-03-13 12:58:51ROOFING SYSTEM TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-07 Cont ID  
Sent By rmcphers Date 2023-07-07 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2023-07-07 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By rmcphers Date 2023-05-09 Time 16:47 Rev Time 0.00
Received By rmcphers Date 2023-05-09 Time 16:47 Sent To  
Notes
2023-05-09 16:48:26SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-502 DOES NOT SHOW IN ADOBE READER AS
 DIGITALLY SIGNED - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
2023-05-09 14:44:48MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-13 Cont ID  
Sent By rmcphers Date 2023-03-13 Time 13:06 Rev Time 0.00
Received By rmcphers Date 2023-03-13 Time 13:06 Sent To  
Notes
2023-02-21 10:06:28MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By ckimmerl Date 2023-05-30 Time 10:18 Rev Time 0.00
Received By ckimmerl Date 2023-05-30 Time 10:17 Sent To  
Notes
2023-05-30 10:18:191. PROPOSAL FOR 831 N RAILROAD AVENUE HAS BEEN
 SUBMITTED FOR FORMAL SITE PLAN APPROVAL AND HAS NOT
 RECEIVED SAID APPROVAL.
 ZONING STAFF CANNOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-18 (Z22070025).
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By CKimmerl Date 2023-03-09 Time 17:04 Rev Time 0.00
Received By ckimmerl Date 2023-03-09 Time 15:59 Sent To  
Notes
2023-03-09 17:04:331. PROPOSAL FOR 831 N RAILROAD AVENUE HAS BEEN
 SUBMITTED FOR FORMAL SITE PLAN APPROVAL AND HAS NOT
 RECEIVED SAID APPROVAL.
 ZONING STAFF CANNOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-18 (Z22070025).
  
 2. PLEASE PROVIDE SITE SURVEY.
  
 3. APPLICATION AND PROJECT SCOPE SPEAKS TO NEW GROUNDUP
 BUILDING CONSTRUCTION, PLEASE PROVIDE DEMOLITION SHEETS
 OR SUBMIT FOR A SEPARATE DEMOLITION PERMIT.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426
  