Plan Review Stops For Permit 23020290 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-03-20 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-03-20 |
Time |
10:29 |
Sent To |
|
|
Notes |
2023-03-20 10:30:33 | PLAN ADDRESS UPDATED, I UPDATED APPLICATION FORM AND | | PERMIT TO THE CORRECT ADDRESS. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-02-09 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-02-09 |
Time |
06:53 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-02-09 |
Time |
06:53 |
Sent To |
|
|
Notes |
2023-02-09 06:57:25 | JUNIOR SUITE 1B WAS ASSIGNED THE ADDRESS OF 2777 S | | DIXIE HWY WITH THE PCN 74434333480010000, PLEASE UPDATE | | PLANS AND APPLICATION FORM TO REFLECT THE CORRECT | | ADDRESS. THE ADDRESS PROVIDED OF 2751 S DIXIE HWY IS | | THE PARCEL ADDRESS AND DOES NOT CORRELATE WITH ANY | | BUILDING OR SUITE. PLEASE CONTACT [email protected] | | OR CALL 561-805-6659 |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-27 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-27 |
Time |
11:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-03-20 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-03-20 |
Time |
08:30 |
Sent To |
|
|
Notes |
2023-04-18 11:14:45 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 23020290 | | | | REVIEWED: 4/18/2023 | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC BUILDING | | FBC EXISTING BUILDING | | | | COMMENTS: PASSED WITH PROVISO-INFORMATION TO BE | | COLLECTED DURING INSPECTION PROCESS | | | | AS PER 2017 WPB AMEND 107.2.1 CLARIFY SOCPE OF WORK IN | | REGARDS TO: | | | | | | 1. PROVIDE NORTH EXTERIOR ELEVATION SHOWING | | ACCESSIBLITY TO THE PROPOSED COMMERCIAL SPACE | | 2. CLEARLY DEFINE THE ACCESSIBILITY PATH TO THE PARKING | | AND SIDEWALK FROM THE DOUBLE DOOR ENTRANCE LABELED EX-1 | | 3. ELEVATE EXTERIOR DINING SPACE AND ENTRANCE ON ALL | | SIDES. SHOW CORRESPONDING ELEVATION FROM EXTERIOR | | PARKING ELEVATION TO SIDEWAL TO EXTERIOR DINING | | SPACE-INDICAPE N.G.V.D.ELEVATIONS ON PLAN SHEET A210 AS | | WELL | | IF ANY STEPS OR RAMP ARE PART OF THE ACCESS/EGRESS | | PLEASE SHOW ON PLAN AND SURVEY. | | 4. CLARIFY LINK TO EXISTING EXTERIOR CONCRETE PLAZA AND | | EXTERIOR DINING ROOM 100. | | | | NOTES: | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | HESITATE TO CONTACT ME | | | | LOUIS BOND, AIA | | BUILDING PLANS EXAMINER II | | DEVELOPMENT SERVICES DEPT. | | BUILDING DIVISION | | 401 CLEMATIS STREET | | WEST PALM BEACH, FLORIDA 33401 | | PH: 561-805-6729 | | FX: 561-805-6676 | | EMAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-27 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-27 |
Time |
14:59 |
Sent To |
|
|
Notes |
2023-02-27 15:00:45 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 23020290 | | | | REVIEWED: FEBRUARY 27, 2023 | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC BUILDING | | FBC EXISTING BUILDING | | | | COMMENTS: | | | | 1) PROVIDE HANDICAP CLEAR PATH TO BAR, APPROPRIATE | | SECTION AND BETTER LOCATION FOR HANDICAP SPACE @ BAR. | | 2) PROVIDE HANDICAP TEMPLATE SHOWING CLEAR ACCESSIBLE | | PATH FOR SEATING IN DINING AREAS. | | 3) UPDATE ALL SHEETS AS PER ADDRESS COMMENT. | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | HESITATE TO CONTACT ME | | | | LOUIS BOND, AIA | | BUILDING PLANS EXAMINER II | | DEVELOPMENT SERVICES DEPT. | | BUILDING DIVISION | | 401 CLEMATIS STREET | | WEST PALM BEACH, FLORIDA 33401 | | PH: 561-805-6729 | | FX: 561-805-6676 | | EMAIL: [email protected] | | | | | | NOTES: | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-03-24 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-03-24 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-02-20 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-02-20 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-02-20 |
Time |
11:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2023-03-20 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
2023-03-20 |
Time |
|
Sent To |
|
|
Notes |
2023-03-17 08:50:42 | FIRE PROVISO COMMENTS: | | | | (1) THE PROVISIONS DESCRIBED FOR LOCKING MECHANISMS ON | | EXTERIOR EXIT DOORS ARE PERMITTED TO BE REVOKED BY THE | | AUTHORITY HAVING JURISDICTION. NFPA 101, 7.2.1.5.5.2 | | | | (2) EMERGENCY LIGHTING THAT COMPLIES WITH NFPA 101 7.9 | | AND EXIT SIGNAGE THAT COMPLIES WITH NFPA 101 7.10 SHALL | | BE INSTALLED IN OCCUPIABLE AREAS INCLUDING INSIDE | | FREEZERS AND COOLERS. | | | | (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS BY PROPERLY LICENSED | | AND QUALIFIED CONTRACTORS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-02-09 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2023-02-09 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
2023-02-09 |
Time |
|
Sent To |
|
|
Notes |
2023-02-09 12:24:00 | FIRE PROVISO COMMENTS: | | | | (1) THE PROVISIONS DESCRIBED FOR LOCKING MECHANISMS ON | | EXTERIOR EXIT DOORS ARE PERMITTED TO BE REVOKED BY THE | | AUTHORITY HAVING JURISDICTION. NFPA 101, 7.2.1.5.5.2 | | | | (2) EMERGENCY LIGHTING THAT COMPLIES WITH NFPA 101 7.9 | | AND EXIT SIGNAGE THAT COMPLIES WITH NFPA 101 7.10 SHALL | | BE INSTALLED IN OCCUPIABLE AREAS INCLUDING INSIDE | | FREEZERS AND COOLERS. | | | | (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS BY PROPERLY LICENSED | | AND QUALIFIED CONTRACTORS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-03-20 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-03-20 |
Time |
09:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-13 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-13 |
Time |
15:39 |
Sent To |
|
|
Notes |
2023-02-13 16:24:38 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 23020290 | | 2/13/23 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P2.1: INDICATE THE MEANS OF PROVIDING | | COMBUSTION AIR FOR THE GAS-FIRED COOKING APPLIANCES- | | SEC. 304.1 FBC FG. PLEASE INCLUDE CALCULATIONS. | | | | 2) P2.1 & P2.2: PROVIDE A GAS WATER HEATER DIRECT VENT | | EXHAUST AND INTAKE DIAGRAM SHOWING THE TYPES AND SIZES | | OF THE VENT AND DUCT, THE VENT AND DUCT RUN LENGTHS, | | AND TERMINATION LOCATIONS- SECS. 503.2.3, 503.8, AND | | 624.1 FBC FG. | | | | 3) THE ENERGY EFFICIENCY REPORT DOES NOT PROVIDE | | COMPLIANCE DATA FOR THE WATER HEATERS- TABLE C404.2 FBC | | EC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-03-27 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-03-27 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-03-15 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-27 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-27 |
Time |
15:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-03-22 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-03-22 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-03-22 |
Time |
07:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-02-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-16 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-16 |
Time |
11:41 |
Sent To |
|
|
Notes |
2023-02-16 11:42:01 | 1ST REVIEW FMC | | PERMIT: 23020290 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT | | REFRIGERATION EQUIPMENT (WALK-IN COOLER AND FREEZER) | | WILL REQUIRE A SEPARATE PERMIT APPLICATION AND A | | SEPARATE REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS | | PERMIT. | | | | 2) SHEETS M1.2 AND M1.1: PROVIDE ON THE DRAWING HOW THE | | MECHANICAL UNITS ON THE ROOF AND EQUIPMENT DECK WILL BE | | ACCESSED FOR SERVICE AND REMOVAL. FMC 306.5 | | | | 3) SHEET M1.2: PROVIDE THE GUARD REQUIREMENTS FOR | | EQUIPMENT THAT IS WITHIN 10 FEET OF THE ROOFS EDGE. FMC | | 304.11 | | | | 4) SHEET M1.1: SHOW THAT THE O/A DUCT TERMINATIONS | | KEYNOTES 1 AND 2, WILL MEET THE REQUIREMENTS OF FMC | | 401.4 INTAKE OPENING LOCATION | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-03-20 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-03-20 |
Time |
09:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-13 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-10 |
Time |
14:14 |
Sent To |
|
|
Notes |
2023-02-13 15:39:01 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 23020290 | | 2/13/2023 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET T: THE INDEX ON THE TITLE SHEET SHOWS SHEETS | | P0.1 & P0.2 WHICH WERE NOT INCLUDED WITH THE PLAN SET | | FOR REVIEW. A COMPLETE REVIEW OF THE PLANS CANNOT BE | | ACCOMPLISHED WITHOUT A COMPLETE SET OF PLUMBING PLANS- | | SEC. 107.2.1 WPB. IT APPEARS THAT THE PLUMBING FIXTURE | | AND EQUIPMENT SCHEDULES ARE ON THOSE MISSING PLANS. | | | | 2) SHEETS A211, P1.1 & P2.3: THE FLOOR SINKS RECEIVING | | DRAINAGE FROM ICE BINS #45 & 57 SHALL DISCHARGE INTO | | THE SANITARY SYSTEM AND NOT THE GREASE WASTE- SEC. | | 1003.3.1 FBC P. | | | | 3) P2.2 & P3.1: A MEANS OF LIMITING THE HOT WATER | | TEMPERATURE FROM THE WATER HEATERS OTHER THAN THE | | THERMOSTATS SHALL BE PROVIDED- SEC. 607.1. 1 FBC P. | | TYPICALLY A MASTER THERMOSTSTIC MIXING VALVE WILL BE | | INSTALLED. THIS REQUIREMENT IS IN ADDITION TO THE | | MIXING VALVES PROVIDED AT THE SINKS. PLEASE PROVIDE A | | DETAIL TO SHOW COMPLIANCE. | | | | 4) P3.1: CORRECT THE GREASE WASTE CALCULATIONS SHOWING | | ICE MACHINE AND HAND SINK DRAINAGE INTO THE GREASE | | INTERCEPTOR. THE PLANS ARE CORRECTLY INDICATING THE | | DRAINAGE INTO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P. | | | | 5) P1.1 & P2.3: PLEASE SHOW EXISTING OR NEW CLEANOUTS | | WILL BE INSTALLED AT THE AT THE JUNCTION OF THE | | SANITARY BUILDING DRAIN AND SEWER LINE- SEC. 708.1.3 | | FBC P. | | | | 6) A210: THERE APPEARS TO BE NUMEROUS ACCESSIBLE | | PLUMBING FIXTURE DETAILS MISSING INCLUDING THE | | FOLLOWING ITEMS- FBC ACC: | | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- | | SEC. 604.3. | | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- | | SEC. 606.2. | | C) TURNING SPACE DIAMETERS- SEC. 304.3. | | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE | | WALLS- SEC. 604.2. | | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED | | FLOORS- SEC. 604.4. | | F) HEIGHTS OF THE LAVATORY SINK RIMS FROM THE FINISHED | | FLOORS- SECTION 606.3. | | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | THE REFLECTIVE SURFACES- SEC. 603.3 | | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | BARS FOR THE WATER CLOSETS- SECS 604.5 & 609.4, FIGURES | | 604.5.1 & 604.5.2. | | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC. | | 604.6. | | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE | | 604.7. | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. | | 606.2. | | | | 7) THE ENERGY EFFICIENCY REPORT DOES NOT PROVIDE PIPING | | SYSTEM COMPLIANCE DATA- SEC. C404.4 FBC EC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-03-20 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-03-20 |
Time |
08:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-27 |
Time |
12:09 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-27 |
Time |
12:09 |
Sent To |
|
|
Notes |
2023-02-27 12:11:29 | ARCHITECT DIGITAL SIGNATURE APPROVED | 2023-02-16 11:42:43 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | 2023-02-13 16:32:02 | PLUMBING AND GAS PLAN DIG.SIGS. APPROVED. |
|
|