Plan Review Stops For Permit 23020210 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2023-02-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-02-14 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-02-14 |
Time |
11:55 |
Sent To |
|
|
Notes |
2023-02-14 11:56:25 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-12 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-12 |
Time |
07:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2023-04-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-04-05 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-04-05 |
Time |
09:58 |
Sent To |
|
|
Notes |
2023-04-05 10:18:24 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW: | | | | FAILED PLAN REVIEW: | | | | AN ASBESTOS ACKNOWLEDGEMENT LETTER IS REQUIRED. A | | MITIGATION REPORT IS NOT REQUIRED | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | ES/ENVIRONMENTAL-HEALTH/AIR- | | QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-02-24 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-02-24 |
Time |
13:31 |
Sent To |
|
|
Notes |
2023-02-24 13:34:27 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW: | | | | FAILED PLAN REVIEW: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | ES/ENVIRONMENTAL-HEALTH/AIR- | | QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-28 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-27 |
Time |
09:24 |
Sent To |
|
|
Notes |
2023-07-28 11:06:36 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | A SEWER LATERAL CAPPING PERMIT NEEDS TO BE CLOSED OUT | | PRIOR TO APPROVAL OF DEMO PERMIT. | | PLEASE INFORM ME WHEN THE PLUMBING FINAL FIELD | | INSPECTION (#703) FOR THE SEWER LATERAL CAPPING HAS | | BEEN APPROVED AND I WILL ADJUST THE DEMO PERMIT | | BUILDING REVIEW STATUS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-12 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-12 |
Time |
07:50 |
Sent To |
|
|
Notes |
2023-07-12 07:51:08 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703. | | A SEPARATE PLUMBING PERMIT (TURN AROUND PERMIT) AND A | | FINAL FIELD INSPECTION OF THE CAPPING ARE REQUIRED FOR | | THE SEWER LATERAL CAPPING. THIS NEEDS TO BE COMPLETED | | PRIOR TO DEMO PERMIT ISSUANCE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-04-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-04-05 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-04-05 |
Time |
09:58 |
Sent To |
|
|
Notes |
2023-04-05 10:18:49 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC). | | SEE ELECTRIC REVIEW. | | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) | | RELEASE OF SERVICE CONFIRMATION | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | DEPARTMENT, REQUEST FOR METER PULL, ON | | THEIR FORM "DEMOLITION APPLICATION" | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703. | | 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART | | MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS | | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR | | THE FORM TO [email protected]. | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-02-24 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-02-24 |
Time |
13:31 |
Sent To |
|
|
Notes |
2023-02-24 13:37:12 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC). | | SEE ELECTRIC REVIEW. | | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) | | RELEASE OF SERVICE CONFIRMATION | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | DEPARTMENT, REQUEST FOR METER PULL, ON | | THEIR FORM "DEMOLITION APPLICATION" | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703. | | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST | | CONTROL COMPANY STATING THAT | | DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED | | FOR RODENTS. | | 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART | | MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS | | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR | | THE FORM TO [email protected]. | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-25 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-25 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-07-10 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-07-10 |
Time |
08:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2023-04-05 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-04-05 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-04-05 |
Time |
11:19 |
Sent To |
|
|
Notes |
2023-04-05 11:20:13 | SEE PREVIOUS COMMENT |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-02-24 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-24 |
Time |
15:51 |
Sent To |
|
|
Notes |
2023-02-24 15:52:16 | 2/24/23 SENT EMAIL REQUESTING ELECTRICAL APPLICATION. | | MP | | | | WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | APPLICATION FOR APPROVAL. THIS IS A BUILDING DEPARTMENT | | POLICY TO ENSURE ELECTRICAL SAFETY DURING DEMOLITION. | | PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION FROM A | | LICENSED ELECTRICAL CONTRACTOR TO [email protected], | | [email protected], AND [email protected] . WHEN WE | | RECEIVE THE APPLICATION THE ELECTRICAL REVIEWERS WILL | | APPROVE THE PLAN REVIEW. | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2023-07-24 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2023-07-24 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
Sent By |
sberglun |
Date |
2023-07-21 |
Time |
07:19 |
Rev Time |
0.00 |
Received By |
sberglun |
Date |
2023-07-21 |
Time |
07:19 |
Sent To |
|
|
Notes |
2023-07-21 07:19:47 | SEE COMMENTS UNDER 23020206 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-04-07 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-04-07 |
Time |
14:47 |
Sent To |
|
|
Notes |
2023-04-07 14:48:18 | REPEATED COMMENT: | | | | PASSED WITH PROVISO: | | | | THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS | | PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES, | | YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL | | BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR | | DEMOLITION WORK. INFORMATION CAN BE FOUND HERE: | | HTTP://WWW.SUNSHINE811.COM/ | | | | PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED | | BY BUILDING DEPT. - STORMWATER POLLUTION PREVENTION | | PLAN, AND UTILITY SIGNOFFS - WATER/SEWER, PEST, FPL, | | FPU, ASBESTOS ETC. | | | | TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN | | REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND | | WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT | | FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING | | BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN | | REVIEW TIME. | | | | ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DONT | | UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST | | PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO | | DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE | | AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN | | REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES | | WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S | | ERVICES/PERMITS AND SEE WHERE CAN I FIND MY PLAN REVIEW | | COMMENTS ONLINE? FOR INSTRUCTIONS. | | | | FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON | | WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION | | TEAM MEMBER WILL HELP YOU. | | | | THANKS, | | LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR, | | ENGINEERING SERVICES DEPARTMENT (561) 494-1085 | | [email protected] | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2023-02-13 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2023-02-13 |
Time |
|
Rev Time |
|
Received By |
rrossano |
Date |
2023-02-13 |
Time |
|
Sent To |
|
|
Notes |
2023-02-13 11:13:00 | PASSED WITH PROVISOS: | | | | THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS | | PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES, | | YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL | | BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR | | DEMOLITION WORK. INFORMATION CAN BE FOUND HERE: | | HTTP://WWW.SUNSHINE811.COM/ | | | | PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED | | BY BUILDING DEPT. - STORMWATER POLLUTION PREVENTION | | PLAN, AND UTILITY SIGNOFFS - WATER/SEWER, PEST, FPL, | | FPU, ASBESTOS ETC. | | | | TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN | | REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND | | WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT | | FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING | | BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN | | REVIEW TIME. | | | | ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DON???T | | UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST | | PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO | | DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE | | AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN | | REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES | | WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S | | ERVICES/PERMITS AND SEE ???WHERE CAN I FIND MY PLAN | | REVIEW COMMENTS ONLINE???? FOR INSTRUCTIONS. | | | | FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON | | WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION | | TEAM MEMBER WILL HELP YOU. | | | | THANKS, | | RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES | | DEPT., 561-494-1098, FAX: 561-494-1116 [email protected] | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2023-04-12 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2023-04-12 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2023-04-12 |
Time |
15:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-02-23 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-02-23 |
Time |
10:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-28 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-21 |
Time |
16:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-07-21 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-07-21 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-07-07 |
Time |
08:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-05-03 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-03-29 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-02-28 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-02-28 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-02-09 |
Time |
11:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2023-07-28 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-28 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-28 |
Time |
11:12 |
Sent To |
|
|
Notes |
2023-07-28 11:26:34 | SIGNATURE REVIEW DENIED: | | | | THE SUBMITTED SITE PLAN (SHEET C-100) 3RD VERSION DOES | | NOT HAVE 3RD PARTY VERIFIABLE DESIGN PROFESSIONAL | | SIGNATURE. | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | VERIFIED) PLAN: | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | FEEL FREE TO CONTACT ME AT 561 805 6673. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-04-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-04-05 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-04-05 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-02-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-02-24 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-02-24 |
Time |
13:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-07-25 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-07-25 08:58:10 | SEE PROVISOS UNDER PERMIT NUMBER 23020205. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-07-18 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-07-18 16:57:18 | SEE PROVISOS UNDER PERMIT NUMBER 23020205. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-05-02 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2023-05-02 |
Time |
17:26 |
Sent To |
|
|
Notes |
2023-05-02 17:26:43 | FAILED | | | | 1) REVISED COMMENT: PRIOR TO THE APPROVAL OF THIS | | DEMOLITION PERMIT, THE TREE ALTERATION PERMIT THAT HAS | | BEEN SUBMITTED TO THE CITY'S PLANNING DIVISION MUST BE | | APPROVED. NOTE: THE TREE DISPOSITION IS NOT REVIEWED AS | | PART OF THE DEMOLITION PERMIT. | | | | 2) THIS DEMOLITION PERMIT DOES NOT PERMIT THE | | DEMOLITION OF ANYTHING OUTSIDE OF THE PROPERTY LINE | | EXCEPT FOR THE REMOVAL OF THE AERIAL WALKWAY OVER | | HIBISCUS STREET. | | | | 3) ANY FEATURES OUTSIDE OF THE PROPERTY LINE SHOWN ON | | THE SURVEY/DEMOLITION PLAN, TO INCLUDE FOOTERS, LIGHT | | POLES, CURBS, ETC., WILL REQUIRE AN APPROVED | | RIGHT-OF-WAY PERMIT PRIOR TO REMOVAL. PROVIDE A COPY OF | | THE APPROVED RIGHT-OF-WAY PERMIT. | | | | 4) PROVIDE A COPY OF THE PAID INVOICE FOR THE REMOVAL | | OF THE PARKING METERS ON SOUTH ROSEMARY AVENUE AND THE | | BAGGING OF THE PARKING METERS ON GARDENIA STREET. | | | | 5) PRIOR TO THE APPROVAL OF THIS DEMOLITION PERMIT, THE | | DEMOLITION MINOR PLANNED DEVELOPMENT AMENDMENT THAT HAS | | BEEN SUBMITTED TO THE CITY'S PLANNING DIVISION MUST BE | | APPROVED. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
Sent By |
ESchneid |
Date |
2023-02-27 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2023-02-27 |
Time |
16:22 |
Sent To |
|
|
Notes |
2023-02-27 16:22:47 | FAILED | | | | 1) CURRENTLY, THE BUILDING MAY NOT BE DEMOLISHED UNLESS | | THE SITE PLAN FOR THE NEW BUILDING HAS BEEN APPROVED BY | | THE CITY COMMISSION. AN AMENDMENT TO ALLOW DEMOLITION | | WITHOUT AN APPROVED SITE PLAN HAS BEEN SUBMITTED TO THE | | PLANNING DIVISION. UNTIL EITHER A SITE PLAN FOR THE | | PROPERTY IS APPROVED OR THE AMENDMENT TO PERMIT | | DEMOLITION WITHOUT A SITE PLAN ARE APPROVED, ZONING | | APPROVAL OF THIS PERMIT WILL NOT BE GRANTED. | | | | 2) PROVIDE A SURVEY THAT SHOWING THE PROPERTY LINE. THE | | PROPERTY LINE ON THE SITE PLAN MUST MATCH THE SURVEY. | | | | 3) ANY FEATURES OUTSIDE OF THE PROPERTY LINE SHOWN ON | | THE SURVEY, TO INCLUDE FOOTERS, LIGHT POLES, ETC., WILL | | REQUIRE AN APPROVED RIGHT-OF-WAY PERMIT PRIOR TO | | REMOVAL. PROVIDE A COPY OF THE APPROVED RIGHT-OF-WAY | | PERMIT. | | | | 4) THE PLANS SHOW THE RELOCATION OF THE EXISTING | | BRIGHTBIKE STATION LOCATION. YOU MUST PROVIDE THE | | AGREEMENT FROM BRIGHTBIKE THAT THEY ARE PERMITTING THE | | REMOVAL OF THE BICYCLE STATION FROM THIS LOCATION. | | ADDITIONALLY, YOU MUST PROVIDE A LOCATION APPROVED BY | | THE CITY'S PLANNING DIVISION FOR THE STATION'S | | RELOCATION. | | | | 5) PRIOR TO THE APPROVAL OF THIS DEMOLITION PERMIT, A | | TREE ALTERATION PERMIT SHOWING THE DISPOSITION OF ALL | | TREES CURRENTLY ON AND ADJACENT TO THE SITE MUST BE | | SUBMITTED TO AND APPROVED BY THE CITY'S PLANNING | | DIVISION. THE TREE DISPOSITION IS NOT REVIEWED AS PART | | OF THE DEMOLITION PERMIT. | | | | 6) PROVIDE A COPY OF THE PAID INVOICE FOR THE REMOVAL | | OF THE PARKING METERS ON SOUTH ROSEMARY AVENUE AND THE | | BAGGING OF THE PARKING METERS ON HIBISCUS STREET. | | | | 7) THE TEMPORARY CONSTRUCTION FENCE REQUIRES A SEPARATE | | PERMIT WITH PLANS. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|
|