2023-03-27 13:16:52 | RESIDENTIAL (R2)SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23020061 |
| 701 S OLIVE AVE |
| |
| |
| NOTE: |
| PLEASE UPLOAD EACH REQUIRED TEST IN A SEPARATE PDF |
| FILE, DON'T SEND THEM ALL TOGETHER IN ONE PDF. |
| |
| |
| |
| PREVIUS COMMENT: |
| 1- PLANS SUBMITTED NEED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT SHOWN ON PLANS AS REQUIRED BY 61G1-16.001FAC |
| AND CHAPTER 481 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS |
| FOR PUBLIC RECORDS. |
| NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ARCHITECT'S |
| VERIFIABLE DIGITAL SIGNATURE. |
| |
| RESPONSE: |
| THIS WAS DISCUSSED WITH JOHN MATTEO ON 03/17/23 OVER |
| THE PHONE. PLEASE CONTACT ME TO GO OVER THIS ITEM. |
| |
| 2- OK. |
| EXISTING STAIRS HAVE CERAMIC TILE. NO CHANGE IN FINISH |
| FLOORING. NEW CERAMIC TILE INSTALLATION TO BE |
| NON-SLIPPERY AND INSTALLATION TO MATCH EXISTING ONE, |
| INCLUDING VISUAL CONTACT ON TREAD NOSINGS (SEC. 504 |
| FBC-ACCESSIBILITY). |
| |
| |
| PREVIUS COMMENT: |
| 3- SOUND TRANSMISSION. HARD FLOORING (CERAMIC TILE) |
| NEEDS TO COMPLY WITH THE SOUND TRANSMISSION |
| REQUIREMENTS OF SEC. 1207.1 FBC-BUILDING. NEED TO |
| PROVIDE THE FOLLOWING FOR THE CERAMIC TILE SOUND |
| INSULATION UNDERLAYMENT: |
| |
| (A)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| |
| (B)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| |
| RESPONSE TO ITEM #3: |
| INFORMATION SUBMITTED WAS NOT THE ONE REQUESTED. TEST |
| INFORMATION SUBMITTED IS FOR ASTM-C-627 STANDARD. NEED |
| TO PROVIDE THE TESTS IN ACCORDANCE WITH THE TEST |
| STANDARDS REQUIRED BY ITEMS (A) AND (B) ABOVE. |
| |
| PREVIUS COMMENT: |
| 4- CERAMIC TILE SOUND TRANSMISSION UNDERLAYMENT: |
| PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| (2020). |
| |
| RESPONSE: |
| ICC INTERPRETATION LETTER SUBMITTED DOESN'T APPLY TO |
| THE REQUESTED INFORMATION. THE FINISH FLOOR FOR THIS |
| PROJECT IS NOT VINYL. THE REQUESTED INFORMATION IS FOR |
| THE CONCEALED INSULATION USED FOR THE SOUND INSULATION |
| OF THE CERAMIC TILE INSTALL ION. SEC. 720.2 |
| FBC-BUILDING. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |