Plan Review Details - Permit 23020041
Plan Review Stops For Permit 23020041
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By cpuell Date 2023-05-17 Time 13:35 Rev Time 0.00
Received By cpuell Date 2023-05-17 Time 13:35 Sent To  
Notes
2023-05-17 13:35:55PARCEL READRESSED 1040, 1060 & 1080 N RAILROAD AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-04 Cont ID  
Sent By cpuell Date 2023-02-04 Time 06:25 Rev Time 0.00
Received By cpuell Date 2023-02-04 Time 06:25 Sent To  
Notes
2023-02-04 06:26:41PARCEL NEEDS TO BE READDRESSED SO THAT THE ENTRANCES ON
 THE GROUND FLOOR FALLS IN LINE WITH THE CITY'S ROAD
 CENTER LINES. ADDRESSES THAT NEED TO BE ESTABLISHED
 WOULD BE FOR THE BUILDING ITSELF, THE GROUND FLOOR
 COMMERCIAL SPACE AND THE UNITS ON THE UPPER FLOORS.
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO
 WORK ON THE READDRESSING ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By swelter Date 2023-03-10 Time 12:44 Rev Time  
Received By swelter Date   Time   Sent To  
Notes
2023-03-10 12:44:38SEE MASTER PERMIT# 23020041

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 11:34 Sent To  
Notes
2023-07-21 11:44:31NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE STORM WATER DRAINAGE AWAY FROM THE
 BUILDING AND AWAY FROM THE ADJACENT PROPERTY - PROVIDE
 THE CIVIL PLANS IF THEY WILL PROVIDE THE INFO NEEDED -
 PLEASE SHOW THE FOLLOWING ITEMS ON THE SITE PLAN PER -
 FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 2) PLEASE SHOW THE SOUTH EXTERIOR WALL TO BE 1 HR FIRE
 RATED PER - FBC TABLE 602
  
 3) PLEASE SHOW THE PERCENTAGE CALCULATIONS FOR THE
 EXTERIOR SOUTH WALL SQUARE FOOTAGE VERSES THE OPENINGS
 TO COMPLY WITH FBC 705.8.1 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8. (PER STORY)
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-19 Cont ID  
Sent By rmcphers Date 2023-05-19 Time 09:40 Rev Time 0.00
Received By rmcphers Date 2023-05-19 Time 09:03 Sent To  
Notes
2023-05-19 09:37:32NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PROVIDE THE CIVIL PLANS IF THEY WILL PROVIDE THE
 INFO NEEDED - PLEASE SHOW THE FOLLOWING ITEMS ON THE
 SITE PLAN PER - FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 2) ACCESSIBLE PARKING SPACE LOCATION PLEASE SHOW THE
 ACCESSIBLE PATH FROM THE ACCESSIBLE PARKING SPACE TO
 THE ACCESSIBLE ENTRY - FBC A208.3.1 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
  
 3) CANNOT HAVE A RAMP IN THE 5 FOOT PARKING ACCESS
 AISLE - FBC A 502.4 FLOOR OR GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
  
 4) DRAWING A.104 SHOWS THE RESTROOM WALL COVERING AS
 "WPT" (TILE) - DRAWING A.600 SHOWS THE RESTROOM WALL
 COVERING AS "WVP" (WOOD) - PLEASE CLEARIFY THE DRAWINGS
 SHOULD MATCH - IF USING "WOOD" PLEASE PROVIDE DOCUMENTS
 THAT SHOW THE WOOD VENEER COMPLIES WITH FBC 1210.2.2
 WALLS AND PARTITIONS. WALLS AND PARTITIONS WITHIN 2
 FEET (610 MM) OF SERVICE SINKS, URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR,
  
 5) DRAWINGS SHOW THE BUILDING CONSTRUCTION TYPE AS IIB
 - PLEASE PROVIDE A NOTE ON THE DRAWINGS THAT THE
 EXTERIOR WOOD SHEATHING USED ON THE EXTERIOR WALL NEEDS
 TO BE FIRE RETARDANT PER FBC 603.1
  
 6) DRAWINGS LS.101, LS.102, A.101, A.102, A.600, A.602
 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By rmcphers Date 2023-02-16 Time 11:36 Rev Time 0.00
Received By rmcphers Date 2023-02-16 Time 08:25 Sent To  
Notes
2023-02-16 11:32:37NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE
 PUBLIC RIGHT-OF-WAY. FBC 3202.2
  
 2) DRAWING A-103 - BOTTOM AND TOP STAIR RAIL EXTENSIONS
 ARE SHOWN AS TURNING - STAIR HANDRAIL EXTENSIONS CANNOT
 TURN IF THE STAIRS DO NOT CONTINUE - WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY FBC 1014.6
  
 3) PLEASE SHOW EXTERIOR "CASEMENT COMPOSITE WALL PANEL
 SYSTEM" ATTACHMENT DETAILS OR PROVIDE A PRODUCT
 APPROVAL. FBC 1609
  
 4) PLEASE SHOW EXTERIOR "METAL WALL PANEL" ATTACHMENT
 DETAILS OR PROVIDE A PRODUCT APPROVAL. FBC 1609
  
 5) PLEASE SHOW THE FOLLOWING ITEMS ON THE SITE PLAN PER
 - FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 6) ACCESSIBLE PARKING SPACE LOCATION - FBC A208.3.1
 PARKING SPACES COMPLYING WITH 502 THAT SERVE A
 PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE
 SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE
 COMPLYING WITH 206.4.
  
 7) ACCESSIBLE RESTROOM = DRAWING A-104 MENS ROOM DOOR
 IS SHOWN SWINGING INTO THE CLEAR FLOOR SPACE - FBC
 603.2.3 WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING.
  
 8) PLEASE PROVIDE A SURVEY.
  
 9) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, PARKING LOT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-07-28 Cont ID  
Sent By mpeterso Date 2023-07-28 Time 13:15 Rev Time 0.00
Received By mpeterso Date 2023-07-28 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-26 Cont ID  
Sent By mpeterso Date 2023-05-26 Time 11:00 Rev Time 0.00
Received By mpeterso Date 2023-05-26 Time 10:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 08:24 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 08:24 Sent To  
Notes
2023-02-15 08:35:28ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM. NEC 215.5
  
 2) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION. NEC
 215.5
  
 3) PLEASE PROVIDE AN ELECTRIC LIGHTING PLAN. FBC 107.2
  
 4) PLEASE PROVIDE A NOTE STAING , LOW VOLTAGE, FIRE
 ALRM, ACCESS CONTOL, SECURITY, AUDIO, VIDEO, SITE
 LIGHTING, SIGN, AND OTHER LOW VOLTAGE SYSTEM WIRING
 REQUIRE A SEPARATE PERMIT.
  
 5) PROVIDE A ROOF POWER PLAN AS APPLICABLE. FBC 107.2
  
 6) PROVIDE ACTUAL GROUNDING ELECTRODE AND OTHER
 GROUNDING CONDUCTOR SIZES FOR ELECTRICAL SERVICE. NOT
 JUST NEC CODE REFERENCES. NEC 250 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-05-25 Cont ID  
Sent By lquinone Date 2023-05-25 Time 07:20 Rev Time 0.00
Received By lquinone Date 2023-05-25 Time 07:20 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By rrossano Date 2023-02-07 Time   Rev Time  
Received By rrossano Date 2023-02-07 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-20 Cont ID  
Sent By pleduc Date 2023-07-20 Time   Rev Time 0.00
Received By pleduc Date 2023-07-20 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By pleduc Date 2023-05-19 Time   Rev Time 0.00
Received By pleduc Date 2023-05-19 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By pleduc Date 2023-02-06 Time   Rev Time 0.00
Received By pleduc Date 2023-02-06 Time 11:04 Sent To  
Notes
2023-02-06 11:26:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS 101- THERE APPEARS TO BE AN OCCUPANY LOAD
 OF 150 WITHIN THE PLAN LEGEND.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY & CH 7 MEANS OF
 EGRESS, THE OCCUPANY CLACULATION IS SQ FT / EITHER 7 OR
 15.
  
 EACH ASSEMBLY SPACE IS REQUIRED TO BE CALCULATED
 SEPARATLY AND RECORDED.
  
 PLEASE REVIEW AND PROVIDE THE SEPARATE CALCULATIONS OF
 THE AREA SERVED.
  
  
  
 2) THERE ARE INDICATIONS WITHIN THE DOOR SCHEDULE THAT
 DO NOT APPEAR TO MEET THE NFPA 101 CH 7, MEANS OF
 EGRESS & CH 12 NEW ASSEMBLY REQUIREMENTS FOR ASSEMBLY
 OCCUPANCIES.
  
 7.2.1.7* PANIC HARDWARE AND FIRE EXIT HARDWARE.
  
 7.2.1.7.1 WHERE A SIDE-HINGED OR PIVOTED-SWINGING DOOR
 ASSEMBLY IS
 REQUIRED TO BE EQUIPPED WITH PANIC OR FIRE EXIT
 HARDWARE, SUCH HARDWARE
 SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, WITH
 THE LENGTH OF THE
 ACTUATING PORTION OF THE CROSS BAR OR PUSH PAD NOT LESS
 THAN ONE-HALF
 OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND
 NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF
 (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND LATCHES
  
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAP TERS 22 AND 23, SHALL NOT BE EQUIPPED
 WITH ANY LOCKING DEVICE, SET SCREW,
 OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE OF THE
 LATCH WHEN PRESSURE
 IS APPLIED TO THE RELEASING DEVICE
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PLEASE REVIEW AND ENSURE THE PROPER EXIT HARDWARE IS
 PROVIDED AT EACH DOOR.
  
  
  
 3) SHEET LS 101- THERE IS AN INDICATION REGARDING THE
 KNOX BOX LOCATION BEING COORDINATED WITH PBC FIRE
 RESCUE.
  
 THAT IS THE INCORRECT JURISDICTION. WEST PALM BEACH
 FIRE DEPARTMENT IS THE CORRECT JURISDICTION.
  
 PLEASE REVIEW AND CORRECT.
  
  
 4) SHEETS FP - THERE IS AN INDICATION OF A FIRST FLOOR
 FIRE PROTECTION PLAN BUT NO INDICATION OF A SECOND
 FLOOR PLAN.
  
 FOR CLARIFICATION PURPOSES PLEASE PROVIDE A SECOND
 FLOOR PLAN OR JUSTIFICATION WHY FIRE SPRINKLER
 PROTECTION IS NOT BEING PROVIDED WITH CODE REFERENCES.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE. DELINEATE
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-19 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-09 Cont ID  
Sent By hmoser Date 2023-06-09 Time 09:11 Rev Time 0.00
Received By hmoser Date 2023-05-17 Time 17:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By aoliver Date 2023-03-13 Time 08:39 Rev Time 0.00
Received By aoliver Date 2023-02-03 Time 14:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By rmcphers Date 2023-02-16 Time 11:36 Rev Time 0.00
Received By rmcphers Date 2023-02-16 Time 11:36 Sent To  
Notes
2023-02-16 11:37:02PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-08-07 Cont ID  
Sent By hmoser Date 2023-08-07 Time 09:10 Rev Time 0.00
Received By hmoser Date 2023-08-07 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-06-09 Cont ID  
Sent By hmoser Date 2023-06-09 Time 09:08 Rev Time 0.00
Received By hmoser Date 2023-06-09 Time 07:02 Sent To  
Notes
2023-06-09 09:07:15PLAN DENIED
 1) PROVIED A EQUIPMENT SCHEDULE FOR THE AIR
 CONDITIONING
 UNITS ON THE PLAN SECTION 107.
 2) THERE WAS NO 2ND FLOOR MECHANICAL PLAN SUBMITTED.
 3) REFER TO SECTION 607.5.3 FIRE PARTITIONS FBC (M).
 MISSING A NUMBER OF FIRE DAMPERS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-07 Time 06:31 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 06:31 Sent To  
Notes
2023-02-07 06:32:251ST REVIEW FMC
 PERMIT: 23020041
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL DRAWINGS THAT SHOW THE
 SYSTEMS AND DUCTWORK THAT IS SPECIFIED ON SHEET M-600.
 FBC 107.3.5
  
 2) PROVIDE THE ENERGY CALCULATIONS FOR THE MECHANICAL
 DESIGN FOR THIS SHELL. FEC C402
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS SHELL DESIGN. FEC C403.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-20 Cont ID  
Sent By rwbrown Date 2023-07-20 Time 10:37 Rev Time 0.00
Received By rwbrown Date 2023-07-20 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-22 Cont ID  
Sent By rwbrown Date 2023-05-22 Time 07:46 Rev Time 0.00
Received By rwbrown Date 2023-05-22 Time 07:45 Sent To  
Notes
2023-05-22 07:51:451ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. DONE
  
 4. DONE
  
 5. ENGINEERING PERMITS ARE FOR THE RIGHT-OF-WAYS AND DO
 NOT REPLACE THE REQUIREMENTS FOR BUILDING PERMITS -
 2017 WPB AMENDS 107.3.5.1.3 - BE AWARE THAT IF
 IRRIGATION IS INSTALLED, IT WILL REQUIRE A SEPARATE
 PERMIT.
  
 6. ENGINEERING PERMITS ARE FOR THE RIGHT-OF-WAYS AND DO
 NOT REPLACE THE REQUIREMENTS FOR BUILDING PERMITS -
 2017 WPB AMENDS 107.3.5.1.3 - SITE PLAN SHOWING THE
 LOCATION OF THE WATER SERVICE, SEWER SERVICE, GREASE
 TRAPS, BACKFLOWS, ETC.
  
 7. DONE
  
 8. ENGINEERING PERMITS ARE FOR THE RIGHT-OF-WAYS AND DO
 NOT REPLACE THE REQUIREMENTS FOR BUILDING PERMITS -
 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE AT
 THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By rwbrown Date 2023-02-09 Time 12:45 Rev Time 0.00
Received By rwbrown Date 2023-02-09 Time 12:45 Sent To  
Notes
2023-02-09 13:02:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - PLEASE SHOW THE FIXTURE
 CALCULATIONS AND THE SHOW THAT YOU ARE PROVIDING THE
 MINIMUM NUMBER OF FIXTURES.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A RISER DIAGRAM
 THAT INCLUDES THE DRAIN, WASTE AND VENT SYSTEM AND THE
 WATER DISTRIBUTION SYSTEM.
  
 3. 2017 WPB AMENDS 107.3.5.1.3 - SHOW THE LOCATION OF
 THE WATER HEATER AND INCLUDE DETAILS FOR A MIXING VALVE
 PER FPC 607.1.1 INSTALLED AT THE HEAT SOURCE PER 613.1.
  
 4. 2017 WPB AMENDS 107.3.5.1.3 - SHOW A ROOF DRAINAGE
 PLAN INCLUDE GALLONS PER MINUTE, LEADER/DRAIN SIZES.
 DRAIN PIPING PLAN, OVERFLOW/SCUPPER SIZES ETC.
  
 5. 2017 WPB AMENDS 107.3.5.1.3 - BE AWARE THAT IF
 IRRIGATION IS INSTALLED, IT WILL REQUIRE A SEPARATE
 PERMIT.
  
 6. 2017 WPB AMENDS 107.3.5.1.3 - SITE PLAN SHOWING THE
 LOCATION OF THE WATER SERVICE, SEWER SERVICE, GREASE
 TRAPS, BACKFLOWS, ETC.
  
 7. 2020 FPC 607.2 - PROVIDE A CIRCULATING LOOP IF THE
 LENGTH OF THE HOT WATER SUPPLY EXCEEDS 50 FEET. IF A
 RETURN LOOP IS PROVIDED, THE RETURN SHALL BE IN
 COMPLIANCE WITH 2020 FPC 607.2.2 AND RETURN TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
  
 8. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-02-16 Cont ID  
Sent By rmcphers Date 2023-02-16 Time 11:37 Rev Time 0.00
Received By rmcphers Date 2023-02-16 Time 11:37 Sent To  
Notes
2023-02-16 11:37:32ROOFING SYSTEM TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 12:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-19 Cont ID  
Sent By rmcphers Date 2023-05-19 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2023-05-19 Time 10:18 Sent To  
Notes
2023-05-19 10:20:30SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS LS.101, LS.102, A.101, A.102, A.600, A.602
 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By mpeterso Date 2023-02-15 Time 08:40 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 08:40 Sent To  
Notes
2023-02-15 08:41:53SIGNATURE REVIEW FAILED
 1) SHEET A 602 DOES NOT DETAIL THE REQUIRED DIGITAL
 SIGNATURE OF THE EOR/AOR AS REQUIRED. PLEASE CORRECT AS
 OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2023-02-07 06:34:27MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By ckimmerl Date 2023-05-30 Time 10:22 Rev Time 0.00
Received By ckimmerl Date 2023-05-30 Time 10:20 Sent To  
Notes
2023-05-30 10:22:48PROPOSAL FOR 444 10TH STREET HAS BEEN SUBMITTED FOR
 FORMAL SITE PLAN APPROVAL AND HAS NOT RECEIVED SAID
 APPROVAL .
 ZONING STAFF CANNOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-17 - (Z22070024).
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By CKimmerl Date 2023-03-10 Time 16:35 Rev Time 0.00
Received By ckimmerl Date 2023-03-10 Time 16:32 Sent To  
Notes
2023-03-10 16:34:19SCOPE OF PROJECT DEMONSTRATES SUBSTANTIAL CHANGE IN
 STRUCTURE AND TRIGGERS THE PROVISIONS OF ARTICLE IV -
 SEC. 94-124 AND THE NONCOMFORMITIES SECTION OF ARTICLE
 XVI SEC. 94-515.
 THIS IS AN ALTERATION OR DEMOLITION WITH CONSTRUCTION
 OF 'NEW' STRUCTURE, THE NEW MUST BE BUILT IN COMPLIANCE
 WITH CODE PROVISIONS OF THE BPD-R DISTRICT.
  
 1. PLEASE PROVIDE A SITE SURVEY.
  
 2. PLEASE PROVIDE A SITE PLAN WITH SETBACKS ILLUSTRATED
 AND PROVIDE TABULAR DATA OR CALCULATIONS FOR BPD-R
 STANDARDS. RENOVATION AND ALTERATION MUST MEET
 SETBACKS, HEIGHT, BUILDING FOOTPRINT, ETC. FOR
 SUBDISTRICT.
  
 3. PROJECT PROPOSAL APPEARS TO DEMOLISH SINGLE-FAMILY
 STRUCTURE, PLEASE PROVIDE DEMOLITION SHEETS DETAILING
 FULL SCOPE.
  
 PROPOSAL FOR 444 10TH STREET HAS BEEN SUBMITTED FOR
 FORMAL SITE PLAN APPROVAL AND HAS NOT RECEIVED SAID
 APPROVAL .
 ZONING STAFF CANNOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-17 - (Z22070024).
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822-1426 [email protected]