2023-03-02 07:52:49 | 1ST BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: VALUE HAS BEEN INCREASED TO $78,058 PER THE ICC |
| BUILDING VALUATION DATA: |
| |
| 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| 2. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) |
| R401.2COMPLIANCE. |
| SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| THROUGH R404 LABELED MANDATORY. |
| |
| 3.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED |
| WINDOWS AND SGD. |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 4.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE |
| SPECIFICATION SHEETS OF A FLUID APPLIED MEMBRANE. |
| FBC R 703.4, FBC B 1405.4: |
| A FLASHING DETAIL OR SPECIFICATION IS REQUIRED. THIS |
| COMMENT CAN BE RESOLVED BY DOING ONE OF THE FOLLOWING: |
| |
| REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED |
| AND NOTE THE CODE REFERENCE ??? FBC R 703.4; FBC B |
| 1405.4: |
| EXAMPLE "FLASHING IN ACCORDANCE WITH FBC R 703.4/B |
| 1405.4 WILL BE INSTALLED". |
| PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS |
| MAY INCLUDE MORE THAN ONE OPTION |
| PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN |
| ONE |
| OPTION. |
| |
| 5.PROVIDE SMOKE ALARMS. |
| FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| BUILDING. |
| |
| SMOKE ALARMS |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| |
| 6. WIND LOAD DESIGN ON PAGE A-1.0 IS INCORRECT. (ASCE |
| 7-10) THE CURRENT DESIGN CRITERIA IS ASCE 7-16. PLEASE |
| CORRECT. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |
| |
| |