Plan Review Details - Permit 23011362
Plan Review Stops For Permit 23011362
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-04 Cont ID  
Sent By cthroop Date 2023-03-04 Time 08:30 Rev Time 0.00
Received By cthroop Date 2023-03-04 Time 08:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-25 Cont ID  
Sent By cthroop Date 2023-02-25 Time 08:00 Rev Time 0.00
Received By cthroop Date 2023-02-25 Time 07:33 Sent To  
Notes
2023-02-25 08:01:04NOTICE: BUILDING REVIEW APPROVAL IS PENDING THE
 APPROVAL OF THE SIGNATURE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-11 Cont ID  
Sent By cthroop Date 2023-02-11 Time 10:19 Rev Time 0.00
Received By cthroop Date 2023-02-11 Time 10:12 Sent To  
Notes
2023-02-11 10:20:01NOTICE: BUILDING REVIEW APPROVAL IS PENDING THE
 APPROVAL OF THE SIGNATURE REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-02 Cont ID  
Sent By fgiaquin Date 2023-02-02 Time 23:14 Rev Time 0.00
Received By fgiaquin Date 2023-02-02 Time 22:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-04 Cont ID  
Sent By cthroop Date 2023-03-04 Time 08:31 Rev Time 0.00
Received By cthroop Date 2023-02-27 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-25 Cont ID  
Sent By cthroop Date 2023-02-25 Time 08:03 Rev Time 0.00
Received By cthroop Date 2023-02-13 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-11 Cont ID  
Sent By cthroop Date 2023-02-11 Time 10:21 Rev Time 0.00
Received By cthroop Date 2023-01-30 Time 14:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-04 Cont ID  
Sent By cthroop Date 2023-03-04 Time 08:30 Rev Time 0.00
Received By cthroop Date 2023-03-04 Time 08:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-02-25 Cont ID  
Sent By cthroop Date 2023-02-25 Time 08:01 Rev Time 0.00
Received By cthroop Date 2023-02-25 Time 07:33 Sent To  
Notes
2023-02-25 08:03:362ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: SEPERATE THE PRE-CAST GENERATOR PAD DESIGN LOAD
 CALC'S FROM THE GENERATOR SPEC. PACKAGE. PROVIDE A
 VALID DIGITAL SIGNATURE OF THE ENGINEER ON THE
 GENERATOR PAD DESIGN.
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-11 Cont ID  
Sent By cthroop Date 2023-02-11 Time 10:20 Rev Time 0.00
Received By cthroop Date 2023-02-11 Time 10:13 Sent To  
Notes
2023-02-11 10:21:211ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PRE-CAST GENERATOR PAD DESIGN LOAD CALC'S
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-10 Cont ID  
Sent By VBroglia Date 2023-02-10 Time 14:30 Rev Time 0.00
Received By vbroglia Date 2023-02-10 Time 14:30 Sent To  
Notes
***NONE***