Plan Review Stops For Permit 23011196 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-03-10 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-03-10 |
Time |
09:51 |
Sent To |
|
|
Notes |
2023-03-10 09:53:10 | IN APRIL 2021 THE PARCEL WAS READDRESSED THE SOUTH | | BUILDING HAS THE ADDRESS OF 309 NOTTINGHAM BLVD AND THE | | NORTH BUILDING IS 311 NOTTINGHAM BLVD, THE PERMIT | | APPEARS TO BE FOR THE BUILDING WITH THE ADDRESS OF 309 | | NOTTHINGHAM BLVD. PLEASE UPDATE THE APPLICATION AND | | PLANS TO REFLECT THE CORRECT ADDRESS. FOR QUESTIONS | | CONTACT [email protected] OR CALL 561-805-6659 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-03-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-09 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-09 |
Time |
06:44 |
Sent To |
|
|
Notes |
2023-03-09 10:23:18 | 1ST BUILDING REVIEW | | RESULTS: CORRECTIONS NEEDED | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | PLANS EXAMINER II | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NFPA 70 2017 EDITION NEC 2017 | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | NOTICE: PROVISO ON PLAN PAGE S-3: A SEPERATE ROOFING | | PERMNIT IS REQUIRED. | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | SURVEY. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | FBC R401.3 SITE DRAINAGE | | | | 3.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED | | WINDOWS AND EXT. DOORS. | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | 4. ADDRESS: | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-02 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-28 |
Time |
14:03 |
Sent To |
|
|
Notes |
2023-03-02 09:00:45 | ELECTRIC REVIEW FAILED | | | | 1) IT APPEARS ELECTRICAL DRAWINGS ARE INCOMPLETE. NEW | | FLOOR PLAN DETAILS A KITCHEN, DEN, DINING ROOM, FRONT | | PORCH AND SECOND FLOOR BATHROOM, AND BEDROOMS ARE TO BE | | RENOVATED. ELECTRIC PLANS DO NOT DETAIL ALL WIRING THAT | | WILL BE MODIFIED OR ADDED. IN ADDITION, NOTES STATE | | THAT ALL EXTERIOR WALLS ARE TO BE INSULATED AND | | CONDUITS ARE TO BE INSTALLED IN THESE WALLS. PLEASE | | PROVIDE A COMPLETE ELECTRICAL PLAN AS APPLICABLE. | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL | | | | 2) PLEASE PROVIDE AN ELECTRICAL RISER DETAILING ALL | | EQUIPMENT, CONDUIT, CONDUCTORS, GROUNDING ELECTRODE | | SYSTEM, AND OVERCURRENT PROTECTION. | | | | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE | | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER | | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF | | THE FEEDERS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-03-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-09 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-02-14 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2023-03-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-09 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-09 |
Time |
06:44 |
Sent To |
|
|
Notes |
2023-03-09 08:11:10 | IMPACT FEES | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2023-02-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-21 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-21 |
Time |
14:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-02-16 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-16 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-16 |
Time |
12:16 |
Sent To |
|
|
Notes |
2023-02-16 12:26:03 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC P3107.1 - THE COMMON VENT SERVING THE LAV, | | BATHTUB, WASHER, AND LAUNDRY TUB IS NON-COMPLIANT. A | | COMMON VENT CAN ONLY SERVE FIXTURES ON THE SAME FLOOR. | | | | 2. 2020 FRC P3201.7 - THE TRAP SIZE SHOWN FOR THE | | WASING MACHINE IS 1 1/2" AND THE MINIMUM IS 2". | | | | 3. 2020 FRC P3107.1 - THE SHOWER UPSTAIRS CANNOT DRAIN | | DOWN ONTO THE LAVATORY AS EITHER A COMMON VENT. THEY | | WOULD HAVE TO BE ON THE SAME FLOOR LEVEL. | | | | 4. 2020 FRC P3108.2.1 - THE DOWNSTAIRS SHOWER AND WATER | | CLOSET ARE NOT VENTED TO CODE. ONLY ONE TRAPPED FIXTURE | | IS ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S | | CONNECTION TO THE WET VENT. YOU CURRENTLY HAVE 2 | | UPSTREAM (OF THE LAV THAT IS NOT VENTED CORRECTLY DUE | | TO THE SHOWER UPSTAIRS). | | | | 5. THE KITCHEN SINK IS INCORRECTLY LABELED AS A "LAV". | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2023-03-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-09 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-09 |
Time |
06:44 |
Sent To |
|
|
Notes |
2023-03-09 09:24:28 | PROVISO ON PLAN PAGE S-3: A SEPERATE ROOFING PERMIT IS | | REQUIRED. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-03-02 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-03-02 |
Time |
09:01 |
Sent To |
|
|
Notes |
2023-03-02 09:04:06 | SIGNATURE REVIEW FAILED | | | | 1) IT APPEARS ALL PLANS UPLOADE ARE COPIES OF AN | | EOR/AOR SIGNATURE AND SEAL. PLEASE CORRECT AS OUTLINED | | BELOW. | | | | THERE ARE ONLY TWO WAYS IN WHICH PLANS PREPARED BY AN | | ENGINEER OR ARCHITECT ARE ACCEPTABLE AND WILL PASS A | | SIGNATURE REVIEW. SEE THE DESCRIPTION BELOW. | | | | 1) PAPER DOCUMENTS SUBMITTED MUST HAVE A SEAL WITH A | | WET SIGNATURE. | | | | 2) DIGITALLY SUBMITTED DOCUMENTS MUST HAVE A SEAL WITH | | A DIGITAL SIGNATURE. PLEASE NOTE IT IS EXTREMELY | | IMPORTANT THAT ALL DIGITAL SIGNATURES ARE VERIFIABLE | | THROUGH ADOBE OR BLUEBEAM SOFTWARE | | | | DIGITALLY SUBMITTED DOCUMENTS ARE PREFERRED | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | DIGITALLY SEALED AND SIGNED. | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-02-28 |
|
|
Cont ID |
|
Sent By |
ASangele |
Date |
2023-02-28 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-02-28 |
Time |
10:27 |
Sent To |
|
|
Notes |
2023-02-28 10:29:34 | FAILED | | 2/28/2023 | | | | PLEASE PROVIDE A PROPERTY SURVEY WITH LABELED SETBACKS | | FOR THE PROPOSED PORCH AND BACK PATIO | | | | | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|