2023-02-02 11:18:48 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL15218-R6 |
| HAS BEEN REVISED TO FL15218-R8. PLEASE PROVIDE A |
| COMPLETE SET; IT COVERS MULTIPLE DESIGN PRESSURE |
| RATINGS. PLEASE SELECT CORRECT PLYWOOD THICKNESS, |
| FASTENER, DESIGN PRESSURE, FASTENER SPACING FOR TOP |
| EDGE/BOTTOM EDGE/CENTER ROWS # OF ROWS & SPACING FROM |
| TABLE 2 PAGE #4 OF THE EVALUATION REPORT THAT MEET OR |
| EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENT FOR ALL |
| ZONES EXPOSURE CATEGORY C AREAS. (-70). ALL APPLICABLE |
| DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS |
| NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |