Plan Review Details - Permit 23011162
Plan Review Stops For Permit 23011162
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By cpuell Date 2023-05-17 Time 12:47 Rev Time 0.00
Received By cpuell Date 2023-05-17 Time 12:47 Sent To  
Notes
2023-05-17 12:47:48PARCEL UPDATED 1005 AND 1015 N RAILROAD AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-03 Cont ID  
Sent By cpuell Date 2023-02-03 Time 13:40 Rev Time 0.00
Received By cpuell Date 2023-02-03 Time 13:40 Sent To  
Notes
2023-02-03 13:43:37THIS PARCEL CURRENTLY HAS TWO ADDRESSES 925 N RAILROAD
 AVE AND 1003 N RAILROAD AVE, I ALSO NOTICED THAT THE
 NEW BUILDING WILL HAVE AN UPSTIRS AND DOWNSTAIRS
 TENANT, ADDRESSES WILL NEED TO BE WORKED ON FOR THE
 PERMIT. PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS ADDRESSES

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2023-03-07 Cont ID  
Sent By swelter Date 2023-03-07 Time 10:34 Rev Time 0.00
Received By swelter Date 2023-03-10 Time 12:46 Sent To  
Notes
2023-03-07 10:36:37SEE MASTER PERMIT # 22120561

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-06 Cont ID  
Sent By rmcphers Date 2023-07-06 Time 13:44 Rev Time 0.00
Received By rmcphers Date 2023-07-06 Time 13:23 Sent To  
Notes
2023-07-06 13:34:11NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW ON THE FLOOR PLAN THE NORTH EXTERIOR
 WALL WHICH IS 7' 6" FROM THE PROPERTY LINE TO BE 1 HOUR
 FIRE RATED - FBC TABLE 602
  
 2) PLEASE SHOW THE CALCULATIONS FOR THE UNPROTECTED
 OPENINGS IN THE NORTH EXTERIOR WALL WHICH IS 7' 6" FROM
 THE PROPERTY LINES - PER FBC TABLE 705.8
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-10 Cont ID  
Sent By rmcphers Date 2023-05-10 Time 11:22 Rev Time 0.00
Received By rmcphers Date 2023-05-10 Time 11:04 Sent To  
Notes
2023-05-10 11:11:57NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE BUILDING SETBACK DIMENSIONS FROM THE
 PROPERTY LINES.- FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By rmcphers Date 2023-02-09 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2023-02-09 Time 13:08 Sent To  
Notes
2023-02-09 16:06:33NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING -
 FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 2) PLEASE PROVIDE A SURVEY
  
 3) DRAWING T.100 UNDER PROJECT DATA - BUILDING SQUARE
 FOOT FOR OCCUPANT LOAD APPEARS TO BE INCORRECT - PLEASE
 CORRECT.
  
 4) DRAWING T.100 STATES THAT A RESTROOM IS PROVIDED - A
 RESTROOM IS NOT SHOWN ON THE PLAN.
  
 5) RISK CATEGORY SHOWN IS "II" - FOR A BUILDING WITH AN
 ASSEMBLY OCCUPANCY OVER 300 WILL BE A RISK CATEGORY III
 WITH WIND DESIGN SPEED OF 180MPH PER FBC TABLE 1604.5
  
 6) PLEASE SHOW THE ADJACENT BUILDING OCCUPANCY
 CLASSIFICATION FBC TABLE 706.4
  
 7) DOORS CANNOT SWING BEYOND THE PROPERTY LINE - FBC
 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO
 THE PUBLIC RIGHT-OF-WAY.
  
 8) PLEASE SHOW THAT THE BUILDING ENTRIES ARE ACCESSIBLE
 - FBC 206.2.1
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE. - 206.2.4
 SPACES AND ELEMENTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY
 WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH
  
 9) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING
 BUILDING DEMO.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By mpeterso Date 2023-07-13 Time 13:43 Rev Time 0.00
Received By mpeterso Date 2023-07-13 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-02-06 Cont ID  
Sent By mpeterso Date 2023-02-06 Time 13:27 Rev Time 0.00
Received By mpeterso Date 2023-02-03 Time 11:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By cseifer Date 2023-07-13 Time 08:15 Rev Time 0.00
Received By cseifer Date 2023-07-13 Time 08:15 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By rrossano Date 2023-02-07 Time   Rev Time  
Received By rrossano Date 2023-02-07 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-09 Cont ID  
Sent By pleduc Date 2023-05-09 Time   Rev Time 0.00
Received By pleduc Date 2023-05-09 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By pleduc Date 2023-02-02 Time   Rev Time 0.00
Received By pleduc Date 2023-02-02 Time 10:40 Sent To  
Notes
2023-02-02 11:18:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE REAR EXITS INDICATED ON THE LIFE SAFETY
 PLANS,
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 THERE MAY BE A SERVICE ROAD NEXT TO THE RR, HOWEVER, I
 BELIEVE A FENCE IS BEING PROPOSED THAT MAY
 LIMIT/RESTRICT PASSAGE IN EITHER DIRECTION.
  
 THERE MAY ALSO BE GATES ALONG THIS FENCE THAT NEEDS TO
 BE ACCESSIBLE.
  
 AN ADDITIONAL CONCERN IS THAT THERE MAY BE UNPROTECTED
 OPENINGS ALONG ALL THE VARIOUS OCCUPANCIES ALONG THE
 FENCE LINE THAT COULD EXPOSE PEDESTRIANS TO THE EFFECTS
 OF FIRE AND SMOKE.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE REQUIRED
 CODE.
  
  
  
 2) SHEET LS 101 - THERE IS AN INDICATION REGARDING THE
 KNOX BOX LOCATION WITH A REFERENCE TO COORDINATE
 LOCATION WITH PBC FIRE RESCUE.
  
 THE JURISDICTION IS WEST PALM BEACH FIRE DEPARTMENT.
  
 PLEASE CORRECT AND CONTACT MY OFFICE AND/OR MY FIRE
 INSPECTOR FOR LOCATION.
  
  
 3) SHEET A 600 - WITHIN THE DOOR SCHEDULE, DOOR 103 HAS
 AN INDICATION OF DOOR SET 05.
  
 THIS APPEARS TO INDICATE THE EXIT BAR WITHIN THE LOBBY
 AND LVER SET WITHIN THE STAIRWELL.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE. DELINEATE
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-05-09 Cont ID  
Sent By rwbrown Date 2023-05-09 Time 07:01 Rev Time 0.00
Received By rwbrown Date 2023-05-09 Time 07:01 Sent To  
Notes
2023-05-09 07:01:40SEPARATE PERMIT PER NOTES ON P-100

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By rwbrown Date 2023-02-02 Time 14:39 Rev Time 0.00
Received By rwbrown Date 2023-02-02 Time 14:39 Sent To  
Notes
2023-02-02 14:40:301ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - I DID NOT SEE A GAS
 DETAIL. DO YOU PLAN TO ROUGH IN GAS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-05 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-31 Cont ID  
Sent By aoliver Date 2023-05-31 Time 07:44 Rev Time 0.00
Received By aoliver Date 2023-05-08 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-07 Cont ID  
Sent By aoliver Date 2023-03-07 Time 08:54 Rev Time 0.00
Received By aoliver Date 2023-01-31 Time 15:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-09 Cont ID  
Sent By rmcphers Date 2023-02-09 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2023-02-09 Time 16:12 Sent To  
Notes
2023-02-09 16:12:40PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-07-20 Cont ID  
Sent By cmontell Date 2023-07-20 Time 13:34 Rev Time 0.00
Received By cmontell Date 2023-07-20 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 15:08 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 15:08 Sent To  
Notes
2023-05-09 15:10:39IT APPEARS THAT THE MECHAICAL COMMENTS FOR THIS PROJECT
 GOT MIXED UP WITH ANOTHER PROJECT WHEN YOU RESUBMITTED.
 PLEASE ADDRESS THE COMMET BELOOW AS THIS PROJECT HAS
 THE LOBBIES AND VENTILATION ISSUES, NOT THE RATED
 WALLS.
  
 1ST REVIEW FMC
 PERMIT: 23011162
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-600: IN THE VENTILATION RATES SCHEDULE THE
 ROOMS ARE IDENTIFIED AS LOBBY ON BOTH FLOORS. TABLE
 403.3.1.1 INDICATES LOBBIES TO BE CALCULATED WITH AN
 OCCUPANCY DENSITY OF 150 WITH A PERSON CFM OF 7.5 AND
 THE BREATHING ZONE CFM/SQ FT. OF 0.06. WITH USING
 LOBBIES FROM TABLE 403.3.1.1 THE OUTDOOR AIR
 CALCULATION FOR BOTH LOBBIES ARE LOW. PLEASE PROVIDE
 THE CORRECTED VENTILATION RATES FOR THESE SPACES. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
 2) THESE DRAWINGS INDICATE THAT THIS IS ONLY THE
 BUILDING SHELL. SHEET T.100 INDICATES THIS DESIGN OF
 THIS BUILDING IS FOR WORST CASE SCENARIO WHICH IS
 ASSEMBLY A-2 BUT SHEET M-600 IN THE BASIS OF DESIGN FOR
 FUTURE TENANTS DOES NOT REFLECT THE OUTDOOR AIR OR
 EXHAUST REQUIREMENTS FOR THE WORST CASE SCENARIO.
 EITHER REMOVE ALL COMMENTS AND TABLES FOR THE FUTURE
 USE OR PROVIDE THE CORRECTED SCHEDULES REQUIRED FOR THE
 ASSEMBLY A-2 THAT IS STATED ON SHEET T.100. FMC
 403.3.1.1; TABLE 403.3.1.1 AND FBC 107.3.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By medwards Date 2023-02-02 Time 10:31 Rev Time 0.00
Received By medwards Date 2023-02-02 Time 10:31 Sent To  
Notes
2023-02-02 10:31:491ST REVIEW FMC
 PERMIT: 23011162
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-600: IN THE VENTILATION RATES SCHEDULE THE
 ROOMS ARE IDENTIFIED AS LOBBY ON BOTH FLOORS. TABLE
 403.3.1.1 INDICATES LOBBIES TO BE CALCULATED WITH AN
 OCCUPANCY DENSITY OF 150 WITH A PERSON CFM OF 7.5 AND
 THE BREATHING ZONE CFM/SQ FT. OF 0.06. WITH USING
 LOBBIES FROM TABLE 403.3.1.1 THE OUTDOOR AIR
 CALCULATION FOR BOTH LOBBIES ARE LOW. PLEASE PROVIDE
 THE CORRECTED VENTILATION RATES FOR THESE SPACES. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
 2) THESE DRAWINGS INDICATE THAT THIS IS ONLY THE
 BUILDING SHELL. SHEET T.100 INDICATES THIS DESIGN OF
 THIS BUILDING IS FOR WORST CASE SCENARIO WHICH IS
 ASSEMBLY A-2 BUT SHEET M-600 IN THE BASIS OF DESIGN FOR
 FUTURE TENANTS DOES NOT REFLECT THE OUTDOOR AIR OR
 EXHAUST REQUIREMENTS FOR THE WORST CASE SCENARIO.
 EITHER REMOVE ALL COMMENTS AND TABLES FOR THE FUTURE
 USE OR PROVIDE THE CORRECTED SCHEDULES REQUIRED FOR THE
 ASSEMBLY A-2 THAT IS STATED ON SHEET T.100. FMC
 403.3.1.1; TABLE 403.3.1.1 AND FBC 107.3.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-07-07 Cont ID  
Sent By rwbrown Date 2023-07-07 Time 07:31 Rev Time 0.00
Received By rwbrown Date 2023-07-07 Time 07:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-05-09 Cont ID  
Sent By rwbrown Date 2023-05-09 Time 06:55 Rev Time 0.00
Received By rwbrown Date 2023-05-09 Time 06:55 Sent To  
Notes
2023-05-09 07:01:001ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. ENGINEERING PERMITS DO NOT REPLACE THE NEED FOR
 BUILDING PERMITS FOR THE BACKFLOWS AND GREASE TRAPS -
 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE AT
 THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. DONE
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
 6. DONE
  
 7. DONE
  
 8. DONE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By rwbrown Date 2023-02-02 Time 12:55 Rev Time 0.00
Received By rwbrown Date 2023-02-02 Time 12:41 Sent To  
Notes
2023-02-02 14:32:201ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE
 AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE
 SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. 2020 FPC 607.1.1/613.1 - THE WATER HEATER AT THE
 JANITOR SINK SHALL HAVE A MIXING VALVE. ALL HOT WATER
 SHALL BE LIMITED BY SOMETHING OTHER THAN THE THERMOSTAT
 ON THE WATER HEATER.
  
 3. 2020 FPC 901.2.1 - PROVIDE A VENT FOR THE JANITOR
 SINK.
  
 4. 2020 FPC 906.1 - IT APPEARS THAT ACCORDING TO TABLE
 906.1, YOU NEED AT THE MINIMUM A 3" VENT STACK TO THE
 DOWNSTAIRS TENANT. 4" DRAINS WITH THAT MANY DFU'S
 CANNOT BE VENTED OFF OF 2". PLEASE RECALCULATE THE
 FUTURE VENT SIZING.
  
 5. 2020 FPC 1003.4 - PLEASE SHOW THE OIL ALARM OR OIL
 SEPARATOR FOR THE SUMP IN THE ELEVATOR SHAFT.
  
 6. 2020 FPC 712.3.2/906.5 - PLEASE DETAIL A VENT FOR
 THE SUMP PIT.
  
 7. 2020 FPC 606.2 - ADD A SHUT OFF ON THE SUPPLY LINE
 TO THE HOSE BIB.
  
 8. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE ADD A DETAIL
 FOR THE SCUPPERS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-02-09 Cont ID  
Sent By rmcphers Date 2023-02-09 Time 16:13 Rev Time 0.00
Received By rmcphers Date 2023-02-09 Time 16:12 Sent To  
Notes
2023-02-09 16:13:31ROOFING SYSTEMS TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-06 Cont ID  
Sent By rmcphers Date 2023-07-06 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2023-07-06 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-10 Cont ID  
Sent By rmcphers Date 2023-05-10 Time 11:23 Rev Time 0.00
Received By rmcphers Date 2023-05-10 Time 11:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-06 Cont ID  
Sent By mpeterso Date 2023-02-06 Time 13:32 Rev Time 0.00
Received By mpeterso Date 2023-02-06 Time 13:32 Sent To  
Notes
2023-02-06 13:32:42ALL PLANS PASSED SIGNATURE REVIEW
2023-02-02 10:38:39MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By ckimmerl Date 2023-05-30 Time 10:19 Rev Time 0.00
Received By ckimmerl Date 2023-05-30 Time 10:19 Sent To  
Notes
2023-05-30 10:19:21PROPOSAL FOR 925 N RAILROAD AVENUE HAS BEEN SUBMITTED
 FOR FORMAL SITE PLAN APPROVAL AND HAS NOT RECEIVED SAID
 APPROVAL.
 ZONING STAFF CAN NOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-23 (Z22090018).
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By CKimmerl Date 2023-03-06 Time 14:41 Rev Time 0.00
Received By ckimmerl Date 2023-03-06 Time 14:37 Sent To  
Notes
2023-03-06 14:41:53PROPOSAL FOR 925 N RAILROAD AVENUE HAS BEEN SUBMITTED
 FOR FORMAL SITE PLAN APPROVAL AND HAS NOT RECEIVED SAID
 APPROVAL.
 ZONING STAFF CAN NOT REVIEW OR APPROVE OF THE BUILDING
 PERMIT WITHOUT FIRST RESUBMITTING AND OBTAINING THE
 SITE PLAN APPROVAL FOR FSPR 22-23 (Z22090018).
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426