Plan Review Stops For Permit 23011118 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-02-02 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-02-02 |
Time |
16:07 |
Sent To |
|
|
Notes |
2023-02-02 16:08:10 | ZONING NOT ALLOWING A SECONDARY UNIT, AS SUCH NO | | ADDITION ADDRESS IS REQUIRED |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2023-01-31 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-01-31 |
Time |
07:36 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-01-31 |
Time |
07:36 |
Sent To |
|
|
Notes |
2023-01-31 07:36:50 | A SECONDARY ADDRESS MAY NEED TO BE ASSIGNED IF ZONING | | APPROVES A SECONDARY UNIT. PLEASE CONTACT | | [email protected] OR CALL 561-805-6659 ONCE ZONING | | APPROVES THEIR REVIEW. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-01-26 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-01-26 |
Time |
07:24 |
Sent To |
|
|
Notes |
2023-01-26 07:36:06 | THIS PARCEL CURRENTLY HAS A BUILDING ON IT, PLEASE | | PROVIDE A SITE PLAN SHOWING WHERE THE NEW DETACHED UNIT | | WILL BE LOCATED ON THE PARCEL.A SECONDARY ADDRESS MAY | | NEED TO BE ASSIGNED IF ZONING APPROVES A SECONDARY | | UNIT. PLEASE CONTACT [email protected] OR CALL | | 561-805-6659 ONCE ZONING APPROVES THEIR REVIEW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-01 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-01 |
Time |
07:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-31 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-31 |
Time |
12:43 |
Sent To |
|
|
Notes |
2023-05-31 12:45:58 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) REVISED DRAWING A1.0 DOES NOT SHOW AS DIGITALLY | | SIGNED BY THE ARCHITECT IN ADOBE READER - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2023-05-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-10 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-10 |
Time |
14:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-05 |
Time |
08:41 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-05 |
Time |
08:18 |
Sent To |
|
|
Notes |
2023-05-05 08:25:32 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) (THE PRODUCT APPROVAL PROVIDED FOR THE FOAM IS FOR A | | FOAM ROOFING SYSTEM THE DRAWINGS SHOW THE ROOFING | | SYSTEM TO BE SHINGLES). PLEASE PROVIDE DOCUMENTATION | | FOR THE SPRAY FOAM INSULATION (ICC - ES EVALUATION | | REPORT) - FBC R316.3 SURFACE BURNING CHARACTERISTICS. | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-04-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-18 |
Time |
15:27 |
Sent To |
|
|
Notes |
2023-04-18 15:45:05 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) SEE DRAWING A-1.0 GENERAL NOTE NUMBER 7 - (NOTE | | NUMBER 7 CAN BE CHANGED TO STATE THE SOIL BEARING | | CAPACITY IS 2500 PSF OR MORE) - PLEASE PROVIDE A SOIL | | REPORT (GEOTECHNICAL REPORT) FBC 1803.2 | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR - | | ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | 107.3.4 | | | | 3) A PRODUCT APPROVAL HAS BEEN PROVIDED FOR A SINGLE | | HUNG WINDOW - THE DRAWINGS DO NOT SHOW A LOCATION FOR A | | SINGLE HUNG WINDOW. | | | | 4) PRODUCT APPROVAL (FL11136 - R8) FOR THE SWING DOOR | | IS FOR THE 2017 FBC CODE VERSION - YOU NEED TO PROVIDE | | A DOOR PRODUCT APPROVAL FOR THE 2020 FBC CODE VERSION. | | | | 5) PLEASE PROVIDE DOCUMENTATION FOR THE SPRAY FOAM | | INSULATION (ICC - ES EVALUATION REPORT) - FBC R316.3 | | SURFACE BURNING CHARACTERISTICS. | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-03-08 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-03-08 |
Time |
11:21 |
Sent To |
|
|
Notes |
2023-03-08 11:25:35 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT) | | FBC 1803.2 | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR, | | EXTERIOR SWING DOOR AND THE ROOFING SYSTEMS - ALL | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | 107.3.4 | | | | 3) PLEASE SHOW THE ROOF SHEATHING TYPE AND THICKNESS - | | FBC WPB 107.2.1 | | | | 4) PLEASE PROVIDE DOCUMENTATION FOR THE SPRAY FOAM | | INSULATION (ICC - ES EVALUATION REPORT) - FBC R316.3 | | SURFACE BURNING CHARACTERISTICS. | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | 5) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY - FBC WPB | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-02-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-02 |
Time |
12:53 |
Sent To |
|
|
Notes |
2023-02-02 13:30:31 | POOL HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT) | | FBC 1803.2 | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE EXTERIOR SLIDING GLASS DOOR, | | EXTERIOR SWING DOOR AND THE ROOFING SYSTEMS - ALL | | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | 107.3.4 | | | | 3) PLEASE SHOW THE ROOF SHEATHING TYPE AND THICKNESS - | | FBC WPB 107.2.1 | | | | 4) DRAWING A-1.01 TYPICAL WALL SECTION SHOWS ATTIC | | VENTILATION AND SPRAY FOAM INSULATION - SHOULD NOT HAVE | | ATTIC VENTILATION WITH FOAM ATTACHED TO THE UNDERSIDE | | OF THE ROOF SHEATHING. SEE FOAM INSULATION INSTRUCTIONS | | AND PROVIDE THOSE INSTRUCTIONS. (ICC - ES EVALUATION | | REPORT) - FBC R316.3 SURFACE BURNING CHARACTERISTICS. | | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM | | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN | | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND | | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 | | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY | | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. | | | | 5) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE | | BUILDING AND AWAY FROM THE ADJACENT PROPERTY - FBC WPB | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-03-14 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-03-14 |
Time |
12:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-02-03 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-02-03 |
Time |
10:36 |
Sent To |
|
|
Notes |
2023-02-03 13:04:21 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE LOAD CALCULATION AND PANEL SCHEDULE OF THE | | MAIL PANEL OR MAIL LOAD CENTER INCLUDING INCLUDING | | ADDITION AND POOL HOUSE. NEC 220.82, 408.4(A) | | 2. PROVIDE INFORMATION OF THE SERVICE CONDUCTORS, | | GROUNDED CONDUCTORS, AND PROTECTIONS. NEC 230, 240, 250 | | 3. PROVIDE INFORMATION OF THE FEEDERS FOR SUBPANEL "A" | | (INCLUDING CONDUCTORS SIZES AND EGC). NEC 220, 310.15, | | 250.122 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2023-04-25 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-04-25 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-04-25 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-31 |
Time |
12:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-30 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
P |
Date |
2023-05-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-10 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-09 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-05 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-04 |
Time |
18:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-04-26 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-04-26 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-04-13 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-03-21 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-03-21 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-02-03 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-01-25 |
Time |
08:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2023-06-13 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-13 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-05-10 |
Time |
14:33 |
Sent To |
|
|
Notes |
2023-06-13 09:14:17 | IMPACT FEE RECEIPT MU-2023-0022407-0000 $2,457.78 PAID | | -AO | 2023-05-10 14:33:43 | 5/10/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2023-02-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-02 |
Time |
13:35 |
Sent To |
|
|
Notes |
2023-02-02 13:36:58 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-04-24 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-04-24 |
Time |
16:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-03-07 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-03-07 |
Time |
13:29 |
Sent To |
|
|
Notes |
2023-03-07 13:30:48 | 2ND ATTEMPT, SEE BELOW: | | | | 1) PROVIDE A MECHANICAL DESIGN THAT WOULD INCLUDE A | | DRAWING WITH THE UNITS INSTALLED, THE CONDENSING UNIT | | TIED DOWN DETAIL, THE CONDENSATE DRAIN TERMINATION | | LOCATION AND THE SPEC SHEETS FOR THE MECHANICAL SYSTEM. | | FBC 107.3.5 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-01-27 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-01-27 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-27 |
Time |
12:43 |
Sent To |
|
|
Notes |
2023-01-27 12:43:42 | 1ST REVIEW FMC | | PERMIT: 23011118 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A MECHANICAL DESIGN THAT WOULD INCLUDE A | | DRAWING WITH THE UNITS INSTALLED, THE CONDENSING UNIT | | TIED DOWN DETAIL, THE CONDENSATE DRAIN TERMINATION | | LOCATION AND THE SPEC SHEETS FOR THE MECHANICAL SYSTEM. | | FBC 107.3.5 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-05-05 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-05-05 |
Time |
07:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-04-17 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-04-17 |
Time |
10:10 |
Sent To |
|
|
Notes |
2023-04-17 10:13:26 | 3RD PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | | | 2. POOL HOUSE - 2020 FRC P3108.2.1 - THE SHOWER AND | | WATER CLOSET ARE BOTH UPSTREAM OF THE LAVATORY | | CONNECTION. ONLY ONE TRAPPED FIXTURE IS ALLOWED TO BE | | UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE | | HORIZONTAL BRANCH DRAIN BEING WET VENTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-03-07 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-03-07 |
Time |
06:36 |
Sent To |
|
|
Notes |
2023-03-07 06:37:38 | 2ND PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. COMMENT NOT ADDRESSED - THE KITCHEN SINK IS NOT A | | BATHROOM GROUP FIXTURE. ONLY BATHROOM GROUP FIXTURES | | ARE ALLOWED TO BE INCLUDED WITHIN THE WET VENT FOR THE | | BATHROOM. THE KITCHEN SINK MUST DISCHARGE DOWNSTREAM OF | | THE LAST BATHROOM GROUP FIXTURE BEING WET VENTED. | | POOL HOUSE DIAGRAM - 2020 FRC P3108.1 - THE KITCHEN | | SINK CANNOT BE THE VENTED FIXTURE THAT CREATES THE WET | | VENT FOR THE BATHROOM GROUP FIXTURES. THE KITCHEN SINK | | WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT | | SYSTEM IF A WET VENT IS USED. | | | | 2. ADDITIONAL COMMENT - ADDTION WASTE DIAGRAM - 2020 | | FRC P3108.2.1 - THE TUB AND SHOWER ARE BOTH UPSTREAM OF | | THE LAVATORY CONNECTION. ONLY ONE TRAPPED FIXTURE IS | | ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S | | CONNECTION TO THE HORIZONTAL BRANCH DRAIN BEING WET | | VENTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-01-26 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-01-26 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-01-26 |
Time |
11:29 |
Sent To |
|
|
Notes |
2023-01-26 11:31:36 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC P3108.1 - THE KITCHEN SINK CANNOT BE THE | | VENTED FIXTURE THAT CREATES THE WET VENT FOR THE | | BATHROOM GROUP FIXTURES. THE KITCHEN SINK WOULD NEED TO | | DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM IF A WET | | VENT IS USED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-05 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-05 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2023-04-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-18 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-03-08 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-03-08 |
Time |
11:25 |
Sent To |
|
|
Notes |
2023-03-08 11:26:15 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2023-02-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
13:30 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-02 |
Time |
13:30 |
Sent To |
|
|
Notes |
2023-02-02 13:31:41 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
6 |
Status |
P |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-01 |
Time |
08:00 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-01 |
Time |
08:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
F |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-31 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-31 |
Time |
12:46 |
Sent To |
|
|
Notes |
2023-05-31 12:46:51 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) REVISED DRAWING A1.0 DOES NOT SHOW AS DIGITALLY | | SIGNED BY THE ARCHITECT IN ADOBE READER - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-05 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-05 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-04-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-18 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-18 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-03-08 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-03-08 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-02-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-02 |
Time |
13:38 |
Sent To |
|
|
Notes |
2023-02-02 13:39:47 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-6.0 DOES NOT SHOW AS DIGITALLY SIGNED IN | | ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2023-04-14 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-04-14 |
Time |
17:32 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-04-14 |
Time |
17:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-03-21 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-03-21 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
Sent By |
ASangele |
Date |
2023-02-01 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-02-01 |
Time |
14:14 |
Sent To |
|
|
Notes |
2023-02-01 14:22:40 | FAILED | | 2/1/2023 | | | | A 240 OUTLET CANNOT BE INSTALLED BECAUSE A STOVE IS NOT | | ALLOWED TO BE INSTALLED | | PROPERTY DOESNT MEET THE MINIMUM STANDARDS TO HAVE A | | SECOND UNIT ON PROPERTY. | | | | ARTICLE III. SECTION 94-75 | | MINIMUM LOT DIMENSIONS. | | A.LOT AREA FOR ONE OR TWO DWELLING UNITS: 6,000 SQUARE | | FEET; | | B.LOT AREAS FOR THREE OR MORE DWELLING UNITS: 3,000 | | SQUARE FEET PER UNIT; NOT TO EXCEED A MAXIMUM OF 14.52 | | DWELLING UNITS PER ACRE; | | C.LOT WIDTH: 60 FEET; | | | | PLEASE PROVIDE REAR SETBACK ON SITE PLAN | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] | | | | |
|
|