Plan Review Details - Permit 23010863
Plan Review Stops For Permit 23010863
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-03-16 Cont ID  
Sent By rmcdouga Date 2023-03-16 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2023-03-16 Time 16:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By mpeterso Date 2023-03-02 Time 08:42 Rev Time 0.00
Received By mpeterso Date 2023-02-28 Time 12:30 Sent To  
Notes
2023-03-02 08:44:43ELECTRIC REVIEW FAILED
  
 1) IT APPEARS THE GENERATOR SUBMITTAL SPECIFICATIONS DO
 NO NOT MATCH DRAWING PROVIDE. PLEASE CORRECT AS
 APPLICABLE.
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL
  
 2) PLEASE PROVIDE A CLEAR RISER DETAILING ALL ELECTRIC
 LOADS, EQUIPMENT, CONDUIT, AND CONDUCTORS AND
 OVERCURRENT PROTECTION. PROVIDE A SYMBOL LEGEND FOR ANY
 EQUIPMENT DETAILED WITH ABBREVIATIONS. PLEASE NOTE,
 THAT RISER SHOULD NOT CONFLICT WITH PREVIOUSLY APPROVED
 RISER DIAGRAMS. INDICATE FIRE PUMP WIRING COMPLIES WITH
 ALL RELEVANT NEC CODES, AS PER ARTICLE 695.
  
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER
 DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF
 THE FEEDERS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-15 Cont ID  
Sent By cwalker Date 2023-02-15 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-22 Cont ID  
Sent By aoliver Date 2023-03-22 Time 10:14 Rev Time 0.00
Received By aoliver Date 2023-02-14 Time 15:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By medwards Date 2023-02-15 Time 15:15 Rev Time 0.00
Received By medwards Date 2023-02-15 Time 15:15 Sent To  
Notes
2023-02-15 15:16:291ST REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SITE DRAWING SHOWING THE GENERATOR ROOM
 AND THE EXHAUST TERMINATION LOCATION MEETS THE 10 FEET
 SETBACK FROM PROPERTY LINES. ALSO PROVIDE A DRAWING
 THAT SHOWS WHERE THE EXTERIOR FILL TANK IS TO BE
 LOCATED ON THE PROPERTY. FBC 107.3.5
  
 2) PROVIDE A DETAIL DRAWING SHOWING THE LOCATION OF THE
 INTAKE LOUVER FOR THE GENERATOR ROOM. THE ORIGINAL
 APPROVED SHEET A0-101 INDICATES THE WALL THAT THE
 INTAKE LOUVER IS TO BE INSTALLED IS A 2 HOUR RATED
 WALL. THIS WALL APPEARS TO BE INSIDE THE FOOTPRINT OF
 THE BUILDING. THE INTAKE SHOULD BE OUTSIDE OF THE
 BUILDING. FMC 401.4
  
 3) SHEET A0-101 OF THE ORIGINAL APPROVED PLANS SHOW THE
 GENERATOR ROOM HAVING THE TX VAULT ROOM AND THE
 ELECTRIC ROOM SURROUNDING IT. PROVIDE A DETAIL DRAWING
 SHOWING THE FUEL PIPING AND TANK VENTILATION LOCATION
 ON THE EXTERIOR OF THE BUILDING. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-01-23 Cont ID  
Sent By shill Date 2023-01-23 Time 15:59 Rev Time 0.00
Received By shill Date 2023-01-23 Time 15:59 Sent To  
Notes
2023-01-23 15:59:58INSPECTIONS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-15 Cont ID  
Sent By medwards Date 2023-02-15 Time 15:16 Rev Time 0.00
Received By medwards Date 2023-02-15 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2023-03-21 Cont ID  
Sent By CKimmerl Date 2023-03-21 Time 11:42 Rev Time 0.00
Received By ckimmerl Date 2023-03-21 Time 11:42 Sent To  
Notes
***NONE***