Plan Review Details - Permit 23010735
Plan Review Stops For Permit 23010735
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-08 Cont ID  
Sent By cthroop Date 2023-02-08 Time 15:33 Rev Time 0.00
Received By cthroop Date 2023-02-08 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-24 Cont ID  
Sent By jbrooks Date 2023-01-24 Time 09:37 Rev Time 0.00
Received By jbrooks Date 2023-01-24 Time 07:52 Sent To  
Notes
2023-01-24 09:38:11JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 HAS BEEN REVISED TO FL16709-R10.
 PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION
 REPORT PAGES 1-4 AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 COVERS MULTIPLE OPTIONS FOR SYSTEM
 NO. W-4. PLEASE SELECT EXPOSURE; ENCLOSURE; ROOF
 HEIGHT; ULTIMATE WIND SPEED & FASTENER PATTERNS FOR
 ZONES 1 PRIME, ZONE 1, ZONE 2 & ZONE 3. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 COVERS MULTIPLE OPTIONS FOR SYSTEM
 NO. W-5. PLEASE SELECT EXPOSURE; ENCLOSURE; ROOF
 HEIGHT; ULTIMATE WIND SPEED & FASTENER PATTERNS FOR
 ZONES 1 PRIME, ZONE 1, ZONE 2 & ZONE 3. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-08 Cont ID  
Sent By cthroop Date 2023-02-08 Time 15:34 Rev Time 0.00
Received By cthroop Date 2023-01-24 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-24 Cont ID  
Sent By jbrooks Date 2023-01-24 Time 09:38 Rev Time 0.00
Received By jbrooks Date 2023-01-23 Time 14:41 Sent To  
Notes
***NONE***