Plan Review Details - Permit 23010647
Plan Review Stops For Permit 23010647
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-31 Cont ID  
Sent By lbond Date 2023-03-31 Time 10:32 Rev Time 0.00
Received By lbond Date 2023-03-31 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-17 Cont ID  
Sent By lbond Date 2023-03-17 Time 14:30 Rev Time 0.00
Received By lbond Date 2023-03-17 Time 14:30 Sent To  
Notes
2023-03-17 16:03:09SEE FIRE COMMENTS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-31 Cont ID  
Sent By cwalker Date 2023-03-31 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-31 10:10:54FIRE PROVISO COMMENT:
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-02-21 Cont ID  
Sent By pleduc Date 2023-02-21 Time   Rev Time 0.00
Received By pleduc Date 2023-02-21 Time 11:52 Sent To  
Notes
2023-02-21 11:57:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF "REPLACEMENT OF 2 COMMON
 DOOR" ON THE APPLICATION; HOWEVER, THERE IS NO
 INDICATION OF A DETAILED SCOPE OF WORK AND THERE ARE 3
 DOORS INDICATED ON THE SITE PLAN
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK AND CLARIFY THE
 NUMBER OF DOORS.
  
  
  
 1A) PER SCOPE OF WORK COMMENT ABOVE, PLEASE PROVIDE ALL
 APPLICABLE DOOR SCHEULE INCLUDING, BUT NOT LIMITED TO,
 DOOR SPECS, REQUIRED FIRE RATINGS, LOCK/LATCHING
 HARDWARE, ETC.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 SHOULD THE EXISTING DOOR AND HARDWARE IS EXXISTING AND
 WILL BE REPLACED WITHIN THE NEW DOOR FRAME, PLAESE
 INDICATE SUCH.
  
 OTHERWISE PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE
 DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2023-03-31 Cont ID  
Sent By amhamilt Date 2023-03-31 Time 10:16 Rev Time 0.00
Received By amhamilt Date 2023-03-31 Time 10:16 Sent To  
Notes
2023-03-31 10:17:00WORK DOES NOT AFFECT HISTORIC PORTION OF PARCEL
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-31 Cont ID  
Sent By lbond Date 2023-03-31 Time 10:33 Rev Time 0.00
Received By lbond Date 2023-03-24 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-30 Cont ID  
Sent By lbond Date 2023-03-30 Time 10:50 Rev Time 0.00
Received By lmarchan Date 2023-02-17 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-17 Cont ID  
Sent By lbond Date 2023-03-17 Time 14:31 Rev Time 0.00
Received By lbond Date 2023-03-17 Time 14:31 Sent To  
Notes
***NONE***