Plan Review Details - Permit 23010360
Plan Review Stops For Permit 23010360
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By rmcphers Date 2023-03-03 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2023-03-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 13:49 Sent To  
Notes
2023-02-23 13:53:12CREATE A ROOM FROM THE GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE DOOR FROM THE GARAGE - SIZE AND TYPE
 - FBC R302.5.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMBCORE
 STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR
 20-MINUTE FIRE-RATED DOORS.
  
 2) PLEASE SHOW THE SMOKE DETECTOR LOCATIONS - FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-04-03 Cont ID  
Sent By rperdomo Date 2023-04-03 Time 10:44 Rev Time 0.00
Received By rperdomo Date 2023-04-03 Time 08:33 Sent To  
Notes
2023-04-03 10:41:18FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: PASSED, SEE COMMENTS BELOW
  
 1. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT (MINI
 SPLIT OUTSIDE CONDENSER) PER NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-01 Cont ID  
Sent By rperdomo Date 2023-03-01 Time 15:13 Rev Time 0.00
Received By rperdomo Date 2023-03-01 Time 15:11 Sent To  
Notes
2023-03-01 15:13:19FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW LOAD CALCULATION (NEW MINI SPLIT HAS TO BE AT
 100 %) TO BE IN ACCORDANCE WITH 220.82
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By rperdomo Date 2023-02-07 Time 14:17 Rev Time 0.00
Received By rperdomo Date 2023-02-07 Time 13:37 Sent To  
Notes
2023-02-07 14:17:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW LOAD CALCULATION (AC/HEAT @ 65%) TO BE IN
 ACCORDANCE WITH 220.82
 2. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6FT FROM A RECEPTACLE OUTLET. NEC
 210.52
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-04 Cont ID  
Sent By lmarchan Date 2023-04-04 Time 07:21 Rev Time 0.00
Received By lmarchan Date 2023-03-27 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-09 Cont ID  
Sent By vbroglia Date 2023-03-09 Time 10:26 Rev Time 0.00
Received By vbroglia Date 2023-02-28 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2023-02-06 Time 16:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 08:53 Rev Time 0.00
Received By aoliver Date 2023-04-04 Time 14:03 Sent To  
Notes
2023-04-14 07:15:54RECEIPT MU-2023-016162-0000 - $49.23 PAID
2023-04-04 14:03:374/4/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 15:53 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 15:53 Sent To  
Notes
2023-02-23 15:54:26PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By medwards Date 2023-03-01 Time 11:45 Rev Time 0.00
Received By medwards Date 2023-03-01 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 07:56 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By rmcphers Date 2023-03-03 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2023-03-03 Time 14:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 07:56 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 07:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By vbroglia Date 2023-03-09 Time 10:25 Rev Time 0.00
Received By vbroglia Date 2023-03-09 Time 10:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-13 Cont ID  
Sent By vbroglia Date 2023-02-13 Time 12:59 Rev Time 0.00
Received By vbroglia Date 2023-02-13 Time 12:59 Sent To  
Notes
***NONE***