2023-02-06 09:00:24 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL2533-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL2533-R28 COVERS MULTIPLE ROOF SYSTEMS FOR |
| WOOD DECKS; SYSTEM TYPE A1-F NO. W-1 THRU W-105. |
| SELECTED SYSTEM TYPE TO BE USED. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ZONE 3 DESIGN PRESSURE REQUIREMENTS |
| FOR EXPOSURE CATEGORY D AREAS OF -131.42/PROVIDE SIGNED |
| AND SEALED ENGINEERED NAILING CALCULATIONS WITH AN |
| APPROVED SYSTEM. |
| 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL15216-R10 |
| HAS BEEN REVISED TO FL15216-R11. PLEASE PROVIDE A |
| COMPLETE SET. FLORIDA PRODUCT APPROVAL FL15216-R11 |
| COVERS MULTIPLE INSTALLATION METHODS. INDICATE |
| INSTALLATION METHOD ON SECTION 6.3 PAGE #4. PLEASE |
| NOTE: LAST LINE OF PARAGRAPH 6.3.1.1; FBC REQUIREMENTS |
| TAKES PRECEDENCE OVER MANUFACTUER???S INSTALLATION |
| INSTRUCTIONS. |
| 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL10674-R17 COVERS MULTIPLE PRODUCTS & |
| INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION |
| METHOD TO BE USED. ALL APPLICABLE DETAILS AND |
| ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| APPROVAL DRAWINGS. |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |