Plan Review Stops For Permit 23010098 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-03-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-06 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-06 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-02-07 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-02-07 |
Time |
06:39 |
Sent To |
|
|
Notes |
2023-02-07 15:50:46 | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | (SFHA) WITH FLOOD ZONES X, AE6 & AE7. EVALUATION OF | | PROJECT PER FEMA P-758 DESK REFERENCE FOR SI/SD. THIS | | PROJECT IS NOT REQUIRED TO COMPY WITH FEMA 50% RULE. CT |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-02-16 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-16 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-01-13 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-01-13 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-17 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-17 |
Time |
06:46 |
Sent To |
|
|
Notes |
2023-02-17 07:15:17 | | | 2ND REVIEW FBC-2020 FUEL GAS | | PERMIT- 23010098 | | 2/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. PLEASE RESPOND TO THE 1ST | | REVIEW COMMENT COPIED. BELOW. TO HELP EXPEDITIE THE | | REVIEW PROCESS PLEASE SUBMIT A NARRATIVE RESPONSE AS | | NOTED BELOW. | | | | 1) SHEET A-1.1: THE PLAN SHOWS A GRILL IN THE PERGOLA | | WHICH IS ASSUMED TO BE A GAS GRILL. PLEASE CLARIFY IF | | THE GRILL WILL BE FIRED USING A PORTABLE LP TANK OR | | CONNECTED TO THE EXISTING GAS PIPING SYSTEM- SEC. | | 107.2.1 WPB. PLEASE NOTE IF CONNECTING TO THE EXISTING | | GAS SERVICE A COMPLETE RISER DRAWING WILL BE REQUIRED | | THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND | | APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 | | FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE | | RISER SHALL INDICATE: | | A) TYPE OF GAS- NATURAL OR LP. | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | UNIONS. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | 2) A-1.1: THE SPECS FOR THE GRILL MANUFACTURER PROVIDES | | INSTALLATION CLEARANCES AND LIMITATIONS WHICH MAY | | PROHIBIT THE INSTALLATION UNDER COMBUSTIBLE | | CONSTRUCTION. PLEASE REVIEW THE SPECS AND SUBMIT ONLY | | THE PAGES THAT DETAIL THE REQUIRED CLEARANCES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2023-01-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-17 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-17 |
Time |
12:19 |
Sent To |
|
|
Notes |
2023-01-17 12:44:09 | | | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 23010098 | | 1/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET A-1.1: THE PLAN SHOWS A GRILL IN THE PERGOLA | | WHICH IS ASSUMED TO BE A GAS GRILL. PLEASE CLARIFY IF | | THE GRILL WILL BE FIRED USING A PORTABLE LP TANK OR | | CONNECTED TO THE EXISTING GAS PIPING SYSTEM- SEC. | | 107.2.1 WPB. PLEASE NOTE IF CONNECTING TO THE EXISTING | | GAS SERVICE A COMPLETE RISER DRAWING WILL BE REQUIRED | | THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND | | APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 | | FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE | | RISER SHALL INDICATE: | | A) TYPE OF GAS- NATURAL OR LP. | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | UNIONS. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | 2) A-1.1: THE SPECS FOR THE GRILL MANUFACTURER PROVIDES | | INSTALLATION CLEARANCES AND LIMITATIONS WHICH MAY | | PROHIBIT THE INSTALLATION UNDER COMBUSTIBLE | | CONSTRUCTION. PLEASE REVIEW THE SPECS AND SUBMIT ONLY | | THE PAGES THAT DETAIL THE REQUIRED CLEARANCES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-03-08 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-02-15 |
Time |
16:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-02-08 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2023-02-08 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2023-01-09 |
Time |
09:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2023-02-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-16 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-16 |
Time |
16:07 |
Sent To |
|
|
Notes |
2023-02-16 16:08:39 | RESPOND TO THE FIRST CYCLE REVIEW COMENTS BELOW. | | | | 1ST REVIEW FMC | | PERMIT: 23010098 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) IN THE ALL APPLIANCES AND EQUIPMENT SPECS COMBINED | | FOLDER THERE ARE 3 NEW MECHANICAL SYSTEMS, 2-TON, 3-TON | | AND A 4-TON. THE SUBMITTED M1.1 SHEET ONLY SHOWS AN | | EXHAUST FAN IN THE CABANA. I CANNOT REVIEW THIS | | SUBMITTAL AS THERE IS NOTHING SUBMITTED AS TO WHERE | | THESE UNITS ARE GOING. IF THESE MECHANICAL SYSTEMS ARE | | TO BE INSTALLED INTO THE MAIN HOUSE OR OTHER STRUCTURES | | YOU WILL NEED TO SUBMIT A COMPLETE MECHANICAL DESIGN. | | FBC 107.3.5 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-01-12 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-12 |
Time |
15:36 |
Sent To |
|
|
Notes |
2023-01-12 15:36:20 | 1ST REVIEW FMC | | PERMIT: 23010098 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) IN THE ALL APPLIANCES AND EQUIPMENT SPECS COMBINED | | FOLDER THERE ARE 3 NEW MECHANICAL SYSTEMS, 2-TON, 3-TON | | AND A 4-TON. THE SUBMITTED M1.1 SHEET ONLY SHOWS AN | | EXHAUST FAN IN THE CABANA. I CANNOT REVIEW THIS | | SUBMITTAL AS THERE IS NOTHING SUBMITTED AS TO WHERE | | THESE UNITS ARE GOING. IF THESE MECHANICAL SYSTEMS ARE | | TO BE INSTALLED INTO THE MAIN HOUSE OR OTHER STRUCTURES | | YOU WILL NEED TO SUBMIT A COMPLETE MECHANICAL DESIGN. | | FBC 107.3.5 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-02-17 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-02-17 |
Time |
06:46 |
Sent To |
|
|
Notes |
2023-02-17 07:12:50 | 2ND REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 23010098 | | 2/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. PLEASE RESPOND TO THE 1ST | | REVIEW COMMENT COPIED BELOW. TO HELP EXPEDITE THE | | REVIEW PROCESS PLEASE SUBMIT A NARRATIVE RESPONSE AS | | NOTED BELOW. | | | | 1) SHEET P-1.1: THE PROPERTY IS LOCATED IN AN AE FLOOD | | HAZARD ZONE. THE EXTERIOR SHOWER DRAIN IS NOT APPROVED | | BASED ON SEC. R322.1.7 FBC RES- NEW AND REPLACEMENT | | SANITARY SEWAGE SYSTEMS SHALL BE DESIGNED TO MINIMIZE | | OR ELIMINATE INFILTRATION OF FLOODWATERS INTO SYSTEMS | | AND DISCHARGES FROM SYSTEMS INTO FLOODWATERS IN | | ACCORDANCE WITH THE PLUMBING PROVISIONS OF THIS CODE | | AND IN ACCORDANCE WITH CHAPTER 64E-6, FLORIDA | | ADMINISTRATIVE CODE, STANDARDS FOR ONSITE SEWAGE | | TREATMENT AND DISPOSAL SYSTEMS. | | A) PLEASE NOTE THAT SEC. 90-126 (5) WPB CODE OF | | ORDINANCES ALSO PROHIBITS STORM OR GROUND WATER TO | | DISCHARGE INTO THE SANITARY SEWER SYSTEM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-01-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-17 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-17 |
Time |
12:18 |
Sent To |
|
|
Notes |
2023-01-17 12:18:46 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 23010098 | | 1/17/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P-1.1: THE PROPERTY IS LOCATED IN AN AE FLOOD | | HAZARD ZONE. THE EXTERIOR SHOWER DRAIN IS NOT APPROVED | | BASED ON SEC. R322.1.7 FBC RES- NEW AND REPLACEMENT | | SANITARY SEWAGE SYSTEMS SHALL BE DESIGNED TO MINIMIZE | | OR ELIMINATE INFILTRATION OF FLOODWATERS INTO SYSTEMS | | AND DISCHARGES FROM SYSTEMS INTO FLOODWATERS IN | | ACCORDANCE WITH THE PLUMBING PROVISIONS OF THIS CODE | | AND IN ACCORDANCE WITH CHAPTER 64E-6, FLORIDA | | ADMINISTRATIVE CODE, STANDARDS FOR ONSITE SEWAGE | | TREATMENT AND DISPOSAL SYSTEMS. | | A) PLEASE NOTE THAT SEC. 90-126 (5) WPB CODE OF | | ORDINANCES ALSO PROHIBITS STORM OR GROUND WATER TO | | DISCHARGE INTO THE SANITARY SEWER SYSTEM. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
2 |
Status |
F |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
jbaker |
Date |
2023-03-08 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
jbaker |
Date |
2023-03-08 |
Time |
08:58 |
Sent To |
|
|
Notes |
2023-03-08 09:00:05 | PROVIDE NOTICE TO BUILDING OFFICIAL AND CERTIFICATE OF | | INSURANCE AS REQUIRED BY FS FOR PRIVATE PROVIDERS. |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2023-02-08 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2023-02-08 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2023-02-08 |
Time |
10:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-03-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-06 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-06 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-02-07 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-02-07 |
Time |
06:39 |
Sent To |
|
|
Notes |
2023-01-12 15:38:50 | MECHANICAL DIGITAL SIGNATURE APPEARS TO BE OK. ME |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-02-22 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-02-22 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-02-22 |
Time |
12:24 |
Sent To |
|
|
Notes |
2023-02-22 12:25:59 | 2/22/23 FAILED | | | | PREVIOUS COMMENTS NOT SATISIFIED | | | | PLEASE SHOW THE FRONT SETBACKS, 25 FEET FROM FLAGLER | | | | SEPARATE PERMIT REQUIRED FOR: | | FENCE/WALL, MECHANICAL/AC/POOL EQUIPMENT, DRIVEWAY, | | IRRIGATION, LANDSCAPE, OTHER. | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-01-19 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-01-19 |
Time |
11:29 |
Sent To |
|
|
Notes |
2023-01-19 13:14:01 | 1/19/23 FAILED | | | | PLEASE SHOW ALL THE SETBACKS OF THE ACCESSORY | | STRUCTURES | | | | PLEASE NOTE FLAGLER IS NOTED AS 88 FEET IN LOT WIDTH, | | SO THIS WOULD BE CONSIDERD THE FRONT SETBACKS, PLEASE | | SHOW THE PROPOSED CABANA IS 25 FEET FROM PROPERTY LINE | | PLEASE ALSO NOTE A SEPERATE PERMIT IS REQUIRED FOR | | LANDSCAPE PLANS AND ARTIFICAL TURF | | | | PLEASE NOTE WHICH PROJECTS ARE PROPOSED UNDER THIS | | PERMIT | | | | POOL AND POOL EQUIPMENT REQUIRE SEPERATE PERMITS | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | PLANNER | | [email protected] | | | | | | |
|
|