Plan Review Details - Permit 23010094
Plan Review Stops For Permit 23010094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-11 Cont ID  
Sent By jgomez Date 2023-04-11 Time 16:48 Rev Time 0.00
Received By jgomez Date 2023-04-11 Time 14:09 Sent To  
Notes
2023-04-11 16:48:59RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23010094
 19118 GLENMOOR DR
  
  
 NOTE:
 LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 1-DRAWINGS SUBMITTED DON'T HAVE THE SEAL/SIGNATURE OF
 THE ENGINEER OF RECORD. PLANS/DOCUMENTS NEED TO HAVE
 THE ORIGINAL SEAL/SIGNATURE OF THE ENGINEER OF RECORD
 AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT
 PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- FLOOR PLAN ON SHEET S-1.0 SHOWS NEW SLABS (BY
 OTHERS) OUTSIDE THE NEW SLIDING GLASS DOORS. THIS IS A
 CONDOMINIUM. OWNER ONLY OWNS THE UNIT, THE AREA OUTSIDE
 THE BUILDING IS NOT OWNED BY THIS OWNER. ANY WORK
 OUTSIDE THIS UNIT NEED TO BE DONE BY THE OWNER OF THE
 PROPERTY. REVISE PLANS AS REQUIRED. DON???T INCLUDE
 THIS WORK.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- REVISE OCCUPANCY GROUP SPECIFIED ON SHEET S-0.0.
 THIS IS A CONDOMINIUM. THE OCCUPANCY CLASSIFICATION IS
 R2 NOT R3. REVISE AS REQUIRED. SEC. 310.4 FBC-BUILDING.
  
 4- PROVIDE DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. 1710.3 FBC-BUILDING. SPECIFY
 STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. SEC. 1710.3
 FBC-BUILDING.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR WALL
 FLASHING AT ALL EXTERIOR OPENINGS AS REQUIRED BY SEC.
 1405.4 FBC-BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By   Date 2023-01-30 Time 16:49 Rev Time 0.00
Received By eroseber Date 2023-01-30 Time 16:49 Sent To  
Notes
2023-01-30 16:52:291. THIS PROJECT APPEARS TO BE AN ADDITION OF A SUNROOM
 AND NOT JUST A WINDOW/DOOR REPLACEMENT. PLEASE SUBMIT
 FOR CORRECT PERMIT AND SCOPE OF WORK WITH WPB BUILDING
 DEPT. FBC 107.2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-12 Cont ID  
Sent By rperdomo Date 2023-04-12 Time 13:06 Rev Time 0.00
Received By rperdomo Date 2023-04-12 Time 12:36 Sent To  
Notes
2023-04-12 13:06:28FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE ELECTRICAL SCOPE OF WORK. FBC 107.2.1,
 107.3.5
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2023-04-12 Cont ID  
Sent By pleduc Date 2023-04-12 Time   Rev Time 0.00
Received By pleduc Date 2023-04-12 Time 09:34 Sent To  
Notes
2023-04-12 09:39:09A LIFE SAFETY REVIEW IS NOT REQUIRED FOR A R 3
 OCCUPANCY.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-13 Cont ID  
Sent By aoliver Date 2023-04-13 Time 08:56 Rev Time 0.00
Received By aoliver Date 2023-03-22 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By eroseber Date 2023-01-30 Time 16:53 Rev Time 0.00
Received By eroseber Date 2023-01-05 Time 09:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-04-11 Cont ID  
Sent By jgomez Date 2023-04-11 Time 15:44 Rev Time 0.00
Received By jgomez Date 2023-04-11 Time 15:44 Sent To  
Notes
2023-04-11 15:44:22IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-11 Cont ID  
Sent By jgomez Date 2023-04-11 Time 15:39 Rev Time 0.00
Received By jgomez Date 2023-04-11 Time 15:39 Sent To  
Notes
2023-04-11 15:41:59SIGNATURE REVIEW:
  
 1-DRAWINGS SUBMITTED DON'T HAVE THE SEAL/SIGNATURE OF
 THE ENGINEER OF RECORD. PLANS/DOCUMENTS NEED TO HAVE
 THE ORIGINAL SEAL/SIGNATURE OF THE ENGINEER OF RECORD
 AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT
 PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By eroseber Date 2023-01-30 Time 16:53 Rev Time 0.00
Received By eroseber Date 2023-01-30 Time 16:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-27 Cont ID  
Sent By VBroglia Date 2023-03-27 Time 16:02 Rev Time 0.00
Received By vbroglia Date 2023-03-27 Time 16:02 Sent To  
Notes
2023-03-27 16:02:593/27/2023 FAILED
  
 PLEASE PROVIDE A SURVEY OR SITE PLAN THAT SHOWS THE
 SETBACKS OF THE ENCLOSED PATIO
  
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  