Plan Review Details - Permit 23010048
Plan Review Stops For Permit 23010048
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By cpuell Date 2023-01-05 Time 11:50 Rev Time 0.00
Received By cpuell Date 2023-01-05 Time 11:50 Sent To  
Notes
2023-01-05 11:50:50ADDRESS APPROPRIATE FOR PROJECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-09 Cont ID  
Sent By cwalker Date 2023-01-09 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 10:14 Rev Time 0.00
Received By medwards Date 2023-01-05 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 10:13 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 10:13 Sent To  
Notes
2023-01-13 10:14:061ST REVIEW FMC
 PERMIT: 23010048
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1 OF 5: UNDER THE AIR BALANCE REPORT; A NOTE
 STATES ??? BUILDING HVAC SYSTEM TO PROVIDE MORE THAN
 600 CFM TO INSURE OVERALL BUILDING BALANCE IS POSITIVE.
 PROVIDE THE BUILDING MECHANICAL SYSTEM CALCULATIONS
 SHOWING THAT THE SYSTEM CAN PRODUCE THE REQUIRED
 ADDITIONAL AIR FOR THIS HOOD SYSTEM. FBC 107.3.5
  
 2) SHEET 2 OF 5: EXPLAIN THE USE OF THE 2 - 5 TON
 CONDENSING UNITS.
  
 3) PROVIDE A DEMO DRAWING OF WHAT IS TO BE REMOVED.
 FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 10:14 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 10:14 Sent To  
Notes
***NONE***