Plan Review Details - Permit 22121144
Plan Review Stops For Permit 22121144
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-07-14 Cont ID  
Sent By cpuell Date 2023-07-14 Time 15:43 Rev Time 0.00
Received By cpuell Date 2023-07-14 Time 15:43 Sent To  
Notes
2023-07-14 15:44:04PARCELS UPDATED, ADDRESS AND PARCEL CORRECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-11 Cont ID  
Sent By cpuell Date 2023-01-11 Time 10:02 Rev Time 0.00
Received By cpuell Date 2023-01-11 Time 10:02 Sent To  
Notes
2023-01-11 10:10:05OWNER SEAN HEYNIGER EMAILED ME IN DEC 2022 ABOUT THIS
 PROJECT, I RESPONDED WITH THESE COMMENTS: WILL YOU BE
 CREATING A NEW PARCEL, AND IF SO WHAT STAGE ARE YOU AT
 WITH THAT PROCESS? THE ADDRESSES AVAILABLE TO US WOULD
 BE 3134, 3136 AND 3138 WASHINGTON RD. YOU CAN CHOOSE
 ANY OF THOSE. HOWEVER, THE OWNER NEVER FOLLOWED UP. IF
 THE BUILDING IS GOING TO BE MOVED FROM PARCEL
 74434334050170040 TO A NEWLY CREATED PARCEL THAT
 ENCOMPASSES PORTIONS OF PARCELS 74434334050170040 AND
 74434334050170050. A NEW PARCEL WILL NEED TO BE
 CREATED, YOU WILL NEED TO CONTACT VINCE NOEL
 [email protected] OR CALL 561-494-1040 TO START THE
 PROCESS. YOU WILL NEED TO REQUEST A NEW PARCEL CONTROL
 NUMBER FROM THE PROPERTY APPRAISERS AT THIS LINK
 HTTPS://WWW.PBCGOV.ORG/PAPA/DEPARTMENTS/GIS.HTM, THEY
 WILL ISSUE YOU WITH A NEW PARCEL CONTROL NUMBER (PCN).
 WHEN YOU CONTACT THE PROPERTY APPRAISERS YOU NEED TO
 REQUEST PRELIMINARY LETTER OF THE PROPOSED PCN. ONCE
 YOU HAVE RECEIVED THE PRELIMINARY LETTER, PLEASE
 CONTACT [email protected] OR CALL 561-805-6659 TO
 BE ISSUED AN ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-20 Cont ID  
Sent By rmcphers Date 2023-07-20 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2023-07-20 Time 15:10 Sent To  
Notes
2023-07-20 15:46:03RE LOCATING A SFR - NEW FOUNDATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT.
  
 2) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 BUILDING, THE BASE FLOOD DELINEATION LINES AND THE FEMA
 BASE FLOOD ELEVATIONS.
  
 3) CRAWL SPACE = ADDED AIR VENTS WILL NOT WORK FOR
 FLOOD VENTS UNLESS THE LOUVER OPENINGS ARE 3" APART -
 R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 (2.2.) OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM)
 IN ANY DIRECTION IN THE PLANE OF THE WALL. R408.7 FLOOD
 RESISTANCE.
 FOR BUILDINGS LOCATED IN FLOOD HAZARD AREAS AS
 ESTABLISHED IN TABLE R301.2(1):
  
 A).WALLS ENCLOSING THE UNDER-FLOOR SPACE SHALL BE
 PROVIDED WITH FLOOD OPENINGS IN ACCORDANCE WITH SECTION
 R322.2.2.
  
 B).THE FINISHED GROUND LEVEL OF THE UNDER-FLOOR SPACE
 SHALL BE EQUAL TO OR HIGHER THAN THE OUTSIDE FINISHED
 GROUND LEVEL ON AT LEAST ONE SIDE.
  
  
 4) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC WPB 107.3.5
  
 5) PLEASE PROVIDE FLOOD VENT CERTIFICATION/EVALUATION
 AND PRODUCT APPROVALS.
  
 6) THE TOILET ROOM IN THE GARAGE WILL NEED FLOOD VENTS
 - FBC R322.2.2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 15:21 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 13:42 Sent To  
Notes
2023-02-03 15:10:05RE LOCATING A SFR - NEW FOUNDATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-1 - SECTION 1/S-1 - PLEASE SHOW THE
 BUILDING ANCHORAGE (HURRICANE STRAPS) TO THE NEW
 FOUNDATION - FBC R301.1
  
 2) DRAWING S-1 -SECTIONS 2 AND 3 LOOK TO BE IN THE
 WRONG PLACE ON THE PLAN - PLEASE CHECK CUT SECTION
 LOCATIONS.
  
 3) DRAWING S-4 - SECTIONS 6 AND 7 - LOCATIONS ARE NOT
 SHOWN ON THE PLAN.
  
 4) DRAWING S-1 - SECTIONS 4 AND 5 - LOCATIONS ARE NOT
 SHOWN ON THE PLAN.
  
 5) DRAWING A-4 - PLEASE SHOW THE STEP DIMENSION FROM
 THE FIRST FLOOR TO THE FRONT PORCH.
  
 6) PLEASE SHOW UNDER FLOOR VENTILATION LOCATIONS PER -
 FBC R408.1 VENTILATION.
 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS
 THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM
 NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN
 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 SQUARE FEET (14
 M2) OF UNDER-FLOOR SPACE AREA, UNLESS THE GROUND
 SURFACE IS COVERED BY A CLASS 1 VAPOR RETARDER
 MATERIAL. WHERE A CLASS 1 VAPOR RETARDER MATERIAL IS
 USED, THE MINIMUM NET AREA OF VENTILATION OPENINGS
 SHALL BE NOT LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR
 EACH 1,500 SQUARE FEET (140 M2) OF UNDER-FLOOR SPACE
 AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3
 FEET (914 MM) OF EACH CORNER OF THE BUILDING.
  
 7) SHOW THE ACCESS FOR THE CRAWL SPACE - FBC R408.4
 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16
 INCHES BY 24 INCHES (407 MM BY 610 MM). WHERE ANY
 PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN
 AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM BY
 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY
 SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING.
 THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER
 A DOOR TO THE RESIDENCE.
  
 8) PLEASE PROVIDE A SOIL REPORT.
  
 9) PLEASE SHOW THE STORM WATER DRAINAGE FLOW AWAY FROM
 THE BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE
 SITE PLAN - FBC WPB107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 10) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 BUILDING, THE BASE FLOOD DELINEATION LINES AND THE FEMA
 BASE FLOOD ELEVATIONS.
  
 11) PLEASE SHOW THE GARAGE FLOOR ELEVATION - ELEVATIONS
 LOWER THAN 2 FEET ABOVE FEMA BASE FLOOD ELEVATION WILL
 REQUIRE FLOOD VENTS - FBC R322.2.2
  
 12) PLEASE SHOW THE FLOOR ELEVATION FOR THE
 LAUNDRY/RESTROOM IN THE GARAGE - MUST BE 2 FEET ABOVE
 FEMA BASE FLOOD ELEVATION FBC R322.2.1
  
 13) PLEASE SHOW THE GARAGE FLOOR TO SLOPE PER FBC
 R309.1
  
 14) R408.7 FLOOD RESISTANCE.
 FOR BUILDINGS LOCATED IN FLOOD HAZARD AREAS AS
 ESTABLISHED IN TABLE R301.2(1):
  
 1.WALLS ENCLOSING THE UNDER-FLOOR SPACE SHALL BE
 PROVIDED WITH FLOOD OPENINGS IN ACCORDANCE WITH SECTION
 R322.2.2.
  
 2.THE FINISHED GROUND LEVEL OF THE UNDER-FLOOR SPACE
 SHALL BE EQUAL TO OR HIGHER THAN THE OUTSIDE FINISHED
 GROUND LEVEL ON AT LEAST ONE SIDE.
  
 15) PLEASE SHOW THE REQUIRED TERMITE PROTECTION - FBC
 R318
  
 16) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC WPB 107.3.5
  
 17) PLEASE PROVIDE FLOOD VENT CERTIFICATION/EVALUATION
 AND PRODUCT APPROVALS.
  
 18) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING
 BUILDING DEMO AND DRIVEWAY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-24 Cont ID  
Sent By rperdomo Date 2023-07-24 Time 16:01 Rev Time 0.00
Received By rperdomo Date 2023-07-24 Time 15:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By rperdomo Date 2023-01-19 Time 12:15 Rev Time 0.00
Received By rperdomo Date 2023-01-19 Time 09:40 Sent To  
Notes
2023-01-19 12:13:30FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE AN ELECTRICAL DRAWING SHOWING THE STEEL
 REINFORCING BARS (STEEL REBAR ) TO BE BONDED. NEC
 250.52
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-07-18 Cont ID  
Sent By cseifer Date 2023-07-18 Time 16:02 Rev Time 0.00
Received By cseifer Date 2023-07-18 Time 16:01 Sent To  
Notes
2023-07-18 16:02:01PASSED WITH PROVISO: OBTAIN PERMIT FOR WORK IN ROW.
  
 THANKS,
 CHLOE SEIFER, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By rrossano Date 2023-01-18 Time   Rev Time  
Received By rrossano Date 2023-01-18 Time   Sent To  
Notes
2023-01-18 05:47:44PLEASE RESPOND TO ADDRESSING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2023-01-20 Cont ID  
Sent By cwalker Date 2023-01-20 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-01-20 09:38:40SFH, FIRE REVIEW NOT REQUIRED

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-07-18 Cont ID  
Sent By ccole Date 2023-07-18 Time 16:40 Rev Time 0.00
Received By ccole Date 2023-07-18 Time 16:07 Sent To  
Notes
2023-07-18 16:41:36GAS UNDER SEPARATE PERMIT IN SECOND PHASE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By ccole Date 2023-01-17 Time 16:01 Rev Time 0.00
Received By ccole Date 2023-01-17 Time 16:01 Sent To  
Notes
2023-01-17 16:44:311ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22121144
 1/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A3 & A4: PROVIDE GAS DEMOLITION NOTES AND
 DETAILS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By fmittner Date 2023-07-19 Time 09:54 Rev Time 0.00
Received By fmittner Date 2023-07-19 Time 09:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-02-02 Cont ID  
Sent By fmittner Date 2023-02-02 Time 15:45 Rev Time 0.00
Received By fmittner Date 2023-02-02 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-25 Cont ID  
Sent By aoliver Date 2023-07-25 Time 06:58 Rev Time 0.00
Received By aoliver Date 2023-07-12 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 15:22 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 12:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 15:10 Sent To  
Notes
2023-02-03 15:11:50PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2023-07-20 Cont ID  
Sent By rmcphers Date 2023-07-20 Time 15:54 Rev Time 0.00
Received By rmcphers Date 2023-07-20 Time 15:54 Sent To  
Notes
2023-07-20 15:55:12SEE BUILDING PLAN REVIEW

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 15:12 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 15:12 Sent To  
Notes
2023-02-03 15:13:02SEE BUILDING PLAN REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-07-18 Cont ID  
Sent By ccole Date 2023-07-18 Time 16:38 Rev Time 0.00
Received By ccole Date 2023-07-18 Time 16:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By ccole Date 2023-01-17 Time 15:58 Rev Time 0.00
Received By ccole Date 2023-01-17 Time 15:53 Sent To  
Notes
2023-01-17 16:01:421ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22121144
 1/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SANITARY DRAIN AND VENT ISOMETRIC DRAWING
 SHOWING THE NEW UNDERGROUND PLUMBING IN THE NEW
 FOUNDATION- SEC. 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By rmcphers Date 2023-07-20 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2023-07-20 Time 15:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By rwbrown Date 2023-01-30 Time 09:21 Rev Time 0.00
Received By rwbrown Date 2023-01-30 Time 09:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-07-19 Cont ID  
Sent By fmittner Date 2023-07-19 Time 09:53 Rev Time 0.00
Received By fmittner Date 2023-07-19 Time 09:53 Sent To  
Notes
2023-07-19 09:53:44SEE COMMENTS FROM FIRST REVIEW

Review Stop Z ZONING
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By AHamilto Date 2023-02-02 Time 15:45 Rev Time 0.00
Received By fmittner Date 2023-02-02 Time 15:45 Sent To  
Notes
2023-02-02 15:46:05FRONT SETBACK NOT DIMENSIONED.
 REQUIRES SEPERATE LANDSCAPE PLAN