Plan Review Details - Permit 22121061
Plan Review Stops For Permit 22121061
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 11:27 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 17:01 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 12:23 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 11:27 Sent To  
Notes
2023-01-31 12:23:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121061
 ADD: 1401 FORUM WAY # 600
 CONT: HALLMARK CONSTRUCTION
 TEL: 561-324-8556
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31ST/ 2023
 ACTION: DENIED
  
 1) THE FLOOR PLAN A1.1 NOTE # 8 REFERS TO A NEW HI-LOW
 DRINKING FOUNTAIN REFERS TO SHEET A0.2 FOR MOUNTING
 DETAILS. SHEET A0.2 DOES NOT SHOW A HI-LOW DRINKING
 FOUNTAIN A LOW DRINKING FOUNTAIN AND A BOTTLE FILL
 STATION PLEASE PROVIDE COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 602.7 SPOUT HEIGHT FOR
 THE STANDING PERSONS SHALL BE BETWEEN 38 TO 43 INCHES
 ABOVE FINISH FLOOR.
  
 2) SHEET A1.1 THE RESTROOMS 621 & 622 BOTH SHOW A
 INSWING DOOR WHAT IS MISSING IS THE REQUIRED 30X48 INCH
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY
 AT A 45% ANGLE TO THE DOOR ENTRANCE. SEE FIGURE
 604.8.1.6 EXCEPTION # 2.
  
 3) SHEET A1.3 RESTROOMS 623 JANITORS CLOSET, 621 & 622
 ALL SHOW P-1 WALL FINISHES GENERAL WALL PAINT. 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE. 1210.2.2 WALLS & PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-16 Cont ID  
Sent By rperdomo Date 2023-03-16 Time 15:09 Rev Time 0.00
Received By rperdomo Date 2023-03-16 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By rperdomo Date 2023-01-30 Time 15:17 Rev Time 0.00
Received By rperdomo Date 2023-01-30 Time 14:14 Sent To  
Notes
2023-01-30 15:17:06FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF THE FOLLOWING FEEDERS
 (INCLUDING PROTECTION AND EQUIPMENT GROUNDING
 CONDUCTORS IN ACCORDANCE WITH NEC 215, 250.122 :
 A. EX. METER TO EX PANEL "6H" 200A
 B. EX PANEL '6H1" 200A TO EX PANEL "6H2"
  
 2. PROVIDE INFORMATION OF THE 75 KVA TRANSFORMER
 PRIMARY AND SECONDARY CONDUCTORS AND PROTECTION. NEC
 450
  
 3. PROVIDE INFORMATION OF SERVICE CONDUCTORS. NEC 230
  
 END OF COMMENTS
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-04-14 Cont ID  
Sent By mpeterso Date 2023-04-14 Time 12:10 Rev Time 0.00
Received By mpeterso Date 2023-04-14 Time 12:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By cwalker Date 2023-03-01 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-01 10:21:28FIRE REVIEW COMMENTS:
  
 (1) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS 9FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
  
 (3) ANY WORK BEING PERFORMED ON ANY LIFE SAFETY SYSTEM
 SHALL ONLY BE DONE BY PROPERLY LICENSED CONTRACTORS.
  
 (4) ALL EXITS TO COMPLY WITH MARKING MEANS OF EGRESS
 PER NFPA 101, 7.10
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-29 Cont ID  
Sent By cwalker Date 2022-12-29 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-12-29 13:05:12FIRE REVIEW COMMENTS:
  
 (1) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 DURING ALL PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (3) ANY WORK BEING PERFORMED ON ANY LIFE SAFETY SYSTEM
 SHALL ONLY BE DONE BY PROPERLY LICENSED CONTRACTORS.
  
 (4) ALL EXITS TO COMPLY WITH MARKING MEANS OF EGRESS
 PER NFPA 101, 7.10
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-17 Cont ID  
Sent By aoliver Date 2023-03-17 Time 07:33 Rev Time 0.00
Received By aoliver Date 2023-02-27 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-01-31 Time   Rev Time 0.00
Received By amcgrego Date 2022-12-28 Time 10:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By medwards Date 2023-03-09 Time 09:53 Rev Time 0.00
Received By medwards Date 2023-03-09 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-17 Cont ID  
Sent By medwards Date 2023-01-17 Time 15:34 Rev Time 0.00
Received By medwards Date 2023-01-17 Time 15:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By rwbrown Date 2023-03-01 Time 14:02 Rev Time 0.00
Received By rwbrown Date 2023-03-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rwbrown Date 2023-01-17 Time 12:02 Rev Time 0.00
Received By rwbrown Date 2023-01-17 Time 12:02 Sent To  
Notes
2023-01-17 12:09:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 901.2.1 - THE WATER CLOSETS ARE NOT VENTED
 TO CODE. IF ATTEMPTING TO WET VENT THEM, THE MOP SINK
 AND DRINKING FOUNTAIN WOULD NEED TO DISCHARGE
 DOWNSTREAM OF THE WET VENT SYTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 17:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By rwbrown Date 2023-01-30 Time 13:32 Rev Time 0.00
Received By rwbrown Date 2023-01-30 Time 13:31 Sent To  
Notes
2023-01-17 15:35:01MECHANICAL DIGITAL SIGNATURES APPROVED ME
  