Plan Review Details - Permit 22121040
Plan Review Stops For Permit 22121040
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-10 Cont ID  
Sent By mpeterso Date 2023-02-10 Time 14:13 Rev Time 0.00
Received By mpeterso Date 2023-02-08 Time 11:20 Sent To  
Notes
2023-02-10 14:15:16ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC WORK SCOPE AND PLAN AS
 APPLICABLE OR STATE NO ELECTRIC WORK IS TO BE DONE.
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2023-02-08 12:41:343RD GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. THE EXISTANCE OF A HOOD DOES NOT SUPPLY COMBUSTION
 AIR - YOU NEED TO SHOW THAT THE CALCULATIONS OF THE
 CUBIC FEET OF THE SPACE USED AND THAT THERE IS AT LEAST
 50 CUBIC FEET PER 1000 BTU, OR SUPPLY COMBSTION AIR BY
 ONE OF THE APPROVED METHODS. YOU SHOULD BE SHOWING ME
 THE CUBIC FOOT IN A COMMUNICATED SPACE WITHOUT BARRIERS
 OR DOORS AND DIVIDE BY THE NUMBER OF BTU'S USED. SEE
 SECTION 304.1 FOR MORE INFORMATION.
  
 COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE
 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED.
 - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND
 CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS
 NOT NEEDED.
  
 4. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 06:24 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 06:23 Sent To  
Notes
2023-02-06 06:28:522 GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE
 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED.
 - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND
 CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS
 NOT NEEDED.
  
 4. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 07:13 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 07:13 Sent To  
Notes
2022-12-30 07:20:431ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 - PLEASE SUBMIT A
 DRAWING THAT INCLUDES THE EXISTING SYSTEM FOR SIZING
 CONFIRMATION. THE EXISTING SYSTEM MUST BE VERIFIED TO
 BE SIZED CORRECTLY IN ORDER TO SUPPLY THE NEW BRANCH.
 THIS SHOULD BE CONSIDERED FOR EVERY ADDITION TO A GAS
 SYSTEM. YOUR SIZING TABLE SHOULD BE FOR THE "LONGEST
 RUN" IN THE WHOLE SYSTEM, NOT THE DEVELOPED LENGTH OF
 THE ADDITION.
  
 2. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE DETAILS OR
 NOTATION OF EXISTING VENTING FOR THE APPLIANCES. IS
 THIS UNDER AN EXISTING HOOD?
  
 3. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE MEASUREMENTS
 AND CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT
 IT IS NOT NEEDED.
  
 4. 2017 WPB AMENDS 107.3.5.1.5 - LABEL THE TYPE OF GAS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-10 Cont ID  
Sent By mpeterso Date 2023-02-10 Time 14:15 Rev Time 0.00
Received By mpeterso Date 2023-02-07 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 06:28 Rev Time 0.00
Received By rwbrown Date 2023-02-03 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 07:20 Rev Time 0.00
Received By rwbrown Date 2022-12-28 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2023-02-08 Cont ID  
Sent By rwbrown Date 2023-02-08 Time 12:41 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 06:23 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 06:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 07:13 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 07:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2023-02-08 Cont ID  
Sent By rwbrown Date 2023-02-08 Time 12:42 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 06:23 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 07:20 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***