Plan Review Stops For Permit 22121040 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-02-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-02-10 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-08 |
Time |
11:20 |
Sent To |
|
|
Notes |
2023-02-10 14:15:16 | ELECTRIC REVIEW FAILED | | | | 1) PLEASE PROVIDE AN ELECTRIC WORK SCOPE AND PLAN AS | | APPLICABLE OR STATE NO ELECTRIC WORK IS TO BE DONE. | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-02-08 12:41:34 | 3RD GAS REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | 2. DONE | | | | 3. THE EXISTANCE OF A HOOD DOES NOT SUPPLY COMBUSTION | | AIR - YOU NEED TO SHOW THAT THE CALCULATIONS OF THE | | CUBIC FEET OF THE SPACE USED AND THAT THERE IS AT LEAST | | 50 CUBIC FEET PER 1000 BTU, OR SUPPLY COMBSTION AIR BY | | ONE OF THE APPROVED METHODS. YOU SHOULD BE SHOWING ME | | THE CUBIC FOOT IN A COMMUNICATED SPACE WITHOUT BARRIERS | | OR DOORS AND DIVIDE BY THE NUMBER OF BTU'S USED. SEE | | SECTION 304.1 FOR MORE INFORMATION. | | | | COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE | | 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED. | | - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND | | CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS | | NOT NEEDED. | | | | 4. DONE | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-06 |
Time |
06:24 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-06 |
Time |
06:23 |
Sent To |
|
|
Notes |
2023-02-06 06:28:52 | 2 GAS REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | 2. DONE | | | | 3. COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE | | 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED. | | - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND | | CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS | | NOT NEEDED. | | | | 4. DONE | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-12-30 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-12-30 |
Time |
07:13 |
Sent To |
|
|
Notes |
2022-12-30 07:20:43 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMENDS 107.3.5.1.5 - PLEASE SUBMIT A | | DRAWING THAT INCLUDES THE EXISTING SYSTEM FOR SIZING | | CONFIRMATION. THE EXISTING SYSTEM MUST BE VERIFIED TO | | BE SIZED CORRECTLY IN ORDER TO SUPPLY THE NEW BRANCH. | | THIS SHOULD BE CONSIDERED FOR EVERY ADDITION TO A GAS | | SYSTEM. YOUR SIZING TABLE SHOULD BE FOR THE "LONGEST | | RUN" IN THE WHOLE SYSTEM, NOT THE DEVELOPED LENGTH OF | | THE ADDITION. | | | | 2. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE DETAILS OR | | NOTATION OF EXISTING VENTING FOR THE APPLIANCES. IS | | THIS UNDER AN EXISTING HOOD? | | | | 3. 2017 WPB AMENDS 107.3.5.1.5 - PROVIDE MEASUREMENTS | | AND CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT | | IT IS NOT NEEDED. | | | | 4. 2017 WPB AMENDS 107.3.5.1.5 - LABEL THE TYPE OF GAS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-02-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-02-10 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-02-07 |
Time |
10:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-02-06 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-06 |
Time |
06:28 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-03 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-12-30 |
Time |
07:20 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-12-28 |
Time |
09:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2023-02-08 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-08 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2023-02-06 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-06 |
Time |
06:23 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-06 |
Time |
06:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-12-30 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-12-30 |
Time |
07:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
N |
Date |
2023-02-08 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-08 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
N |
Date |
2023-02-06 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-06 |
Time |
06:23 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-12-30 |
Time |
07:20 |
Rev Time |
|
Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|