Plan Review Details - Permit 22121018
Plan Review Stops For Permit 22121018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-01-04 Cont ID  
Sent By rmcphers Date 2023-01-04 Time 13:57 Rev Time 0.00
Received By rmcphers Date 2023-01-04 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By jleahy Date 2023-01-20 Time 07:55 Rev Time 0.00
Received By jleahy Date 2023-01-19 Time 16:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By jcclark Date 2023-01-05 Time   Rev Time  
Received By bdolan Date 2023-01-05 Time 12:40 Sent To  
Notes
2023-01-05 12:50:39THE FOLLOWING COMMENTS WERE SUBMITTED BY CAPT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 ALL WORK ON THE UNDERGROUND FIRE MAIN IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED UNDERGROUND CONTRACTOR AND
 SHALL COMPLY WITH NFPA 24 STANDARD FOR THE INSTALLATION
 OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES.
 SEPARATE SHOP DRAWINGS COMPLIANT WITH 61G15-32.004
 DESIGN OF WATER BASED FIRE PROTECTION SYSTEMS ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-29 Cont ID  
Sent By hmoser Date 2023-06-29 Time 13:11 Rev Time 0.00
Received By hmoser Date 2023-06-08 Time 08:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-20 Cont ID  
Sent By jleahy Date 2023-01-20 Time 07:55 Rev Time 0.00
Received By jleahy Date 2022-12-29 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-29 Cont ID  
Sent By hmoser Date 2023-06-29 Time 13:10 Rev Time 0.00
Received By hmoser Date 2023-06-29 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 10:01 Rev Time 0.00
Received By medwards Date 2023-01-10 Time 10:01 Sent To  
Notes
2023-01-10 10:01:471ST REVIEW FMC
 PERMIT: 22121018
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.3: OUTSIDE AIR CALCULATIONS; AHU-1 HAS 2
 111B OFFICE SPACES IN SPACE NAME. IN SPACE CATEGORY IT
 LISTS THE SECOND ONE AS STORAGE. SHEET A-0-30 DOES NOT
 SHOW A STORAGE IN THIS AREA. THE OUTDOOR AIR
 CALCULATIONS ON SHEET M0.3 SHOULD REFLECT THE OFFICE
 AND NOT STORAGE. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-16 Cont ID  
Sent By ccole Date 2023-06-16 Time 10:57 Rev Time 0.00
Received By ccole Date 2023-06-16 Time 10:20 Sent To  
Notes
2023-06-16 10:59:512ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22181018
 6/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST. P3.2: THE REVISED ISOMETRIC SHOWS HOT
 WATER REMOVED FROM THE SINK ON THE ROOF WHICH DOES NOT
 COMPLY WITH SEC. 607.1 FBC P. HOT WATER SHALL BE
 PROVIDED TO THE SINK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By ccole Date 2023-01-06 Time 16:20 Rev Time 0.00
Received By ccole Date 2023-01-06 Time 15:27 Sent To  
Notes
2023-01-06 16:21:161ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22181018
 1/6/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.2: THE REVISED WATER HEATER DETAIL NO.3
 DOES NOT SHOW A MASTER THERMOSTATIC MIXING VALVE WILL
 BE INSTALLED TO LIMIT THE TEMPERATURE OF THE HOT WATER-
 SEC. 607.1.1 FBC P. PLEASE REVISE THE DETAIL TO THE
 SHOW THE DEVICE AND WATER PIPING CONNECTIONS.
  
 2) P3.2: THE REVISED ISOMETRIC SHOWS HOT WATER REMOVED
 FROM THE SINK ON THE ROOF WHICH DOES NOT COMPLY WITH
 SEC. 607.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-29 Cont ID  
Sent By hmoser Date 2023-06-29 Time 13:07 Rev Time 0.00
Received By hmoser Date 2023-06-29 Time 13:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-04 Cont ID  
Sent By rmcphers Date 2023-01-04 Time 13:57 Rev Time 0.00
Received By rmcphers Date 2023-01-04 Time 13:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-01-19 Cont ID  
Sent By llouie Date 2023-01-19 Time   Rev Time  
Received By llouie Date 2023-01-19 Time   Sent To  
Notes
2023-01-19 16:36:12ZONING APPROVED WITH THE FOLLOWING PROVISO(S):
  
 1.) SCOPE OF PERMIT IS FOR THE REVISION OF THE OFFICE
 BUILDING ONLY (MASTER PERMIT #21111010).
  
 2.) MINOR PLANNED DEVELOPMENT (PD) AMENDMENT FOR THE
 AS-BUILT WILL BE REQUIRED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 3.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 AREA, SIGNAGE, ETC.
  