Plan Review Stops For Permit 22121018 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2023-01-04 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-01-04 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-01-04 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-01-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-01-20 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-01-19 |
Time |
16:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
Sent By |
jcclark |
Date |
2023-01-05 |
Time |
|
Rev Time |
|
Received By |
bdolan |
Date |
2023-01-05 |
Time |
12:40 |
Sent To |
|
|
Notes |
2023-01-05 12:50:39 | THE FOLLOWING COMMENTS WERE SUBMITTED BY CAPT. BRIAN | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | FIRE RESCUE. | | | | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE | | BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING | | COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED, | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | PRIOR TO ANY INSTALLATION. | | | | ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE | | COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND | | SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | ALL WORK ON THE UNDERGROUND FIRE MAIN IS REQUIRED TO BE | | COMPLETED BY A CERTIFIED UNDERGROUND CONTRACTOR AND | | SHALL COMPLY WITH NFPA 24 STANDARD FOR THE INSTALLATION | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES. | | SEPARATE SHOP DRAWINGS COMPLIANT WITH 61G15-32.004 | | DESIGN OF WATER BASED FIRE PROTECTION SYSTEMS ARE | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. | | | | CAPT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2023-06-29 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2023-06-08 |
Time |
08:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-01-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-01-20 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-12-29 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-06-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2023-06-29 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2023-06-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-01-10 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-10 |
Time |
10:01 |
Sent To |
|
|
Notes |
2023-01-10 10:01:47 | 1ST REVIEW FMC | | PERMIT: 22121018 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M0.3: OUTSIDE AIR CALCULATIONS; AHU-1 HAS 2 | | 111B OFFICE SPACES IN SPACE NAME. IN SPACE CATEGORY IT | | LISTS THE SECOND ONE AS STORAGE. SHEET A-0-30 DOES NOT | | SHOW A STORAGE IN THIS AREA. THE OUTDOOR AIR | | CALCULATIONS ON SHEET M0.3 SHOULD REFLECT THE OFFICE | | AND NOT STORAGE. FMC 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2023-06-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-06-16 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-06-16 |
Time |
10:20 |
Sent To |
|
|
Notes |
2023-06-16 10:59:51 | 2ND REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22181018 | | 6/16/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) 2ND REQUEST. P3.2: THE REVISED ISOMETRIC SHOWS HOT | | WATER REMOVED FROM THE SINK ON THE ROOF WHICH DOES NOT | | COMPLY WITH SEC. 607.1 FBC P. HOT WATER SHALL BE | | PROVIDED TO THE SINK. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-01-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-01-06 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-01-06 |
Time |
15:27 |
Sent To |
|
|
Notes |
2023-01-06 16:21:16 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22181018 | | 1/6/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P0.2: THE REVISED WATER HEATER DETAIL NO.3 | | DOES NOT SHOW A MASTER THERMOSTATIC MIXING VALVE WILL | | BE INSTALLED TO LIMIT THE TEMPERATURE OF THE HOT WATER- | | SEC. 607.1.1 FBC P. PLEASE REVISE THE DETAIL TO THE | | SHOW THE DEVICE AND WATER PIPING CONNECTIONS. | | | | 2) P3.2: THE REVISED ISOMETRIC SHOWS HOT WATER REMOVED | | FROM THE SINK ON THE ROOF WHICH DOES NOT COMPLY WITH | | SEC. 607.1 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-06-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2023-06-29 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2023-06-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-01-04 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-01-04 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-01-04 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2023-01-19 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2023-01-19 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2023-01-19 |
Time |
|
Sent To |
|
|
Notes |
2023-01-19 16:36:12 | ZONING APPROVED WITH THE FOLLOWING PROVISO(S): | | | | 1.) SCOPE OF PERMIT IS FOR THE REVISION OF THE OFFICE | | BUILDING ONLY (MASTER PERMIT #21111010). | | | | 2.) MINOR PLANNED DEVELOPMENT (PD) AMENDMENT FOR THE | | AS-BUILT WILL BE REQUIRED PRIOR TO THE ISSUANCE OF A | | CERTIFICATE OF OCCUPANCY (C.O.). | | | | 3.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING | | AREA, SIGNAGE, ETC. | | |
|
|