Plan Review Details - Permit 22120925
Plan Review Stops For Permit 22120925
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By rmcdouga Date 2023-04-03 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2023-04-03 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By rmcdouga Date 2023-02-13 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2023-02-13 Time 09:51 Sent To  
Notes
2023-02-13 10:59:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA AND IS REQUIRED TO BE LOCATED AT OR ABOVE THE
 ELEVATION OF THE FINISH FLOOR OF THE HABITABLE SPACE OF
 THE DWELLING. FBC R322.1.6
  
 2) THE GENERATOR PAD ENGINEERING DOES NOT MEET THE
 WINDLOAD REQUIREMENTS FOR RISK CATEGORY 1 EXPOSURE D OF
 150 MPH. FBC AMENDMENTS 120.1 THE ENGINEERING FOR THE
 PAD HAS THE R032 GENERAC RATED AT 130 MPH FOR EXPOSURE
 D.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-16 Cont ID  
Sent By rperdomo Date 2023-03-16 Time 15:23 Rev Time 0.00
Received By rperdomo Date 2023-03-16 Time 15:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-05 Cont ID  
Sent By rperdomo Date 2023-01-05 Time 13:59 Rev Time 0.00
Received By rperdomo Date 2022-12-23 Time 11:47 Sent To  
Notes
2023-01-05 13:59:09FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATIONS AND ELCTRICAL PANEL
 SCHEDULES FOR ELECTRICAL PANEL 200 AMPS EXISTING
 ELECTRICAL PANEL AND FOR A NEW 100 AMPS SUB-PANEL,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY.
 NEC 215.2, 220, 408.4
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2023-02-14 Cont ID  
Sent By rwbrown Date 2023-02-14 Time 11:16 Rev Time 0.00
Received By rwbrown Date 2023-02-14 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-06 Cont ID  
Sent By aoliver Date 2023-04-06 Time 07:10 Rev Time 0.00
Received By aoliver Date 2023-03-09 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-16 Cont ID  
Sent By aoliver Date 2023-02-16 Time 09:17 Rev Time 0.00
Received By aoliver Date 2022-12-21 Time 05:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-01-12 Cont ID  
Sent By rwbrown Date 2023-01-12 Time 10:34 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By rgathrig Date 2023-04-05 Time 17:18 Rev Time 0.00
Received By rgathrig Date 2023-04-05 Time 17:18 Sent To  
Notes
2023-04-05 17:19:23PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
  
 REG

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2023-02-16 Cont ID  
Sent By jbaker Date 2023-02-16 Time 08:06 Rev Time 0.00
Received By jbaker Date 2023-02-16 Time 08:06 Sent To  
Notes
2023-02-16 08:06:00IN THE DESCRIPTION OF OPERATIONS /LOCATIONS/VEHICLES
 BOX AT BOTTOM OF COI FORM PROVIDE VERBIAGE:
  
 PERFORMANCE OF INSPECTIONS PURSUANT TO FS 553.791
 FIRM NAME:
 PRIVATE PROVIDER: NAME AND ALL DULY AUTHORIZED
 REPRESENTATIVES
  
 IN OTHER WORDS NEEDS TO MEET INTENT OF FS 553.791 4(B)
 DEMONSTRATING THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER???S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY AUTHORIZED
 REPRESENTATIVE IN THE AMOUNTS REQUIRED BY THIS SECTION.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By rmcdouga Date 2023-04-03 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2023-04-03 Time 14:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-13 Cont ID  
Sent By rmcdouga Date 2023-02-13 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2023-02-13 Time 10:59 Sent To  
Notes
2023-02-13 11:04:03THE GENERATOR PAD DRAWING IS SIGNED AND SEALED,
 HOWEVER, IT DOES NOT MEET THE REQUIRED WINDLOADS.
2023-01-30 08:06:03GAS DRAWING PROPERLY SIGNED BY CONTRACTOR

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-29 Cont ID  
Sent By asangele Date 2022-12-29 Time 16:23 Rev Time 0.00
Received By asangele Date 2022-12-29 Time 16:23 Sent To  
Notes
***NONE***