Plan Review Stops For Permit 22120625 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-25 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-25 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2023-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-20 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-20 |
Time |
15:05 |
Sent To |
|
|
Notes |
2023-04-20 15:34:06 | FOURTH BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22120625 | | 412 CLEMATIS ST | | | | 1- SIGN WAS REVISED. ENGINEER NEEDS TO REVISE THE WIND | | LOAD CALCULATIONS TO REFLECT PROPOSED SIGN. SEC. 1609.1 | | FBC-BUILDING. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | 2- ENGINEER TO SIGN AND SEAL ALL SIGN DRAWINGS | | SUBMITTED . | | ALL PLANS/DOCUMENTS NEED TO HAVE THE SEAL/SIGNATURE OF | | THE ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.001 | | FAC AND CHAPTER 471 F.S. WHEN SUBMITTING | | PLANS/DOCUMENTS FOR PUBLIC RECORDS. | | NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT | | PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL | | SIGNATURE. | | | | ENGINEERS | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-23 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-23 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-25 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-25 |
Time |
09:34 |
Sent To |
|
|
Notes |
2023-01-25 09:54:23 | BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22120625 | | 412 CLEMATIS ST | | | | 1- SIGN MEANS OF ATTACHMENT WAS REVISED. GENERAL | | STATEMENT DESCRIBED IN THE REVISED SIGN MEANS OF | | ATTACHMENT IS NOT ACCEPTABLE. ENGINEER OF RECORD NEEDS | | TO SPECIFY THE ANCHOR TYPE, SIZE AND SPACING AND NUMBER | | OF FASTENERS. SEC. 1609.1 FBC-BUILDING. | | | | 2- ENGINEER NEEDS TO PROVIDE COMPLETE DESIGN CRITERIA | | INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN | | WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND | | EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS | | REQUIRED BY SEC. 1603.1.4 FBC-BUILDING. SEC. 107.3.5 | | CITY AMENDMENTS. | | | | 3- REVISED STRUCTURAL DRAWINGS WERE NOT SIGNED AND | | SEALED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER | | NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE | | OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. | | 61G15-23.004 FAC AND CHAPTER 471 F.S. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-01-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-17 |
Time |
17:57 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-17 |
Time |
17:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-13 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-13 |
Time |
14:23 |
Sent To |
|
|
Notes |
2023-01-13 14:41:49 | BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22120625 | | 412 CLEMATIS ST | | | | 1- ENGINEER TO PROVIDE COMPLETE DESIGN CRITERIA | | INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN | | WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND | | EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS | | REQUIRED BY SEC. 1603.1.4 FBC. SEC. 107.3.5 CITY | | AMENDMENTS. | | | | 2- ENGINEER TO PROVIDE COMPLETE DETAIL/SPECIFICATIONS | | FOR INDIVIDUAL LETTERS ATTACHMENT. SEC. 1609.1 | | FBC-BUILDING. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2023-04-18 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2023-04-18 |
Time |
20:54 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2023-04-18 |
Time |
20:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2023-02-08 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2023-02-07 |
Time |
18:40 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2023-02-07 |
Time |
18:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2023-01-30 |
Time |
21:10 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2023-01-30 |
Time |
21:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-01-03 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2023-01-03 |
Time |
20:33 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-12-27 |
Time |
20:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2023-04-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-25 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-25 |
Time |
10:23 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-20 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-12 |
Time |
08:39 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-02-23 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-23 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-01 |
Time |
11:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-01-30 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2023-01-30 |
Time |
21:10 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2023-01-18 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-13 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-14 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2023-04-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-25 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-25 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2023-04-20 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-04-20 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-04-20 |
Time |
15:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-02-23 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-02-23 |
Time |
11:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-25 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-25 |
Time |
09:54 |
Sent To |
|
|
Notes |
2023-01-25 09:55:10 | SIGNATURE REVIEW: | | | | 1-- REVISED STRUCTURAL DRAWINGS WERE NOT SIGNED AND | | SEALED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER | | NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE | | OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. | | 61G15-23.004 FAC AND CHAPTER 471 F.S. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-13 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-13 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
cibaven |
Date |
2023-04-17 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
cibaven |
Date |
2023-04-17 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
cibaven |
Date |
2023-02-03 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
cibaven |
Date |
2023-02-03 |
Time |
15:56 |
Sent To |
|
|
Notes |
2023-02-03 15:56:53 | | | PLEASE CLARIFY IF THIS IS A 2 STORY OR 3 STORY | | BUILDING. IF IT IS A 2 STORY BUILDING AS PER SEC. | | 94-110(C)(2), THIS SIGN IS CONSIDERED AN ???EXTERNAL | | SIGN BAND???. AN EXTERNAL SIGN BAND SHALL NOT EXCEED 36 | | INCHES IN HEIGHT BY 60 PERCENT OF THE APPLICABLE | | STOREFRONT WIDTH. | | | | CLAUDIA D. IBAVEN | | CITY URBAN DESIGNER | ZONING AND PLANNING | | [email protected] | | 561-822-1402 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-01-25 |
|
|
Cont ID |
|
Sent By |
cibaven |
Date |
2023-01-25 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
cibaven |
Date |
2023-01-25 |
Time |
10:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
clbaven |
Date |
2022-12-30 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
cibaven |
Date |
2022-12-30 |
Time |
10:49 |
Sent To |
|
|
Notes |
2022-12-30 11:32:02 | ZONING AND PLANNING COMMENTS: | | PLEASE REVISE THE ELECTRIC SPECS DRAWING TO SHOW THAT | | NO ELECTRIC EQUIPMENT WILL BE EXPOSED ON THE FACADE TO | | MEET ARTICLE IV ??? DMP, SECTION. 94-110 ??? SIGNAGE | | REQUIREMENTS. | | | | CLAUDIA D. IBAVEN | | CITY URBAN DESIGNER | | [email protected] | | 561-822-1402 | | |
|
|