Plan Review Details - Permit 22120625
Plan Review Stops For Permit 22120625
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-04-25 Cont ID  
Sent By jgomez Date 2023-04-25 Time 10:25 Rev Time 0.00
Received By jgomez Date 2023-04-25 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-04-20 Cont ID  
Sent By jgomez Date 2023-04-20 Time 15:27 Rev Time 0.00
Received By jgomez Date 2023-04-20 Time 15:05 Sent To  
Notes
2023-04-20 15:34:06FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120625
 412 CLEMATIS ST
  
 1- SIGN WAS REVISED. ENGINEER NEEDS TO REVISE THE WIND
 LOAD CALCULATIONS TO REFLECT PROPOSED SIGN. SEC. 1609.1
 FBC-BUILDING. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- ENGINEER TO SIGN AND SEAL ALL SIGN DRAWINGS
 SUBMITTED .
 ALL PLANS/DOCUMENTS NEED TO HAVE THE SEAL/SIGNATURE OF
 THE ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.001
 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT
 PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL
 SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-02-23 Cont ID  
Sent By lbond Date 2023-02-23 Time 11:02 Rev Time 0.00
Received By lbond Date 2023-02-23 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 09:54 Rev Time 0.00
Received By jgomez Date 2023-01-25 Time 09:34 Sent To  
Notes
2023-01-25 09:54:23BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120625
 412 CLEMATIS ST
  
 1- SIGN MEANS OF ATTACHMENT WAS REVISED. GENERAL
 STATEMENT DESCRIBED IN THE REVISED SIGN MEANS OF
 ATTACHMENT IS NOT ACCEPTABLE. ENGINEER OF RECORD NEEDS
 TO SPECIFY THE ANCHOR TYPE, SIZE AND SPACING AND NUMBER
 OF FASTENERS. SEC. 1609.1 FBC-BUILDING.
  
 2- ENGINEER NEEDS TO PROVIDE COMPLETE DESIGN CRITERIA
 INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN
 WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND
 EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS
 REQUIRED BY SEC. 1603.1.4 FBC-BUILDING. SEC. 107.3.5
 CITY AMENDMENTS.
  
 3- REVISED STRUCTURAL DRAWINGS WERE NOT SIGNED AND
 SEALED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER
 NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE
 OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.004 FAC AND CHAPTER 471 F.S.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-17 Cont ID  
Sent By jgomez Date 2023-01-17 Time 17:57 Rev Time 0.00
Received By jgomez Date 2023-01-17 Time 17:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By jgomez Date 2023-01-13 Time 14:41 Rev Time 0.00
Received By jgomez Date 2023-01-13 Time 14:23 Sent To  
Notes
2023-01-13 14:41:49BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120625
 412 CLEMATIS ST
  
 1- ENGINEER TO PROVIDE COMPLETE DESIGN CRITERIA
 INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN
 WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND
 EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS
 REQUIRED BY SEC. 1603.1.4 FBC. SEC. 107.3.5 CITY
 AMENDMENTS.
  
 2- ENGINEER TO PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR INDIVIDUAL LETTERS ATTACHMENT. SEC. 1609.1
 FBC-BUILDING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-04-18 Cont ID  
Sent By fgiaquin Date 2023-04-18 Time 20:54 Rev Time 0.00
Received By fgiaquin Date 2023-04-18 Time 20:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-08 Cont ID  
Sent By fgiaquin Date 2023-02-07 Time 18:40 Rev Time 0.00
Received By fgiaquin Date 2023-02-07 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-30 Cont ID  
Sent By fgiaquin Date 2023-01-30 Time 21:10 Rev Time 0.00
Received By fgiaquin Date 2023-01-30 Time 21:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-03 Cont ID  
Sent By fgiaquin Date 2023-01-03 Time 20:33 Rev Time 0.00
Received By fgiaquin Date 2022-12-27 Time 20:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-04-25 Cont ID  
Sent By jgomez Date 2023-04-25 Time 10:26 Rev Time 0.00
Received By jgomez Date 2023-04-25 Time 10:23 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-20 Cont ID  
Sent By jgomez Date 2023-04-20 Time 15:42 Rev Time 0.00
Received By jgomez Date 2023-04-12 Time 08:39 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-23 Cont ID  
Sent By lbond Date 2023-02-23 Time 11:03 Rev Time 0.00
Received By lbond Date 2023-02-01 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-30 Cont ID  
Sent By fgiaquin Date 2023-01-30 Time 21:10 Rev Time 0.00
Received By fgiaquin Date 2023-01-18 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-13 Cont ID  
Sent By jgomez Date 2023-01-13 Time 14:42 Rev Time 0.00
Received By jgomez Date 2022-12-14 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-04-25 Cont ID  
Sent By jgomez Date 2023-04-25 Time 10:26 Rev Time 0.00
Received By jgomez Date 2023-04-25 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-04-20 Cont ID  
Sent By jgomez Date 2023-04-20 Time 15:42 Rev Time 0.00
Received By jgomez Date 2023-04-20 Time 15:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-23 Cont ID  
Sent By lbond Date 2023-02-23 Time 11:02 Rev Time 0.00
Received By lbond Date 2023-02-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By jgomez Date 2023-01-25 Time 09:54 Rev Time 0.00
Received By jgomez Date 2023-01-25 Time 09:54 Sent To  
Notes
2023-01-25 09:55:10SIGNATURE REVIEW:
  
 1-- REVISED STRUCTURAL DRAWINGS WERE NOT SIGNED AND
 SEALED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER
 NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE
 OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.004 FAC AND CHAPTER 471 F.S.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-13 Cont ID  
Sent By jgomez Date 2023-01-13 Time 14:42 Rev Time 0.00
Received By jgomez Date 2023-01-13 Time 14:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2023-04-17 Cont ID  
Sent By cibaven Date 2023-04-17 Time 12:20 Rev Time 0.00
Received By cibaven Date 2023-04-17 Time 12:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-02-03 Cont ID  
Sent By cibaven Date 2023-02-03 Time 15:57 Rev Time 0.00
Received By cibaven Date 2023-02-03 Time 15:56 Sent To  
Notes
2023-02-03 15:56:53 
 PLEASE CLARIFY IF THIS IS A 2 STORY OR 3 STORY
 BUILDING. IF IT IS A 2 STORY BUILDING AS PER SEC.
 94-110(C)(2), THIS SIGN IS CONSIDERED AN ???EXTERNAL
 SIGN BAND???. AN EXTERNAL SIGN BAND SHALL NOT EXCEED 36
 INCHES IN HEIGHT BY 60 PERCENT OF THE APPLICABLE
 STOREFRONT WIDTH.
  
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER | ZONING AND PLANNING
 [email protected]
 561-822-1402

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By cibaven Date 2023-01-25 Time 10:56 Rev Time 0.00
Received By cibaven Date 2023-01-25 Time 10:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By clbaven Date 2022-12-30 Time 11:32 Rev Time 0.00
Received By cibaven Date 2022-12-30 Time 10:49 Sent To  
Notes
2022-12-30 11:32:02ZONING AND PLANNING COMMENTS:
 PLEASE REVISE THE ELECTRIC SPECS DRAWING TO SHOW THAT
 NO ELECTRIC EQUIPMENT WILL BE EXPOSED ON THE FACADE TO
 MEET ARTICLE IV ??? DMP, SECTION. 94-110 ??? SIGNAGE
 REQUIREMENTS.
  
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER
 [email protected]
 561-822-1402
  