2023-01-12 18:10:16RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120553
 255 EVERNIA ST # 204
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 (1)-FLOORING SOUND INSULATION MATERIAL:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 NOTE:
 SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB
 WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T
 MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO
 ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE
 COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL
 CEILING.
  
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE:
 SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB
 WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T
 MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO
 ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE
 COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL
 CEILING.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 (2)PROVIDE FLOOR PLAN OR SKETCH OF APARTMENT SHOWING
 AREAS OF WORK. SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By pleduc Date 2022-12-14 Time   Rev Time 0.00
Received By pleduc Date 2022-12-14 Time 11:18 Sent To  
Notes
2022-12-14 11:24:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS AND SPECIFICATIONS OF THE
 FLOOR UNDERLAYMENT BUT NO SPECIFICATIONS NOR PRODUCT
 NAME FOR THE PROPOSED BASIC VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING PRODUCT NAME AND THE PRODUCT SPEC SHEETS
 INDICATING THE FIRE BEHAVIOR RATING.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-12 Cont ID  
Sent By jgomez Date 2023-01-12 Time 18:11 Rev Time 0.00
Received By jgomez Date 2022-12-13 Time 11:00 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-01-12 Cont ID  
Sent By jgomez Date 2023-01-12 Time 18:01 Rev Time 0.00
Received By jgomez Date 2023-01-12 Time 18:01 Sent To  
Notes
2023-01-12 18:01:28NO ARCHITECT OR ENGINEER. JG.