Plan Review Details - Permit 22111270
Plan Review Stops For Permit 22111270
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-01-18 Cont ID  
Sent By cpuell Date 2023-01-18 Time 14:44 Rev Time 0.00
Received By cpuell Date 2023-01-18 Time 14:43 Sent To  
Notes
2023-01-18 14:44:11805 & 815 N RAILROAD AVE & 490 7TH ST ASSIGNED TO THE
 DIFFERENT TENANT SPACES,
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By cpuell Date 2023-01-17 Time 12:10 Rev Time 0.00
Received By cpuell Date 2023-01-17 Time 12:10 Sent To  
Notes
2023-01-17 12:10:46ADDRESS APPROPRIATE FOR PROJECT, HOWEVER ADDRESSES NEED
 TO BE ASSIGNED FOR THE DOWNSTAIRS AND UPSTAIRS TENANTS,
 PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS ADDRESSING OPTIONS.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By swelter Date 2023-03-10 Time 12:39 Rev Time 0.00
Received By swelter Date 2023-03-10 Time 12:39 Sent To  
Notes
2023-03-10 12:39:39DEVELOPMENT PROJECT BUNDLED TO SATISFY THE PUBLIC ART
 REQUIREMENT.
 APPLICANT HAS COMPLETED AN ART ASSESSMENT APPLICATION
 OPTION 1 (ONE) ART ON SITE.
 MASTER PERMIT #22120561 WILL BE NOTED FOR RELATED
 PERMIT NUMBERS.
 CONTACT SYBILLE WELTER AT [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By rmcphers Date 2023-04-17 Time 11:51 Rev Time 0.00
Received By rmcphers Date 2023-04-17 Time 11:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-03-02 Cont ID  
Sent By rmcphers Date 2023-03-02 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2023-03-02 Time 13:32 Sent To  
Notes
2023-03-02 13:32:32PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 10:19 Sent To  
Notes
2022-12-09 10:19:32PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By rmcphers Date 2023-04-17 Time 11:51 Rev Time 0.00
Received By rmcphers Date 2023-04-17 Time 11:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-02 Cont ID  
Sent By rmcphers Date 2023-03-02 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2023-03-02 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 10:19 Sent To  
Notes
2022-12-09 10:33:01RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS AND
 ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
 2) PLEASE SHOW THE ROOF SCUTTLE DISTANCE FROM EDGE OF
 ROOF OR GUARD RAILS PER FBC 1015.7 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 3) PLEASE SHOW THE ROOF TOP EQUIPMENT DISTANCE FROM THE
 EDGE OF THE ROOF - FBC 1015.6 MECHANICAL EQUIPMENT,
 SYSTEMS AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 4) EXTERIOR DOORS ON THE SOUTH AND EAST SIDE OF THE
 BUILDING SHOULD NOT OPEN ON TO THE SIDE WALK - FBC
 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO
 THE PUBLIC RIGHT-OF-WAY.
  
 5) NOT A COMPLETE REVIEW -THE STRUCTURAL DRAWINGS ARE
 NOT IN PROJECTDOX.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-02-24 Cont ID  
Sent By jleahy Date 2023-02-24 Time 15:12 Rev Time 0.00
Received By jleahy Date 2023-02-24 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By jleahy Date 2022-12-08 Time 12:42 Rev Time 0.00
Received By jleahy Date 2022-12-08 Time 12:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-04-20 Cont ID  
Sent By lquinone Date 2023-04-20 Time 20:02 Rev Time 0.00
Received By lquinone Date 2023-04-20 Time 20:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-02-27 Cont ID  
Sent By rrossano Date 2023-02-27 Time   Rev Time 0.00
Received By rrossano Date 2023-02-27 Time   Sent To  
Notes
2023-02-27 11:39:06PLEASE ADDRESS BUILDING & ZONING COMMENTS REGARDING
 DOORS OPENING INTO ROW.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By sberglun Date 2022-12-30 Time 10:47 Rev Time 0.00
Received By sberglun Date 2022-12-30 Time 10:47 Sent To  
Notes
2022-12-30 10:48:291) ADDRESS ALL ZONING COMMENTS. ENGINEERING WILL
 RE-REVIEW ONCE ZONING COMMENTS ARE ADDRESSED.
 SUZANNE BERGLUND
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-04-14 Cont ID  
Sent By pleduc Date 2023-04-14 Time   Rev Time 0.00
Received By pleduc Date 2023-04-14 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-23 Cont ID  
Sent By pleduc Date 2023-02-23 Time   Rev Time 0.00
Received By pleduc Date 2023-02-23 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-16 Cont ID  
Sent By pleduc Date 2023-02-16 Time   Rev Time 0.00
Received By pleduc Date 2023-02-16 Time 09:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By pleduc Date 2022-12-09 Time   Rev Time 0.00
Received By pleduc Date 2022-12-08 Time 15:12 Sent To  
Notes
2022-12-08 15:30:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE EXITS INDICATED ON THE LIFE SAFETY PLANS,
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE REQUIRED
 CODE.
  
  
  
 2) THERE ARE TWO EXIT STAIRS INDICATED FROM THE 2ND
 FLOOR.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 12.2.2.3 STAIRS.
 12.2.2.3.1 GENERAL. STAIRS COMPLYING WITH 7.2.2 SHALL
 BE PERMITTED,
 UNLESS ONE OF THE FOLLOWING CRITERIA APPLIES:
 ( EXCEPTIONS NOT APPLICABLE)
  
 38.2.2.3 STAIRS.
 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED
  
 PLEASE PROVIDE STAIR DETAILS IN COMPLIANCE WITH THE
 REQUIREMENTS.
  
  
  
 3) THERE ARE INDICATIONS OF AN ELEVATOR; HOWEVER, THERE
 IS NO INDICATION OF AREA OF REFUGE FOR ACCESSIBILTIY.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH
 7 MEANS OF EGRESS.
  
 12.2.2.12 AREAS OF REFUGE. AREAS OF REFUGE COMPLYING
 WITH 7.2.12
 SHALL BE PERMITTED
  
 38.2.2.12 AREAS OF REFUGE.
 38.2.2.12.1 AREAS OF REFUGE COMPLYING WITH 7.2.12 SHALL
 BE
 PERMITTED.
  
 PLEASE PROVIDE AREA OF REFUGE DETAILS IN COMPLIANCE
 WITH THE REQUIREMENTS.
  
  
 4) SHEET A601 - THERE ARE INDICATIONS OF MAGNETIC LOCKS
 & CARD READERS ON THE DOOR SCHEDULE.
  
 THE INSTALLATION OF CARD READERS/ACCESS CONTROL SHALL
 BE INSTALLED UNDER SEPARATE PERMIT & SHOP DRAWING
 IN COMPLIANCE WITH NFPA 101, MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE PLAN SHEET.
  
  
 5) SHEET T100 - THERE ARE INDICATIONS OF SEPARATE FIRE
 SPRINKLER SHOP DRAWING SUBMITTAL.
  
 IS THERE AN EXISTING FIRE SPRINKLER SYSTEM OR IS IT A
 NEW SYSTEM?
  
 PER F.A.C.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER???S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY???NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY???NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
 THE DESIGN DOCUMENTS ARE REQUIRED TO BE SUBMITTED WITH
 THE MASTER PERMT.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
 6) SHEET T100 - THERE ARE INDICATIONS OF SEPARATE FIRE
 ALARM SHOP DRAWING SUBMITTAL.
  
 IS THERE AN EXISTING FIRE ALARM SYSTEM OR IS IT A NEW
 SYSTEM?
  
 PER F.A.C.
  
 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS,
 AND CONTROL SYSTEMS.
 (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE
 PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS,
 ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE
 SIGNALING OF EMERGENCY CONDITIONS. ITEMS TO BE
 CONSIDERED IN THE DESIGN OR ANALYSIS OF FIRE ALARM AND
 DETECTION SYSTEMS ARE, AS APPLICABLE TO THE PARTICULAR
 PROJECT: OCCUPANCY AND CLASSIFICATION, MONITORING,
 CONTROL AND COMMUNICATION, CABLING AND SUPERVISION
 REQUIREMENTS, INSTALLATION REQUIREMENTS,
 INTEROPERABILITY AND PERFORMANCE REQUIREMENTS.
 (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE
 FLORIDA BUILDING CODE, THE FLORIDA FIRE PREVENTION
 CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION. THE FLORIDA BUILDING CODE AND THE FLORIDA
 FIRE PREVENTION CODE ARE INCORPORATED BY REFERENCE IN
 RULE 61G15-18.011, F.A.C.
 (3) FOR ENGINEERING DOCUMENTS PERTAINING TO FIRE
 PROTECTION SYSTEMS EXEMPTED BY THE THRESHOLD
 REQUIREMENTS FOR MANDATORY USE OF PROFESSIONAL
 ENGINEERING SERVICES, THE ENGINEER OF RECORD SHALL
 DETERMINE THE LEVEL OF DETAIL SHOWN ON PLANS FOR A FIRE
 PROTECTION SYSTEM. ALL SUCH PLANS SHALL INCLUDE A
 DISCLAIMER STATING THE FIRE PROTECTION SYSTEM IS EXEMPT
 FROM PROFESSIONAL ENGINEERING SERVICES AND SHALL
 PROVIDE A CLEAR UNDERSTANDING OF THE MINIMUM SYSTEM
 REQUIREMENTS EXPECTED TO BE INSTALLED BY THE CONTRACTOR
 AND PERMITTED BY THE AUTHORITY HAVING JURISDICTION
 (AHJ). IN THE EVENT THE ENGINEER OF RECORD PROVIDES
 MORE INFORMATION AND DIRECTION THAN IS MINIMALLY
 REQUIRED, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE
 TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH
 APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING
 PRINCIPLES.
 (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND
 DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS
 SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION
 WHEN APPLICABLE:
 (A) THE DOCUMENTS SHALL BE CLEAR, WITH A SYMBOLS
 LEGEND, SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND
 NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. THE
 DOCUMENTS SHALL INDICATE LOCATIONS WHERE FIRE RATINGS
 ARE REQUIRED AS DETERMINED BY THE SYSTEM???S
 SURVIVABILITY REQUIREMENTS, AND SHALL IDENTIFY THE
 GENERAL OCCUPANCY OF THE PROTECTED PROPERTY AND EACH
 ROOM AND AREA UNLESS IT IS CLEAR FROM FEATURES SHOWN.
 (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND
 CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND
 SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS
 INCLUDE ELEVATOR CONTROLS, SMOKE CONTROL SYSTEMS,
 DAMPERS, DOOR RELEASE, ANY OTHER SYSTEMS OR ELEMENTS
 DIRECTLY OR INDIRECTLY CONTROLLED OR MONITORED.
 (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL
 NOTIFICATION DEVICES.
 (D) IDENTIFY THE CLASS OF CIRCUITS AS LISTED IN NFPA
 72, WHICH IS CONTAINED WITHIN AND INCORPORATED INTO THE
 FLORIDA FIRE PREVENTION CODE.
 (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND
 CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY
 SIGNALS BEING MONITORED OR ANNUNCIATED.
 (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR
 ADDRESSABLE, AND INDICATE ALL ZONING.
 (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED
 PROTECTIVE FEATURES.
 (H) IDENTIFY AND LOCATE SYSTEM DEVICES THAT ARE SUBJECT
 TO ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR
 THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY
 OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR.
 (I) THE DOCUMENTS SHALL INCLUDE A SITE PLAN OF THE
 IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE
 OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE
 THE STRUCTURE.
 (J) IN BUILDINGS WHERE SMOKE DETECTION WILL BE
 OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE
 ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND
 DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE
 OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A
 PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH
 AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE
 ENGINEERING DESIGN DOCUMENTS.
 (K) FOR FIRE DETECTION SYSTEMS UTILIZING SMOKE
 DETECTION IN SITUATIONS WHERE SMOKE STRATIFICATION IS
 ANTICIPATED, THE DESIGN SHALL PROVIDE THE NECESSARY
 CRITERIA TO MITIGATE THE DETECTION PROBLEMS.
 (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA
 SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR
 STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE
 FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING
 CODE.
 (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO
 PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED
 EVACUATION FOR ALL HIGH-RISE BUILDINGS OR
 MULTI-TENANTED PROPERTIES AS DEFINED IN SECTION 2 OF
 THE FLORIDA BUILDING CODE, BUILDING.
 (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS,
 CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND
 BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE
 PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND
 INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED
 TO OPERATE THE SYSTEMS AS INTENDED OVER TIME.
 (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO
 SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED
 WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS)
 CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL
 BE COMPLETED USING THE EQUIPMENT MANUFACTURER???S DATA
 AND APPLICABLE NFPA 72 PROCEDURES.
 (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (7) WHEN THE ENGINEER OF RECORD DETERMINES THAT SPECIAL
 REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE
 UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE
 REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (8) NO LATER THAN 90 DAYS PRIOR TO DECEMBER 31, 2026,
 THE BOARD SHALL REVIEW AND AMEND, MODIFY, OR SUNSET
 THIS RULE IF IT DETERMINES THIS RULE CREATES BARRIERS
 TO ENTRY FOR PRIVATE BUSINESS COMPETITION, IS
 DUPLICATIVE, OUTDATED, OBSOLETE, OVERLY BURDENSOME, OR
 IMPOSES EXCESSIVE COSTS. FAILURE BY THE BOARD TO ACT IN
 ACCORDANCE WITH THIS PROVISION WILL RESULT IN THE
 EXPIRATION OF THIS RULE ON DECEMBER 31, 2026.
 RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW
 IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY
 21H-32.008, AMENDED 3-26-09, 3-28-17, 7-25-19, 3-23-22.
  
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION
 PER THE F.A.C.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2023-04-14 Cont ID  
Sent By ccole Date 2023-04-14 Time 16:25 Rev Time 0.00
Received By ccole Date 2023-04-14 Time 15:57 Sent To  
Notes
2023-04-14 16:26:44GAS TO BE UNDER SEPARATE PERMIT PER ARCHITECT'S
 REQUEST.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-02-24 Cont ID  
Sent By ccole Date 2023-02-24 Time 15:12 Rev Time 0.00
Received By ccole Date 2023-02-24 Time 12:49 Sent To  
Notes
2023-02-24 15:21:002ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22111270
 2/24/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P.100 & P.500: 2ND REQUEST FOR GAS RISER AND GAS
 PIPING PLAN- SEC. 107.3.5.1.5 WPB. THE NEW PLAN SHEET
 DOES NOT SHOW THE PIPING RUN THROUGH THE BUILDING AS
 INDICATED ON SHEET P.500. PLEASE SHOW THE PIPING RUN ON
 THE PLAN AND SUBMIT A GAS RISER DRAWING. PLEASE NOTE
 GAS CAN BE UNDER A SEPARATE PERMIT IF PLANS ARE NOT
 FINALIZED AT THIS TIME. THIS CAN BE ACCOMPLISHED BY
 SENDING AN EMAIL REQUEST TO ME AT [email protected] AND I
 WILL CHANGE THE FAILED REVIEW TO N (NON REVIEW).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By ccole Date 2023-02-17 Time 15:24 Rev Time 0.00
Received By ccole Date 2023-02-17 Time 15:24 Sent To  
Notes
2023-02-17 15:25:181ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22111270
 2/17/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.500: THE NEW SUBMITTED PLAN SHOWS A NEW GAS
 METER. PROVIDE GAS PLANS PER SEC. 107.3.5.1.5 WPB.
 PLEASE INCLUDE A GAS RISER DRAWING, A GAS PIPING FLOOR
 PLAN DRAWING SHOWING PIPING RUNS THROUGH THE BUILDING
 TO APPLIANCE AND EQUIPMENT LOCATIONS, COMBUSTION AIR
 AND VENTING PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-26 Cont ID  
Sent By aoliver Date 2023-04-26 Time 08:51 Rev Time 0.00
Received By aoliver Date 2023-04-13 Time 17:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-21 Cont ID  
Sent By aoliver Date 2023-03-21 Time 09:24 Rev Time 0.00
Received By aoliver Date 2023-02-22 Time 06:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By aoliver Date 2022-12-30 Time 12:49 Rev Time 0.00
Received By aoliver Date 2022-12-07 Time 07:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By aoliver Date 2023-05-24 Time 12:58 Rev Time 0.00
Received By aoliver Date 2023-05-02 Time 18:54 Sent To  
Notes
2023-05-23 10:46:10RECEIPT MU-2023-020633 - $51,712.23 PAID
2023-05-02 18:54:37EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 10:36 Sent To  
Notes
2022-12-09 10:37:09PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-04-17 Cont ID  
Sent By medwards Date 2023-04-17 Time 16:38 Rev Time 0.00
Received By medwards Date 2023-04-17 Time 16:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 10:58 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 10:58 Sent To  
Notes
2023-02-27 10:59:003RD REVIEW FMC
 PERMIT: 22111270
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANT DENSITY OF FMC TABLE 403.3.1.1 FOR THE LOBBY.
 THE CORRECTED OCCUPANT COUNT WOULD BE 25 OCCUPANTS.
  
 ALL OF THE OTHER DUCTWORK AND OPENINGS WILL NOT BE
 REVIEWED UNTIL THE UPFIT FOR THE SPACE IS SUBMITTED FOR
 REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-21 Cont ID  
Sent By medwards Date 2023-02-21 Time 08:14 Rev Time 0.00
Received By medwards Date 2023-02-21 Time 08:14 Sent To  
Notes
2023-02-21 08:15:462ND ATTEMPT. PROVIDE A COMPLETE MECHANICAL DESIGN.
 ACCORDING TO NOTE 6 OF THE DEMOLITION NOTES THE
 EXISTING HVAC AND ALL DUCTWORK IS BEING REMOVED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By medwards Date 2022-12-13 Time 09:41 Rev Time 0.00
Received By medwards Date 2022-12-13 Time 09:41 Sent To  
Notes
2022-12-13 09:42:02PLEASE PROVIDE THE MECHANICAL DESIGN FOR THIS BUILDING.

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-04-14 Cont ID  
Sent By ccole Date 2023-04-14 Time 16:26 Rev Time 0.00
Received By ccole Date 2023-04-14 Time 15:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-02-24 Cont ID  
Sent By ccole Date 2023-02-24 Time 15:00 Rev Time 0.00
Received By ccole Date 2023-02-24 Time 12:49 Sent To  
Notes
2023-02-24 15:10:51 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22111270
 2/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW PLAN SHEET P.100 SHOWS A NEW BACKFLOW
 PREVENTER AND A GREASE WASTE LINE TO A GREASE
 INTERCEPTOR. BOTH OF THESE ITEMS REQUIRE SEPARATE
 PERMITS AND APPLICATION FOR EACH SHALL BE SUBMITTED
 PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN
 SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) P.100: NUMEROUS REFERENCES TO CIVIL PLANS ARE MADE
 IN THE PLAN NOTES FOR THE LOCATIONS OF THE WATER METER,
 GREASE INTERCEPTOR, SANITARY AND STORM DRAINAGE
 CONNECTIONS TO MAINS ETC. THE CIVIL PLANS ARE REQUIRED
 FOR ENGINEERING REVIEW HOWEVER THEY WILL NOT DELAY
 PLUMBING PLAN APPROVAL. PLEASE NOTE THE LOCATION OF THE
 INTERCEPTOR SHALL BE SHOWN ON THE SEPARATELY PERMITTED
 PLAN.
  
 2) P.100 GREASE INTERCEPTOR PLAN REVIEW SUBMITTAL
 REQUIREMENTS:
  
 A) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL, AND
 CAPACITY OF THE UNIT.
  
 B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
  
 C) PLUMBING PIPING DIAGRAM INCLUDING THE LOCATIONS AND
 SIZES OF THE INLET AND OUTLET PIPES, CLEANOUTS, VENT
 PIPES, AND OUTLET PIPE POINT OF CONNECTION TO THE MAIN
 SANITARY LINE.
  
 D) CLEANOUT ASSEMBLY DETAIL INCLUDING THE MAKE AND
 MODEL AND TYPE OF ACCESS LID TO BE INSTALLED IF LOCATED
 IN A VEHICLE TRAFFIC AREA. PLEASE NOTE THE WPB
 UTILITIES DEPT. USES THE CLEANOUT ACCESS FOR PERIODIC
 GREASE SAMPLING.
  
 E) MANUFACTURER'S SPECIFICATIONS FOR THE INTERCEPTOR
 AND ACCESS LIDS ARE REQUIRED FOR FINAL APPROVAL BUT CAN
 BE DEFERRED SUBMITTALS AND BE ONSITE FOR INSPECTION.
  
 3) 2ND REQUEST- P.500: THE NEW INSTA-HOT WATER HEATER
 WILL REQUIRE AN ASSE APPROVED MIXING VALVE TO LIMIT THE
 HOT WATER TEMPERATURE DELIVERY FROM THE MOP SINK- SEC.
 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-17 Cont ID  
Sent By ccole Date 2023-02-17 Time 14:33 Rev Time 0.00
Received By ccole Date 2023-02-17 Time 12:56 Sent To  
Notes
2023-02-17 14:34:51 
 2ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22111270
 2/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P.001, P.100, P.101, P.102, & P.700 SHOWN IN
 THE INDEX ON SHEET T.100 WERE NOT UPLIOADED FOR REVIEW.
 SHEETS P.102 & P.701 WHICH ARE REFERENCED IN THE
 RESPONSE TO COMMENTS NARRATIVE BY CES ENGINEERING WERE
 ALSO NOT UPLOADED. A THOROUGH PLUMBING REVIEW CANNOT BE
 COMPLETED WITHOUT A FULL SET OF PLUMBING PLANS- SEC.
 107.2.1 WPB. PLEASE REVIEW REMAINING COMMENTS 1, 2, & 4
 FROM THE FIRST REVIEW COPIED BELOW.
  
 2) P.500: THE NEW INSTA-HOT WATER HEATER WILL REQUIRE
 AN ASSE APPROVED MIXING VALVE TO LIMIT THE HOT WATER
 TEMPERATURE DELIVERY FROM THE MOP SINK- SEC. 607.1.1
 FBC P.
  
 1ST REVIEW COMMENTS BELOW.
  
 1) SHEETS A.101 & A.502: THE DRAWINGS SHOW AN ELEVATOR
 SUMP PIT. ASSUMING THE PIT IS FOR A HYDRAULIC ELEVATOR
 PLEASE DETAIL THE SUMP PUMP INSTALLATION INCLUDING SUMP
 PIT DIMENSIONS AND PUMP PIPING CONNECTIONS AND DRAINAGE
 DISCHARGE LOCATION- SECS. 712.3- 712.3.5 FBC P. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP AND NOTE AN
 OIL INTERCEPTOR IS REQUIRED FOR THE PUMP DRAINAGE
 SYSTEM UNLESS THE PUMP IS EQUIPPED WITH AN APPROVED
 ALARM SYSTEM- SEC. 1003.4 FBC P.
  
 2) A.102: PROVIDE SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW MOP SINK- SEC. 107.3.5.1.3 FBC
 P. PLEASE INCLUDE A LAYOUT PLAN THAT SHOWS THE LOCATION
 OF THE NEW DRAIN LINE CONNECTION TO THE EXISTING
 BUILDING DRAIN.
  
 4) A.301 PROVIDE ROOF DRAINAGE CALCULATIONS INCLUDING
 THE RAIN FALL RATE, DRAINAGE SQUARE FOOTAGE INCLUDING
 PARAPET WALLS, TOTAL GPM FLOW, AND GPM FLOW AT EACH
 PRIMARY AND SECONDARY DRAIN LOCATION- SEC. 1106.1 &
 1106.2 FBC P.
 A) PROVIDE A STORM DRAIN ISOMETRIC DRAWING SHOWING
 VERTICAL LEADER AND HORIZONTAL DRAIN SIZES, AND
 DISCHARGE LOCATIONS- SEC. 1101.2, 1106.1, 1106.2 &
 1106.3 FBC P.
 B) SHOW THE DIMENSIONS OF THE NEW SCUPPER REPLACEMENTS-
 SEC. 1106.5 & 1108.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By ccole Date 2022-12-09 Time 14:04 Rev Time 0.00
Received By ccole Date 2022-12-09 Time 11:54 Sent To  
Notes
2022-12-09 14:06:591ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22111270
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A.101 & A.502: THE DRAWINGS SHOW AN ELEVATOR
 SUMP PIT. ASSUMING THE PIT IS FOR A HYDRAULIC ELEVATOR
 PLEASE DETAIL THE SUMP PUMP INSTALLATION INCLUDING SUMP
 PIT DIMENSIONS AND PUMP PIPING CONNECTIONS AND DRAINAGE
 DISCHARGE LOCATION- SECS. 712.3- 712.3.5 FBC P. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP AND NOTE AN
 OIL INTERCEPTOR IS REQUIRED FOR THE PUMP DRAINAGE
 SYSTEM UNLESS THE PUMP IS EQUIPPED WITH AN APPROVED
 ALARM SYSTEM- SEC. 1003.4 FBC P.
  
 2) A.102: PROVIDE SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW MOP SINK- SEC. 107.3.5.1.3 FBC
 P. PLEASE INCLUDE A LAYOUT PLAN THAT SHOWS THE LOCATION
 OF THE NEW DRAIN LINE CONNECTION TO THE EXISTING
 BUILDING DRAIN.
  
 3) A.102: SHOW THE SOURCE OF THE HOT WATER FOR THE MOP
 SINK- SEC. 607.1 FBC P. IF A NEW WATER HEATER IS
 PROPOSED PLEASE SHOW THE LOCATION AND PROVIDE THE
 FOLLOWING INFORMATION:
 A) EQUIPMENT SCHEDULE.
 B) PROVIDE A SCHEMATIC DRAWING THAT SHOWS PIPING
 CONNECTIONS INCLUDING THE COLD WATER FEED, CHECK VALVE,
 HOT WATER SUPPLY, THERMAL EXPANSION CONTROL, HOT WATER
 RECIRCULATION PUMP (IF INSTALLED), AND MASTER
 THERMOSTATIC MIXING VALVE- SECS. 607.1.1, 607.2.2,
 607.3 FBC P.
 C) PROVIDE RELIEF VALVE PIPING DETAILS INCLUDING TYPE
 AND SIZE OF RELIEF PIPE AND DISCHARGE LOCATION; PAN AND
 PAN DRAIN DETAILS, PAN DRAIN RUN AND TERMINATION
 LOCATION- SECS. 504.4- 504.7.2 FBC P.
  
 4) A.301 PROVIDE ROOF DRAINAGE CALCULATIONS INCLUDING
 THE RAIN FALL RATE, DRAINAGE SQUARE FOOTAGE INCLUDING
 PARAPET WALLS, TOTAL GPM FLOW, AND GPM FLOW AT EACH
 PRIMARY AND SECONDARY DRAIN LOCATION- SEC. 1106.1 &
 1106.2 FBC P.
 A) PROVIDE A STORM DRAIN ISOMETRIC DRAWING SHOWING
 VERTICAL LEADER AND HORIZONTAL DRAIN SIZES, AND
 DISCHARGE LOCATIONS- SEC. 1101.2, 1106.1, 1106.2 &
 1106.3 FBC P.
 B) SHOW THE DIMENSIONS OF THE NEW SCUPPER REPLACEMENTS-
 SEC. 1106.5 & 1108.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2023-03-02 Cont ID  
Sent By rmcphers Date 2023-03-02 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2023-03-02 Time 13:32 Sent To  
Notes
2023-03-02 13:33:08ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 10:37 Sent To  
Notes
2022-12-09 10:38:27SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By rmcphers Date 2023-04-17 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2023-04-17 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-02 Cont ID  
Sent By rmcphers Date 2023-03-02 Time 13:41 Rev Time 0.00
Received By rmcphers Date 2023-03-02 Time 13:41 Sent To  
Notes
2023-02-27 10:59:55MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-02-17 15:06:45PLUMBING (P) PLAN SIGS APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-09 Cont ID  
Sent By rmcphers Date 2022-12-09 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2022-12-09 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-04-25 Cont ID  
Sent By ckimmerl Date 2023-04-25 Time 11:46 Rev Time 0.00
Received By ckimmerl Date 2023-04-25 Time 11:46 Sent To  
Notes
2023-04-25 11:46:33PROVISO: ANY NEW ROOFTOP MECHANICAL EQUIPMENT SHALL BE
 SCREENED FROM VIEW WITH THE ROOF PARAPET OR A SCREEN
 EQUAL IN HEIGHT TO THE PROPOSED MECHANICAL EQUIPMENT.

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By ckimmerl Date 2023-03-20 Time 14:32 Rev Time 0.00
Received By ckimmerl Date 2023-03-20 Time 14:31 Sent To  
Notes
2023-03-20 14:31:58PROVISO: ANY NEW ROOFTOP MECHANICAL EQUIPMENT SHALL BE
 SCREENED FROM VIEW WITH THE ROOF PARAPET OR A SCREEN
 EQUAL IN HEIGHT TO THE PROPOSED MECHANICAL EQUIPMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By ckimmerl Date 2022-12-21 Time 10:31 Rev Time 0.00
Received By ckimmerl Date 2022-12-21 Time 10:26 Sent To  
Notes
2022-12-21 10:29:041. PROPOSED DOORS AND STOREFRONT OPEN UP INTO THE
 PUBLIC ROW & SIDEWALK, THIS IS NOT PERMITTED.
  
 PROVISO: ANY NEW ROOFTOP MECHANICAL EQUIPMENT SHALL BE
 SCREENED FROM VIEW WITH A SCREEN EQUAL IN HEIGHT TO THE
 PROPOSED MECHANICAL EQUIPMENT.