Plan Review Details - Permit 22111193
Plan Review Stops For Permit 22111193
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By cthroop Date 2023-03-15 Time 08:32 Rev Time 0.00
Received By cthroop Date 2023-03-15 Time 07:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By cthroop Date 2023-01-19 Time 14:16 Rev Time 0.00
Received By cthroop Date 2023-01-19 Time 06:45 Sent To  
Notes
2023-01-19 14:23:141ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PERMIT TYPE CHANGED TO RES-ADD
  
 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 2. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 3.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7.
 R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  
 4.ROOF VENTILATION
 R806.1VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 5.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS.
  
 6.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
  
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-08 Cont ID  
Sent By rperdomo Date 2023-03-08 Time 08:58 Rev Time 0.00
Received By rperdomo Date 2023-03-08 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-28 Cont ID  
Sent By rperdomo Date 2022-12-28 Time 13:06 Rev Time 0.00
Received By rperdomo Date 2022-12-28 Time 11:21 Sent To  
Notes
2022-12-28 13:06:27FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITIION
 ELECTRICAL REVIEW STATUS: PASSED, NOTES BELOW
  
 1. GENERATOR SYSTEM REQUIRES A SEPARATE PERMIT
 APPLICATION.
  
 END OF NOTES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By rwbrown Date 2023-03-01 Time 13:59 Rev Time 0.00
Received By rwbrown Date 2023-03-01 Time 13:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-12-28 Cont ID  
Sent By rwbrown Date 2022-12-28 Time 12:55 Rev Time 0.00
Received By rwbrown Date 2022-12-28 Time 12:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By fmittner Date 2023-03-09 Time 09:21 Rev Time 0.00
Received By fmittner Date 2023-03-09 Time 09:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 16:17 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 11:44 Rev Time 0.00
Received By medwards Date 2023-04-06 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 12:17 Rev Time 0.00
Received By medwards Date 2023-03-22 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-15 Cont ID  
Sent By cthroop Date 2023-03-15 Time 08:32 Rev Time 0.00
Received By cthroop Date 2023-02-28 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-19 Cont ID  
Sent By cthroop Date 2023-01-19 Time 14:23 Rev Time 0.00
Received By cthroop Date 2022-12-22 Time 12:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-03-26 Cont ID  
Sent By lmarchan Date 2023-03-26 Time 08:07 Rev Time 0.00
Received By lmarchan Date 2023-03-22 Time 16:46 Sent To  
Notes
2023-03-26 08:07:37NO IMPACT FEES DUE. LEM
2023-03-22 16:46:463/22/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By cthroop Date 2023-01-19 Time 13:54 Rev Time 0.00
Received By cthroop Date 2023-01-19 Time 13:17 Sent To  
Notes
2023-01-19 13:55:24IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 11:44 Rev Time 0.00
Received By medwards Date 2023-04-14 Time 11:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 12:11 Rev Time 0.00
Received By medwards Date 2023-03-24 Time 12:11 Sent To  
Notes
2023-03-24 12:15:31THE ENERGY CALCULATIONS FOR THE MINI SPLIT FOR THE
 GARAGE WOULD NEED TO ALSO INCLUDE THE GARAGE DOOR.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 14:19 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 14:19 Sent To  
Notes
2023-03-02 14:20:011ST REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THE GARAGE. FEC
 R101.5.1.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 07:09 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 07:09 Sent To  
Notes
2022-12-30 07:09:541ST REVIEW FMC
 PERMIT: 22111193
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT THE KITCHEN HOOD WILL MEET THE
 MAKE-UP AIR REQUIREMENTS IN FRC M1503.4
  
 2) REMOVE THE DUCTWORK FROM THE NEW AHU-2 THAT IS
 SUPPLYING THE GARAGE AS YOU CANNOT SUPPLY THE GARAGE
 FROM THE HOUSE MECHANICAL SYSTEM. FRC M1601.6
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THE NEW AHU-2. FRC M1401.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By rwbrown Date 2023-03-01 Time 13:59 Rev Time 0.00
Received By rwbrown Date 2023-03-01 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-12-28 Cont ID  
Sent By rwbrown Date 2022-12-28 Time 12:56 Rev Time 0.00
Received By rwbrown Date 2022-12-28 Time 12:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By cthroop Date 2023-03-15 Time 08:31 Rev Time 0.00
Received By cthroop Date 2023-03-15 Time 07:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By cthroop Date 2023-01-19 Time 13:57 Rev Time 0.00
Received By cthroop Date 2023-01-19 Time 06:45 Sent To  
Notes
2023-01-19 14:01:26PLAN REVIEW ROOFING
  
 1ST ROOFING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
  
 NOTICE: A ROOFING SUB-PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS??? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
  
 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA
 FOR THE PROPOSED ROOFING UNDERLAYMENT TO BE INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOA???S DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 3. DESIGNER SHALL SELECT TYPE OF ATTACHMENT FOR
 CONCRETE TILES.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 4. IF ATTACHMENT SELECTED IS OTHER THAN MECHANICL,
 PROVIDE THE FLORIDA PRODUCT APPROVAL OR MIAM-DADE NOA
 OF THE ADHESIVE TO BE USED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By cthroop Date 2023-03-15 Time 08:31 Rev Time 0.00
Received By cthroop Date 2023-03-15 Time 07:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By cthroop Date 2023-01-19 Time 13:55 Rev Time 0.00
Received By cthroop Date 2023-01-19 Time 06:45 Sent To  
Notes
2023-01-19 13:57:071ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PLAN PAGES A-101, A-501 & A-502
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
2022-12-30 07:10:35MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By fmittner Date 2023-03-09 Time 09:21 Rev Time 0.00
Received By fmittner Date 2023-03-09 Time 09:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 16:17 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 16:17 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved