2022-12-08 07:12:31 | 2ND GAS REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FRC G2439.5 - PER YOUR NOTE, A 10" ROUND DOES |
| NOT PROVIDE 100 SQ. IN. OF MAKEUP AIR TO SATISFY THIS |
| CODE SECTION. IF YOU ARE USING "ANOTHER APPROVED |
| METHOD", YOU WILL NEED TO SHOW YOUR CALCULATIONS AND |
| HOW YOU CAME UP WITH THE AMOUNT OF COMBUSTION AIR |
| NEEDED. I AM UNABLE TO VERIFY THE CALCULATIONS BECAUSE |
| THE PLANS DO NOT SHOW A FLOOR PLAN WHICH WOULD INCLUDE |
| ROOM DIMENSIONS. YOU NEED TO DETAIL THE ROOM SIZE AND |
| CALCULATIONS USED. |
| |
| 2. 2020 FRC G2439.5 - YOU WILL NEED TO SHOW A DETAIL |
| SHOWING HOW YOU ARE ACHEIVING THE REQUIRED MAKEUP AIR. |
| SHOW A SIMPLE FLOOR PLAN THAT SHOWS WHERE THE AIR IS |
| COMING FROM, AND WHAT TYPE OF DUCTS OR GRILLS ARE BEING |
| USED TO TRANSFER THE AIR INTO THOSE ROOMS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |