Plan Review Details - Permit 22110889
Plan Review Stops For Permit 22110889
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2023-05-23 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-04-08 Cont ID  
Sent By cthroop Date 2023-04-08 Time 08:40 Rev Time 0.00
Received By cthroop Date 2023-04-08 Time 08:40 Sent To  
Notes
2023-04-08 08:44:37APPROVAL OF THE BUILDING REVIEW IS PENDING APPROVAL OF
 THE SIGNATURE REVIEW. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-01 Cont ID  
Sent By rmcdouga Date 2023-03-01 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2023-03-01 Time 13:55 Sent To  
Notes
2023-03-01 13:57:56****CORRECTIONS****
  
 ROBERT MCDOUGAL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6714
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NOT RESOLVED. FBC R 301 IT IS NOT CLEAR WHICH
 GENERATOR IS PROPOSED. UNTIL THAT INFORMATION IS
 PROVIDED, THE GENERATOR PAD ENGINEERING CANNOT BE
 REVIEWED, FBC 107.
  
 2. NOT RESOLVED. FS 471, PLEASE UPLOAD DIGITALLY SIGNED
 ENGINEERING FOR THE GENERATOR PAD. THE DOCUMENT HAS THE
 IMAGE OF A DIGITAL SIGNATURE BUT THE DIGITAL SIGNATURE
 CERTIFICATE WAS REMOVED FROM THE DOCUMENT BEFORE
 UPLOADING.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-14 Cont ID  
Sent By shill Date 2023-01-14 Time 13:47 Rev Time 0.00
Received By shill Date 2023-01-14 Time 13:47 Sent To  
Notes
2023-01-14 13:48:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301 IT IS NOT CLEAR WHICH GENERATOR IS
 PROPOSED. UNTIL THAT INFORMATION IS PROVIDED, THE
 GENERATOR PAD ENGINEERING CANNOT BE REVIEWED, FBC 107.
  
 2. FS 471, PLEASE UPLOAD DIGITALLY SIGNED ENGINEERING
 FOR THE GENERATOR PAD. THE DOCUMENT HAS THE IMAGE OF A
 DIGITAL SIGNATURE BUT THE DIGITAL SIGNATURE CERTIFICATE
 WAS REMOVED FROM THE DOCUMENT BEFORE UPLOADING. YOU MAY
 EMAIL THE ENGINEERING TO [email protected],
 [email protected] FOR PRELIMINARY REVIEW.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-29 Cont ID  
Sent By shill Date 2022-12-29 Time 15:52 Rev Time 0.00
Received By shill Date 2022-12-29 Time 15:52 Sent To  
Notes
2022-12-29 16:06:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301 PROVIDE A STRUCTURAL DETAIL FOR THE
 GENERATOR PAD, INCLUDING WIND DESIGN CRITERIA AND
 ANCHORING TO RESIST SPECIFIED WIND LOADS.
  
 2. FBC R 303.5.1, OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT. REVISE PLAN TO SHOW
 DISTANCE FROM GENERATOR EXHAUST TO CLOSEST OPENING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-10 Cont ID  
Sent By jleahy Date 2023-02-10 Time 18:33 Rev Time 0.00
Received By jleahy Date 2023-02-10 Time 17:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-16 Cont ID  
Sent By fgiaquin Date 2023-01-16 Time 23:26 Rev Time 0.00
Received By fgiaquin Date 2023-01-16 Time 22:56 Sent To  
Notes
2023-01-16 22:59:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CUT SHEETS OF TRANSFER SWITCH AND GENERATOR
 FBC 107.2.1 NEC 110.3B
  
 2. WHAT IS WHAT IS GENERATOR OUTPUT OCP SIZE? FBC
 107.2.1
  
 3. **** PREVIOUS COMMENT SATISFIED. (PLAN IS NOW
 SIGNED)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-10 Cont ID  
Sent By fgiaquin Date 2022-12-10 Time 20:42 Rev Time 0.00
Received By fgiaquin Date 2022-12-10 Time 20:07 Sent To  
Notes
2022-12-10 20:42:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CUT SHEETS OF TRANSFER SWITCH AND GENERATOR
 FBC 107.2.1 NEC 110.3B
  
 2. WHAT IS WHAT IS GENERATOR OUTPUT OCP SIZE? FBC
 107.2.1
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2023-05-04 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-17 Cont ID  
Sent By asangele Date 2023-04-17 Time 15:02 Rev Time 0.00
Received By asangele Date 2023-04-17 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-01 Cont ID  
Sent By rmcdouga Date 2023-03-01 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2023-02-07 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-16 Cont ID  
Sent By fgiaquin Date 2023-01-16 Time 23:26 Rev Time 0.00
Received By fgiaquin Date 2023-01-09 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-29 Cont ID  
Sent By shill Date 2022-12-29 Time 16:06 Rev Time 0.00
Received By shill Date 2022-11-22 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2023-05-23 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-04-08 Cont ID  
Sent By cthroop Date 2023-04-08 Time 08:40 Rev Time 0.00
Received By cthroop Date 2023-04-08 Time 08:40 Sent To  
Notes
2023-04-08 08:43:564TH SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PLAN PAGE CONCRETE GEN PAD REQUIRES VALID
 DIGITAL SIGNATURE OF ENGINEER.
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-01 Cont ID  
Sent By rmcdouga Date 2023-03-01 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2023-03-01 Time 13:52 Sent To  
Notes
2023-03-01 13:54:39THE ENGINEER'S DIGITAL SIGNATURE ON THE GENERATOR PAD
 ENGINEERING COULD NOT BE VERIFIED. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC
 61G1 OR FS 471 & FAC 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-14 Cont ID  
Sent By shill Date 2023-01-14 Time 13:48 Rev Time 0.00
Received By shill Date 2023-01-14 Time 13:48 Sent To  
Notes
2023-01-14 13:49:31SEE BULDING REVIEW
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 09:22 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 09:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By asangele Date 2023-04-17 Time 15:01 Rev Time 0.00
Received By asangele Date 2023-04-17 Time 15:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-13 Cont ID  
Sent By asangele Date 2023-01-13 Time 14:38 Rev Time 0.00
Received By asangele Date 2023-01-13 Time 14:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-07 Cont ID  
Sent By asangele Date 2022-12-07 Time 14:22 Rev Time 0.00
Received By asangele Date 2022-12-07 Time 14:22 Sent To  
Notes
***NONE***