Plan Review Stops For Permit 22110836 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-12-09 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-12-09 |
Time |
10:02 |
Sent To |
|
|
Notes |
2022-12-09 10:02:26 | WORK IS FOR THE NORTH AND SOUTH BUILDING ONLY |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2022-11-18 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-11-18 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-11-18 |
Time |
09:08 |
Sent To |
|
|
Notes |
2022-11-18 09:08:43 | IS THIS FOR THE NORTH OF SOUTH BUILDING? PLEASE RESPOND | | TO [email protected] OR CALL 561-805-6659 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-16 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-16 |
Time |
13:41 |
Sent To |
|
|
Notes |
2022-12-16 13:44:22 | 12/16/22 RECEIVED EMAIL FROM PERMIT LADI: | | | | JULIO, | | THANK YOU FOR BEING SO PATIENT WITH US. FASTENING | | OPTION #5 ON PAGE 63 IS THE METHOD OF INSTALLATION. | | | | ON FRI, DEC 16, 2022 AT 10:28 AM JULIO C. GOMEZ | | WROTE: | | GOOD MORNING, | | | | PLEASE SEE COMMENTS FOR LATEST SUBMITTAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-16 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-16 |
Time |
10:17 |
Sent To |
|
|
Notes |
2022-12-16 10:24:10 | RE-ROOF RESIDENTIAL, FOURTH BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110836 | | 705 PALM BEACH LAKES BLVD | | | | ORIGINAL COMMENT: | | 2-PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE | | NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. | | SEC. R905.1.1.1 FBC-RESIDENTIAL. | | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 | | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE | | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. | | | | RESPONSE: | | PEEL & SEAL UNDERLAYMENT NOA 16-0728.22 SUBMITTED | | EXPIRED ON 08/31/21. NEED TO PROVIDE CURRENT PRODUCT | | APPROVAL. | | | | PREVIOUS COMMENT STILL NO ADDRESSED: | | 3- FLAT ROOF NOA 18-0919.12 SUBMITTED: | | A)NEED TO SPECIFY/MARK WHICH APPROVED ASSEMBLY IS GOING | | TO BE INSTALLED. | | | | EMAIL RESPONSE FROM PERMIT LADI STATES "I HAVE CHECKED | | AND THE MODIFIED BIT NOA IS INCLUDED. WE ARE USING | | PAGES 61-63, INSTALLATION OPTION 7." | | | | THIS RESPONSE DOESN'T ANSWER WHICH APPROVED ASSEMBLY IS | | GOING TO BE INSTALLED. THERE ARE SEVERAL ASSEMBLIES ON | | PAGES 61-63 AND THERE IS NOT "INSTALLATION OPTION 7". | | | | NEED TO SPECIFY OR MARK WHICH ANCHOR SHEET FASTENING | | OPTION IS GOING TO BE INSTALLED. NOTE: IF THE SPECIFIED | | FASTENING OPTION DON'T MEET THE DESIGN PRESSURES FOR | | ALL ROOF ZONES, THEN ENGINEER'S SIGNED AND SEALED RAS | | 117 CALCULATIONS ARE REQUIRED (THIS IS REQUIRED BY | | GENERAL LIMITATION #7 STATED ON EACH FASTENING OPTION). | | | | NOTE: ONLY FASTENING OPTION #5 ON PAGE 61 OF 67 AND | | FASTENING OPTION #5 ON PAGE 63 OF 67 MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES IN THIS PROJECT. IF THIS | | ASSEMBLY IS SELECTED, THEN RAS 117 CALCULATIONS ARE NOT | | REQUIRED. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-15 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-15 |
Time |
15:32 |
Sent To |
|
|
Notes |
2022-12-15 15:37:31 | RE-ROOF RESIDENTIAL, THIRD BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110836 | | 705 PALM BEACH LAKES BLVD | | | | ORIGINAL COMMENT: | | 2-PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE | | NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. | | SEC. R905.1.1.1 FBC-RESIDENTIAL. | | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 | | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE | | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. | | | | RESPONSE: | | REPEAT COMMENT. THREE TIMES. NOT ADDRESSED. | | | | | | 3- FLAT ROOF NOA 18-0919.12 SUBMITTED: | | A)NEED TO SPECIFY/MARK WHICH APPROVED ASSEMBLY IS GOING | | TO BE INSTALLED. | | | | EMAIL RESPONSE FROM PERMIT LADI STATES "I HAVE CHECKED | | AND THE MODIFIED BIT NOA IS INCLUDED. WE ARE USING | | PAGES 61-63, INSTALLATION OPTION 7." | | | | THIS RESPONSE DOESN'T ANSWER WHICH APPROVED ASSEMBLY IS | | GOING TO BE INSTALLED. THERE ARE SEVERAL ASSEMBLIES ON | | PAGES 61-63 AND THERE IS NOT "INSTALLATION OPTION 7". | | | | NEED TO SPECIFY OR MARK WHICH ANCHOR SHEET FASTENING | | OPTION IS GOING TO BE INSTALLED. NOTE: IF THE SPECIFIED | | FASTENING OPTION DON'T MEET THE DESIGN PRESSURES FOR | | ALL ROOF ZONES, THEN ENGINEER'S SIGNED AND SEALED RAS | | 117 CALCULATIONS ARE REQUIRED (THIS IS REQUIRED BY | | GENERAL LIMITATION #7 STATED ON EACH FASTENING OPTION). | | | | NOTE: ONLY FASTENING OPTION #5 ON PAGE 61 OF 67 AND | | FASTENING OPTION #5 ON PAGE 63 OF 67 MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES IN THIS PROJECT. IF THIS | | ASSEMBLY IS SELECTED, THEN RAS 117 CALCULATIONS ARE NOT | | REQUIRED. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-15 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-15 |
Time |
09:16 |
Sent To |
|
|
Notes |
2022-12-15 09:35:19 | 12/15/22 REVISED COMMENTS. | | | | RE-ROOF RESIDENTIAL, BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110836 | | 705 PALM BEACH LAKES BLVD | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C. | | 61G20-3.001 FOR: | | | | A)OK. | | | | ORIGINAL COMMENT: | | B)ROOFING UNDERLAYMENT. NOTE: COORDINATE WITH ITEM #2 | | BELOW. | | | | RESPONSE: | | NOA 18-0919.12 SUBMITTED IS FOR MODIFIED BITUMEN ROOF | | SYSTEMS (FLAT ROOF ASSEMBLIES) NOT A SHINGLES | | UNDERLAYMENT. NEED TO SUBMIT PRODUCT APPROVAL FOR | | UNDERLAYMENT DESIGNED FOR SHINGLES UNDERLAYMENT. NOTE: | | COORDINATE WITH ITEM #2 BELOW. | | | | 12/15/22 REVISED COMMENTS. | | PERMIT APPLICATION CALLS ONLY FOR SHINGLES RE-ROOF. IT | | DIDN'T MENTIONED THE FLAT ROOF. AFTER LOOKING AT THE | | ROOF REPORT SUBMITTED ON 12/9/22 IT WAS FOUND THAT REAR | | STRUCTURE HAS A FLAT ROOF. | | FLAT ROOF NOA 18-0919.12: NEED TO SPECIFY WHICH | | APPROVED ASSEMBLY FROM PAGE 63 OF 67 IS GOING TO BE | | INSTALLED AND NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. SEE | | LAST PAGE OF NOA FOR GENERAL LIMITATION #7 | | REQUIREMENTS. | | | | | | ORIGINAL COMMENT: | | 2- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH | | THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. | | SEC. R905.1.1.1 FBC-RESIDENTIAL. | | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 | | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE | | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-12-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-14 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-14 |
Time |
16:39 |
Sent To |
|
|
Notes |
2022-12-14 16:52:40 | RE-ROOF RESIDENTIAL, SECOND BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110836 | | 705 PALM BEACH LAKES BLVD | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C. | | 61G20-3.001 FOR: | | | | A)OK. | | | | ORIGINAL COMMENT: | | B)ROOFING UNDERLAYMENT. NOTE: COORDINATE WITH ITEM #2 | | BELOW. | | | | RESPONSE: | | NOA 18-0919.12 SUBMITTED IS FOR MODIFIED BITUMEN ROOF | | SYSTEMS (FLAT ROOF ASSEMBLIES) NOT A SHINGLES | | UNDERLAYMENT. NEED TO SUBMIT PRODUCT APPROVAL FOR | | UNDERLAYMENT DESIGNED FOR SHINGLES UNDERLAYMENT. NOTE: | | COORDINATE WITH ITEM #2 BELOW. | | | | ORIGINAL COMMENT: | | 2- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH | | THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. | | SEC. R905.1.1.1 FBC-RESIDENTIAL. | | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 | | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE | | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | ORIGINAL COMMENT: | | 3- NEED TO SPECIFY THE MEAN ROOF HEIGHT, ROOF PITCH, | | ROOF AREAS (PITCHED AND FLAT AREAS) AS REQUIRED BY THE | | CITY POLICY FOR ALL ROOFING PERMITS. SEC. 107.2.1 CITY | | AMENDMENTS. | | NOTE: AN SKETCH SHOWING THE ROOF AREAS WILL HELP | | EXPEDITE YOUR PERMIT. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-09 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-09 |
Time |
13:19 |
Sent To |
|
|
Notes |
2022-12-09 14:03:14 | RE-ROOF RESIDENTIAL, BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22110836 | | 705 PALM BEACH LAKES BLVD | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C. | | 61G20-3.001 FOR: | | | | A)ROOF SHINGLES. | | | | B)ROOFING UNDERLAYMENT. NOTE: COORDINATE WITH ITEM #2 | | BELOW. | | | | 2- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH | | THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. | | SEC. R905.1.1.1 FBC-RESIDENTIAL. | | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 | | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE | | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. | | | | 3- NEED TO SPECIFY THE MEAN ROOF HEIGHT, ROOF PITCH, | | ROOF AREAS (PITCHED AND FLAT AREAS) AS REQUIRED BY THE | | CITY POLICY FOR ALL ROOFING PERMITS. SEC. 107.2.1 CITY | | AMENDMENTS. | | NOTE: AN SKETCH SHOWING THE ROOF AREAS WILL HELP | | EXPEDITE YOUR PERMIT. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2022-12-09 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2022-12-09 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-16 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-16 |
Time |
13:41 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-12-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-16 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-16 |
Time |
08:39 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-12-15 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-12-15 |
Time |
15:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-15 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-15 |
Time |
09:16 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-14 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-14 |
Time |
16:39 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-09 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-09 |
Time |
14:03 |
Sent To |
I |
|
Notes |
|
|