Plan Review Details - Permit 22110693
Plan Review Stops For Permit 22110693 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
rcmphers |
Date |
2022-12-01 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-12-01 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-12-09 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-12-09 |
Time |
11:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-11-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-11-21 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-12-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-12-09 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-11-18 |
Time |
12:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-11-30 |
Time |
12:57 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-11-30 |
Time |
12:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2022-11-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-11-23 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-11-23 |
Time |
14:51 |
Sent To |
|
|
Notes |
2022-11-23 16:07:33 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22110693 | | 11/23/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET A4.22: SEC. 604.2 FBC ACC REQUIRES THE | | CENTERLINE OF THE WATER CLOSET TO BE 16 INCHES MINIMUM | | TO 18-INCHES MAXIMUM FROM THE SIDE WALL. THERE IS NO | | EXCEPTION FOR PRIVATE BATHROOMS. BASED ON THE PLAN | | NOTE, THE CENTERLINE OF THE WATER CLOSET WAS RELOCATED | | TO 19-INCHES DUE TO THE BEAM OBSTRUCTION BELOW, HOWEVER | | THE ROOM WIDTH DIMENSION OF 5???6??? INDICATES THERE IS | | SUFFICIENT ROOM TO EITHER MOVE THE WALL INWARD OR FURR | | IT OUT 1-INCH SO THAT THE CENTERLINE OF THE WATER | | CLOSET WOULD BE IN COMPLIANCE. IT DOES NOT APPEAR THE | | EXCEPTIONS UNDER SEC. 203.15 FBC ACC STRUCTURAL | | IMPRACTICALLY ARE APPLICABLE TO THIS SITUATION. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-12-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-12-01 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-12-01 |
Time |
15:54 |
Sent To |
|
|
Notes |
2022-11-30 12:58:07 | MECHANICAL DIGITAL SIGNATURE APPROVED ME |
|
|
|