Plan Review Details - Permit 22110652
Plan Review Stops For Permit 22110652
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-12-13 Cont ID  
Sent By cpuell Date 2022-12-13 Time 16:30 Rev Time 0.00
Received By cpuell Date 2022-12-13 Time 16:30 Sent To  
Notes
2022-12-13 16:31:00ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By jwitmer Date 2023-01-10 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2023-01-10 Time 14:01 Sent To  
Notes
2023-01-10 15:46:40COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By jwitmer Date 2023-01-13 Time 09:20 Rev Time 0.00
Received By jwitmer Date 2023-01-10 Time 13:46 Sent To  
Notes
2023-01-11 11:28:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110652
 ADD: 777 S FLAGLER DR. # 150
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 11/23
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) UNDER THE HEADING PROJECT INFORMATION: NOTE 7
 STATES THE OCCUPANCY TYPES THAT WILL OCCUR UNDER THIS
 PERMIT ARE A-2 & F-2. PLEASE PROVIDE WHAT TYPE OF
 FACTORY, INDUSTRIAL USES ARE GOING TO OCCUR THESE USES
 INCLUDE BUT NOT LIMITED TO FABRICATION OR MANUFACTURING
 OF NONCOMBUSTIBLE MATERIALS THAT DURING FINISHING,
 PACKING OR PROCESSING DO NOT INVOLVE A SIGNIFICANT FIRE
 HAZARD. 2020 FBC-BUILDING CODE SECTION 306.3. NOTE F-1
 OCCUPANCIES CAN BE KITCHENS, FOOD PROCESSING NOT
 ASSOCIATED WITH RESTAURANTS. SECTION 306.2.
  
 1B) ACCESSIBILITY NOTE EATING & DRINKING
 ESTABLISHMENTS, KNEE SPACE AT TABLES STATES AT LEAST27
 INCHES HIGH, 30 INCHES WIDE, AND 19 INCHES WIDE. WHERE
 DOES THE 19 INCHES WIDE COME FROM. IN THE 2020
 FBC-ACCESSIBILITY CODE SECTION902.2 (DINING) REFERS YOU
 TO 306 FOR KNEE & TOE SPACES. PLEASE REVIEW SECTIONS
 306.3.2 & 306.3.3 MAXIMUM & MINIMUM REQUIRED DEPTH.
  
 2) SHEET A-061:
 2A) FIRST FLOOR LIFE SAFETY SHEET HAS 2 DIFFERENT WAYS
 OF FIGURING OCCUPANT LOADS (1ST) BASED ON AREA WITH
 OCCUPANT LOAD OF 444, THE (2ND) BASED ON THE ACTUAL
 SEATING OF 287. PLEASE NOTE OCCUPANT LOADS FOR MEANS OF
 EGRESS ARE FIGURED ON THE WORST-CASE SCENARIO. WHEN
 FIGURING THE WORST-CASE SCENARIO ASSEMBLY OCCUPANCIES
 WITH OCCUPANT LOADS OVER 300 THE STRUCTURES HAVE A RISK
 CATEGORY OF III. TABLE 1604.5/ FIGURE 1609.3.2, 180
 VULT WIND SPEED (NEW CONSTRUCTION). CODE DATA STATES
 CLASSIFICATION OF WORK RENOVATION OF EXISTING
 COMMERCIAL SPACE, THE PLAN DOES NOT INDICATE WHAT TYPE
 OF OCCUPANCY WAS IN THE SPACE TO BE REMODELED. NO
 REFERENCE TO THE 2020 EXISTING BUILDING CODE, AND
 CLASSIFICATION OF WORK CHAPTER 5. 2020 EXISTING
 BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
 ALTERATIONS COMPLIANCE METHOD. MISSING THE REFERENCE TO
 THE 2020 FLORIDA EXISTING BUILDING CODE 7TH EDITION YOU
 ALSO HAVEN???T INDICATED TO WHAT CLASSIFICATION THE
 PLANS WERE DESIGNED TO SEE 2020 FBC-EXISTING BUILDING
 CODE CHAPTER 5 501.1. THE DESIGNER OF RECORD HAS NOT
 INDICATED TO WHICH METHOD THE PLANS WERE DEVELOPED,
 COMPLYING WITH THE PROVISIONS OF CHAPTER 6 THROUGH 13
 OR WITH ONE OF THE ALTERNATE PROVISIONS IN SECTION
 301.1.
  
 2B) LIFE SAFETY PLAN, OCCUPANT LOADS TAKEN FOR 36-INCH
 AND 48-INCH SWING DOORS ARE TAKING THE FULL DOOR WIDTH,
 NOT THE CLEAR WIDTH OF THE DOOR. 2020 FBC-B 1010.1.1.
 SIZE OF DOORS. CLEAR WIDTH. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN AT 90
 DEGREES.
  
  
 3) THIS ALTERATION IS IN A 20-STORY BUILDING MAKING THE
 BUILDING BY DEFINITION A THRESHOLD BUILDING. THRESHOLD
 BUILDING / FL S. S. 553.71(7) ???THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3G) PLEASE CALL THE CITY OF WEST PALM BEACH???S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 FLOORS, WALLS AND CEILINGS.
  
 4) SHEET 131-S-0.01:
 4A) DESIGN LOADS, THIS REVIEW THE RISK CATEGORY: II /
 170 VULT MPH. SEE COMMENT (2A) WITH OCCUPANT LOADS FOR
 ASSEMBLY OCCUPANCY OVER 300, RISK CATEGORY III. TABLE
 1604.5/ FIGURE 1609.3.2, 180 VULT WIND SPEED (NEW
 CONSTRUCTION). CODE DATA STATES CLASSIFICATION OF WORK
 RENOVATION OF EXISTING COMMERCIAL SPACE, THE PLAN DOES
 NOT INDICATE WHAT TYPE OF OCCUPANCY WAS IN THE SPACE TO
 BE REMODELED. NO REFERENCE TO THE 2020 EXISTING
 BUILDING CODE, AND CLASSIFICATION OF WORK CHAPTER 5.
 THE 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4B) DESIGN LOADS, MEAN ROOF HEIGHT IS GIVEN AS 40 FEET.
 THIS IS A 20 STORY HIGHRISE. COMPONENTS & CLADDING.
 NEGATIVE PRESSURES ARE TO BE TAKEN FROM THE ROOF;
 POSITIVE PRESSURES TAKEN FROM CLADDING LOCATION ABOVE
 GRADE. THE BUILDING COMPONENTS AND CLADDING CHART WILL
 NEED TO BE UPDATED ONCE ALL DESIGN ISSUES ARE CLEARED
 UP.
  
 4C) PLEASE PROVIDE A DIGITALLY SIGNED AND SEALED SOILS
 REPORT, ARDAMAN & ASSOCIATES (FILE NO. 21-1637) DATED
 MY 10TH, 2021. 61G15-23.004 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS (DIGITAL
 SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
  
 5) SHEET 134-S-1.03 UTILITY PROVISIONS. NEW FPL VAULT.
 THE PLANS DO NOT PROVIDE THE HOURLY RATING FOR THE FPL
 VAULT WALLS AND STRUCTURAL CEILING NOR (2) SETS OF
 DOUBLE DOORS. 2017 NEC 450.42. THE UTILITY PLAN DOES
 NOT PROVIDE HOW THE FEEDERS ARE GOING INTO THE VAULT
 NOR ONCE THROUGH THE TRANSFORMER HOW THEY ARE GOING TO
 THE FUTURE ELECTRICAL ROOM, WILL THE FLOOR SLABS BE
 CUT, PLEASE PROVIDE ADDITIONAL DETAILS. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 6A) SHEETS 022 A-072 & 027 A-112.00 BOTH SHOW NEW
 FOOTINGS AND COLUMNS TO A NEW MECHANICAL MEZZANINE /
 EQUIPMENT PLATFORM. SHEET 133 S-1.02 SHOWS A
 SECOND-FLOOR AREA. PLEASE PROVIDE AN ANALYSIS HOW THIS
 AREA IS TO BE USED, AS A MEZZANINE, EQUIPMENT PLATFORM
 OR A TRUE 2ND FLOOR. MEZZANINE, 2020 FBC-BUILDING
 505.2.1.EXCEPTION 1 IS FOR TYPE I OR II CONSTRUCTION,
 SPECIAL INDUSTRIAL, 2/3RDS OF THE ROOM IT IS LOCATED,
 505.3.1 EQUIPMENT PLATFORMS AREA PLATFORMS ALSO HAS A
 2/3RDS OF THE ROOM IT IS LOCATED, THE EQUIPMENT
 PLATFORM IS LARGER THAN 2/3RDS OF THE ROOM IT IS
 LOCATED AND IF A 2ND FLOOR THEN THE FLOOR, ALL WALLS
 AND DUCTS WOULD NEED TO BE FIRE RATED AND FIRE DAMPERS.
  
 6B) SHEET 133 S-1.02 SHOWS DASHED WALL LINES (HIDDEN
 WALLS) WHERE ARE THESE WALLS LOCATED, THEY ARE NOT
 LOCATED BENEATH IN THE KITCHEN? 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 6C) THE PLANS ARE SILENT AS TO HOW ONE GAINS ACCESS TO
 THIS MECHANICAL EQUIPMENT AREA. SECTION 505.3 EQUIPMENT
 PLATFORMS AND WALKWAYS, STAIRWAYS, ALTERNATING TREAD
 DEVICES AND LADDERS PROVIDING ACCESS TO AN EQUIPMENT
 PLATFORM SHALL NOT SERVE AS A PART OF THE MEANS OF
 EGRESS FROM THE BUILDING.
  
 7) SHEET 056 A-503.33 ENLARGE DETAIL 6 SHOWS A SERIES
 OF STOREFRONT SLIDING GLASS DOORS SIMILAR TO FLEETWOOD
 3070-HI SERIES. WITH THE RECESSED TRACK IN THE FLOOR
 HOW IS A WHEELCHAIR TO NAVIGATE OVER THIS RECESS?
 PLEASE REVIEW THE 2020 FBC-ACCESSIBILITY CODE SECTION
 302.3 OPENINGS.
  
 8) SHEET 132 S-1.01 CANOPY COLUMNS BY OTHERS, ARE THE
 CANOPIES PART OF THIS PERMIT, IF SO WILL THE SAME WIND
 DESIGN BE USED FOR THE CANOPIES? SHEET 056 A-503.00
 SHOWS AWNING RAFTERS & NOTE FOR A RETRACTABLE/ FIXED
 ROOF SURFACE.
 8A) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 8B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 8C) NO MENTION OF MATERIAL FOR FRAMEWORK OR RETRACTABLE
 ROOFING MATERIAL. FABRIC USED IN THE CONSTRUCTION OF
 AWNINGS SHALL MEET THE REQUIREMENTS OF 3104.3.4 2020
 FBC-BUILDING.
  
 8D) RETRACTABLE AWNINGS DESIGN SHALL MEET THE
 REQUIREMENT OF 3105.4.2.2.
  
 9A) SHEET 132 S-1.01 GLASS RAILING BY OTHERS. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 9B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10A) SHEET 057 A-505.00 SHOWS A NEW EXTERIOR LOUVER
 SCREEN WALL, WIND GIRT FRAME AND KICKERS. SHEET 135
 S-1.04 STATES DELEGATED SCREEN WALL SUBMIT SIGNED AND
 SEALED SHOP DRAWINGS. DELEGATED ENGINEERING.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 10B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 11) SHEET 057 A-505.00 SHOWS A NEW EXTERIOR ROOF TOP
 CURB & FAN. SHEET 076 M-401 SHOW DETAIL FOR ROOF TOP
 FAN AND INDICATES THE USE OF NOA # 21-1129.02 PLEASE
 PROVIDE AND HIGHLIGHT THE APPROPRIATE ANCHORAGE FOR
 WIND ZONE. FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR
 A/C STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE
 ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF
 STAND TO THE EQUIPMENT ABOVE.
  
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 12) SHEET 007 G-012.00 DETAILS 2 & 3 BOTH SHOW THE GRAB
 BAR MEASURED TO THE CENTER OF THE GRAB BAR. FOR ALL
 ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR
 VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK
 AS WELL AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT
 ABOVE. SAME FOR ALL RESTROOM ELEVATION SHEETS.
  
 13) SHEET 048 A-400.00 DETAILS 1 & 2 DO MOT PROVIDE THE
 LOCATION OF THE WATERCLOSET CENTERLINE FROM SIDE WALL,
 GANGED RESTROOM DETAIL # 3 SHOWS THE ACCESSIBLE
 WATERCLOSET AT 19 INCHES CENTERLINE FROM THE SIDEWALL.
 PLEASE REVIEW THE 2020 FBC-ACCESSIBILITY CODE SECTION
 604.2 16-18 INCHES. AMBULATORY STALLS ARE 17-19 INCHES.
 STANDS FOR ELEVATION SHEETS.
  
 14) 050 A-402.00 TOILET PAPER DISPENSERS. 604.7. THE
 TOILET PAPER DISPENSER SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND THE GRAB BARS.
 THIS COMMENT STANDS FOR ALL ELEVATION SHEETS.
  
 15) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By fgiaquin Date 2023-01-05 Time 20:57 Rev Time 0.00
Received By fgiaquin Date 2023-01-04 Time 20:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By parking Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By pleduc Date 2022-12-14 Time   Rev Time 0.00
Received By pleduc Date 2022-12-13 Time 10:40 Sent To  
Notes
2022-12-13 10:48:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE EXIT SIGNS ON THE LIFE SAFETY SHEET; A
 061.00, HOWEVER, THERE ARE NO EXIT SIGNS ON ANY
 ELECTIRCAL SHEET.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND
 THIS CHAPTER.
  
 12.2.10 MARKING OF MEANS OF EGRESS.
 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE
 WITH SECTION 7.10.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE EXIT SIGNAGE
 ON THE ELECTICAL PLAN SHEETS.
  
  
 1A) THERE IS AN INDICATION OF A DOUBLE SWING DOOR;
 D112, WITH AN EXIT SIGN OVER THE MIDDLE OF IT.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS.
  
 PLEASE ENSURE THAT THE EXIT SIGN IS MOVED TO ONE SIDE
 IN THE DIRECTION OF TRAVEL, NOT INSTALLED OVER THE
 MIDDLE, PER THE REQUIREMENT.
  
  
 2) SHEET D 103.00 THRU D 107.00 - THERE ARE INDICATIONS
 OF DEMOLITION.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE DEMO SHEETS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
 THE KITCHEN HOOD & SUPPRESSION SYSTEMS SHALL BE
 INSTALLED UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 THE EXIT SIGN OVER THE DOUBLE SWING DOOR; D112, IS
 REQUIRED TO BE OVER ONE SIDE OF THE DOOR, NOT IN THE
 MIDDLE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-24 Cont ID  
Sent By rwbrown Date 2023-01-24 Time 10:47 Rev Time 0.00
Received By rwbrown Date 2023-01-24 Time 10:47 Sent To  
Notes
2023-01-24 11:14:491ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE FG-000 -- 2017 WPB AMENDS 107.2.1 - THE
 REFERENCED TABLE 402.4.1(1) IS FOR .3" W.C. AND YOU'VE
 DETAILS IT IS FOR 14" W.C. PLEASE REFERENCE A MORE
 ACCURATE SIZE TABLE.
  
 2. PAGE FG-000 -- 2020 FGC 304.6 - COMBUSTION AIR
 CALCULATIONS SHOWN ON THE PLANS STATE THE COMBUSTION
 AIR IN CFM'S. THE CODE ASKS FOR COMBUSTION AIR TO BE
 PROVIDED BY SQUARE INCHES OF OPENINGS PROVIDED. PLEASE
 RECONFIGURE THE COMBUSTION AIR TO STATE IT IN CODE
 COMPLIANT MEASUREMENTS.
  
 3. PAGE FG-300 -- 2017 WPB AMENDS 107.3.5.1.5 -- THE
 "LOOP" DOES NOT HAVE A PIPE SIZE FOR THE LINE THAT
 SUPPLIES THE FIXTURES (THE TOP OF THE LOOP). COULD YOU
 PLEASE ADD THAT PIPE SIZE. THE BOTTOM SIDE OF THE LOOP
 IS 1/2". WHAT IS THE TOP?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-27 Cont ID  
Sent By aoliver Date 2023-01-27 Time 14:36 Rev Time 0.00
Received By aoliver Date 2022-12-12 Time 08:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By jwitmer Date 2023-01-10 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2023-01-10 Time 13:55 Sent To  
Notes
2023-01-10 15:47:45IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM???S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-28 Cont ID  
Sent By medwards Date 2022-12-28 Time 10:46 Rev Time 0.00
Received By medwards Date 2022-12-28 Time 10:46 Sent To  
Notes
2022-12-28 10:46:391ST REVIEW FMC
 PERMIT: 22110652
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADD A NOTE TO THE KITCHEN HOOD DRAWINGS STATING THAT
 THE KITCHEN HOODS AND GREASE DUCT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS
 THEY WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 THE REFRIGERATION FOR THIS PROJECT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS
 THEY WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 4) SHEET M-201A: THE NOA???S MENTIONED IN NOTES 13 AND
 14 MUST BE ON THE JOBSITE FOR THE INSPECTOR AT TIME OF
 INSPECTION.
  
 5) SHEET M-301: PLEASE UPDATE THE VENTILATION
 CALCULATIONS TO REFLECT THE CURRENT CODE AND SECTION OF
 THE CODE. 2020 FMC TABLE 403.3.1.1
  
 6) PLEASE PROVIDE A DETAIL FOR THE HP-2 RETURN AIR. THE
 HP-2 IS LOCATED IN THE KITCHEN BUT IT???S SERVING THE
 BAR AREA. PLEASE SHOW THAT NO RETURN AIR IS COMING FROM
 THE KITCHEN FOR THIS UNIT. FMC 601.5 NUMBER 7
  
 7) SHEET M-201A: PROVIDE A DETAIL DRAWING SHOWING THE
 INTAKE DUCT LOCATION, ARE THEY TO BE LOCATED ON THE
 ROOF? IF LOCATED IN THE COVERED WALKWAY THIS AREA IS
 CLOSED ON 3 SIDES AND WOULD NOT BE ABLE TO BE USED FOR
 OUTSIDE AIR INTAKE. FBC 107.3.5
  
 8) PLEASE SHOW HOW ALL OF THE MECHANICAL SYSTEMS,
 INCLUDING THE AHUS, WILL MEET THE SMOKE DETECTOR
 REQUIREMENTS FOR THE COMMON SUPPLY SYSTEMS. FMC 606.2.2
  
 9) SHOW HOW THE AHUS WILL BE SUPPLIED WITH THE REQUIRED
 OUTDOOR AIR. FMC 403.3.1.1
  
 10) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH
 ZONE. FMC 403.3.1.1.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By rwbrown Date 2022-12-21 Time 06:32 Rev Time 0.00
Received By rwbrown Date 2022-12-20 Time 14:36 Sent To  
Notes
2022-12-20 16:04:171ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. P-501 - DETAIL #13 - 2020 FPC 607.1.1 - HOT WATER
 DELIVERY MUST ALSO BE LIMITED BY A THERMOSTATIC MIXING
 DEVICE. A THERMOSTATIC MIXING DEVICE MUST BE ON THE HOT
 WATER LINE. THIS IS IN ADDITION TO THE REQUIREMENTS FOR
 TEMPERED WATER REQUIRED BY 607.1.2.
  
 2. P-302 -- 2020 FEC C404.5.1 - MAXIMUM DISTANCE TO A
 PUBLIC LAVATORY FROM THE NEAREST SOURCE OF HEATED WATER
 SHALL BE LIMITED TO 2' ON 1/2" PIPE AND .5' ON 3/4"
 PIPE. PLEASE ADJUST THE DOMESTIC WATER ISOMETRIC TO
 INDICATE COMPLIANCE. (THE HOT WATER LOOP MUST LOOP DOWN
 TO WITHIN 2' OF THE PUBLIC LAVS).
  
 3. P-503 -- 2017 WPB AMENDS 107.2.1 - MISSING FROM THE
 PLUMBING KITCHEN EQUIPMENT SCHEDULE ARE SEVERAL OF THE
 REFERENCES ON THE SANITARY FLOOR PLAN. EXAMPLES FROM
 THE BAR AREA P-317.1;P-319.1;P-316.1;P-310.1. PLEASE
 CLARIFY.
 A) PAGE P-200 (BOH SEMI-OPEN AREA) - P220.1 IS LISTED
 AS A "DECK BROILER" AND IS POINTING TO A THE HAND SINK
  
  
 4. 2020 FPC 1003.3.1 - BAR AREA HAND SINK DISCHARGES TO
 THE GREASE WASTE AND SHOULD NOT. ONLY FIXTURES DESIGNED
 TO RECEIVE FATS, OILS, AND GREASE WASTES SHALL
 DISCHARGE TO THE INTERCEPTOR. ALL OTHERS SHALL BE
 DIRECTED TO THE SANITARY, INCLUDING CONDENSATES FROM
 COOLING EQUIPMENT. ONLY A/C (ROOM CONDITIONERS)
 CONDENSATES NEED DIRECTED TO STORM. FEEL FREE TO CALL
 TO CLARIFY THIS COMMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By jwitmer Date 2023-01-13 Time 09:28 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-13 09:27:57ARCHITECTURAL SHEETS WOULD NOT OPEN FOR VERIFICATION,
 MEP SHEETS OK.
2022-12-28 10:50:03MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By cibaven Date 2023-01-27 Time 14:23 Rev Time 0.00
Received By cibaven Date 2023-01-27 Time 14:22 Sent To  
Notes
2023-01-27 14:22:57ZONING AND PLANNING
 DATE: JANUARY 27, 2023
 CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT
 561-822-1402 OR VIA [email protected].
  
 PLEASE PROVIDE THE NEW SQUARE FOOTAGE ADDED TO THE
 RETAIL SPACE. IN ADDITION, PLEASE PROVIDE A WRITTEN
 RESPONSE ON HOW THIS PROJECT IS RELATED TO THE PB 833J
 MINOR AMENDMENT PHILLIPS POINT AND IF ANY OF THE
 CHANGES PROPOSED IN THE MINOR AMENDMENT WILL ALTER THIS
 APPLICATION.
  
  
 --END OF COMMENTS--