Plan Review Details - Permit 22110579
Plan Review Stops For Permit 22110579
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 11:44 Sent To  
Notes
2023-06-21 12:29:51TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-01-04 Cont ID  
Sent By jwitmer Date 2023-01-04 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2023-01-04 Time 07:05 Sent To  
Notes
2023-01-04 07:35:00TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 11:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-04 Cont ID  
Sent By jwitmer Date 2023-01-04 Time 07:34 Rev Time 0.00
Received By jwitmer Date 2023-01-04 Time 07:05 Sent To  
Notes
2023-01-04 07:34:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110579
 ADD: 618 6TH ST. / BUILT IN 1968
 CONT: CLOSE PERMITS FAST
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 04TH/2023
 ACTION: DENIED
  
 1) ONLY ONE SHEET OF PLANS WAS SUBMITTED WITH ALL
 TRADES ON THE ONE SHEET. THERE IS NO DEMOLITION PLAN,
 THERE IS NO SCOPE OF WORK FOR EACH TRADE. THE FLOOR
 PLAN STATES THIS IS A LEVEL 3 ALTERATION BUT DOES NOT
 PROVIDE WHERE THE WORK AREA EXCEEDS 50% OF THE
 BUILDING. THE PLANS ARE SILENT AS TO IF THE WORK MEETS
 THE REQUIREMENTS FOR A LIMITED STRUCTURAL ALTERATION
 SEE 907.4.4 OF THE EXIST. BUILD. CODE OR SUBSTANTIAL
 STRUCTURAL ALTERATION UNDER THE HEADING OF 907.4.2
 SUBSTANTIAL STRUCTURAL ALTERATIONS.
  
 2) LEVEL 3 ALTERATIONS SECTION 907.4.1 EVALUATION AND
 ANALYSIS, PLEASE PROVIDE THE ENGINEERING EVALUATION AND
 ANALYSIS.
  
 3) PLEASE NOTE ALL TRADES ARE SHOWN ON ONE SHEET. EACH
 OF THE PERMIT APPLIED FOR BUILD. ELECTRICAL & PLUMBING
 HAVE 3 DIFFERENT QUALIFIERS, EACH TRADE HAS TO HAVE
 THEIR OWN SEPARATE SHEET WHERE THE QUALIFIER FOR THAT
 TRADE PRINTS THEIR NAME, SIGNS THEIR NAME AND LICENSE
 NUMBER FOR THE TRADE THEY ARE LICENSED. PLEASE DO NOT
 SHOW ALL TRADES ON ONE SHEET. AS A CONTRACTOR YOU DO
 NOT HAVE THE SAME RIGHTS AS A DESIGN PROFESSIONAL,
 ARCHITECT OR ENGINEER.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS AND OR
 SCHEDULES WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS AND OR SCHEDULES DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 4) THIS PROJECT WITH AN EVALUATION OF $80.000.00
 DOLLARS REQUIRES DESIGN PROFESSIONAL INVOLVEMENT.
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-06 Cont ID  
Sent By mpeterso Date 2023-07-06 Time 14:21 Rev Time 0.00
Received By mpeterso Date 2023-07-06 Time 14:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-20 Cont ID  
Sent By mpeterso Date 2022-12-20 Time 12:36 Rev Time 0.00
Received By mpeterso Date 2022-12-20 Time 11:04 Sent To  
Notes
2022-12-20 12:37:24ELECTRIC REVIEW FAILED
  
 1)PLEASE DETAIL (2) SMALL APPLIANCE KITCHEN CIRCUITS AS
 REQUIRED PER NEC 210.52
 2)IT APPEARS SOME RECEPTACLE SPACING IS DOES NOT COMPLY
 WITH NEC 210.52. PLEASE CORRECT AS APPLICABLE, IF
 RECEPTACLES ARE EXISTING PLEASE DETAIL THEM AND NOTE
 THAT THEY ARE EXISTING. FBC 107.2
 3) PLAN STATES NEW LIGHTING OUTLETS, HOWEVER NONE ARE
 SHOWN. PLEASE DETAIL AS APPLICABLE. FBC 107.2
 4) PLEASE INDICATE ALL WIRING REPLACED, MODIFIED OR
 REPAIRED. FBC 107.2
 5) PLEASE PROVIDE A DETAILED BUILDING RISER DIAGRAM
 INCLUDING ALL CONDUCTOR, EQUIPMENT, CONDUIT SIZES,
 OVERCURRENT PROTECTION SIZES AND SPECIFICATIONS AND
 GROUNDING ELECTRODE SYSTEM. NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By pleduc Date 2023-06-15 Time   Rev Time 0.00
Received By pleduc Date 2023-06-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-06 Cont ID  
Sent By pleduc Date 2022-12-06 Time   Rev Time 0.00
Received By pleduc Date 2022-12-06 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-06 Cont ID  
Sent By mpeterso Date 2023-07-06 Time 14:24 Rev Time 0.00
Received By mpeterso Date 2023-06-14 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-05 Cont ID  
Sent By lmarchan Date 2023-01-05 Time 08:35 Rev Time 0.00
Received By lmarchan Date 2022-12-05 Time 08:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By jwitmer Date 2023-01-04 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2023-01-04 Time 07:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 10:24 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 10:24 Sent To  
Notes
2022-12-30 10:25:35SCOPE OF WORK STATES NO MECHANICAL WORK FOR THIS
 PROJECT. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-26 Cont ID  
Sent By ccole Date 2023-06-26 Time 09:58 Rev Time 0.00
Received By ccole Date 2023-06-26 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 17:19 Rev Time 0.00
Received By ccole Date 2023-01-04 Time 17:09 Sent To  
Notes
2023-01-04 17:23:231ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110579
 1/4/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PLUMBING
 CONTRACTOR OR QUALIFIER FOR THE PROJECT SHALL BE ON THE
 PLUMBING DRAWING- SEC. 107.2.1 WPB. ALTERNATIVELY, A
 FL. LICENSED ENGINEER MAY PREPARE DIGITALLY SIGNED AND
 SEALED DRAWINGS IN ACCORDANCE WITH FL. STATUTE 471.025
 AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 12:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-04 Cont ID  
Sent By jwitmer Date 2023-01-04 Time 07:36 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-04 07:36:27PLEASE NOTE ALL TRADES ARE SHOWN ON ONE SHEET. EACH OF
 THE PERMIT APPLIED FOR BUILD. ELECTRICAL & PLUMBING
 HAVE 3 DIFFERENT QUALIFIERS, EACH TRADE HAS TO HAVE
 THEIR OWN SEPARATE SHEET WHERE THE QUALIFIER FOR THAT
 TRADE PRINTS THEIR NAME, SIGNS THEIR NAME AND LICENSE
 NUMBER FOR THE TRADE THEY ARE LICENSED. PLEASE DO NOT
 SHOW ALL TRADES ON ONE SHEET. AS A CONTRACTOR YOU DO
 NOT HAVE THE SAME RIGHTS AS A DESIGN PROFESSIONAL,
 ARCHITECT OR ENGINEER.
  
 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS AND OR
 SCHEDULES WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS AND OR SCHEDULES DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 THIS PROJECT WITH AN EVALUATION OF $80.000.00 DOLLARS
 REQUIRES DESIGN PROFESSIONAL INVOLVEMENT. 481.229
 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C) ANY OTHER
 TYPE OF BUILDING COSTING LESS THAN $25,000.00, EXCEPT A
 SCHOOL, AUDITORIUM, OR OTHER BUILDING INTENDED FOR
 PUBLIC USE, PROVIDED THAT THE SERVICES OF A REGISTERED
 ARCHITECT SHALL NOT BE REQUIRED FOR MINOR SCHOOL
 PROJECTS PURSUANT TO 1013.45.
  