Plan Review Details - Permit 22110556
Plan Review Stops For Permit 22110556
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 10:43 Rev Time 0.00
Received By pvalenti Date 2023-05-19 Time 10:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-28 Cont ID  
Sent By rmcdouga Date 2023-04-28 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2023-04-28 Time 16:41 Sent To  
Notes
2023-04-28 16:49:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE
 ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC
 61G1 OR FS 471 & FAC 61G15
  
 2) THE SURVEY DOES NOT SPECIFY OR SHOW THAT THE
 GENERATOR EXHAUST IS AT LEAST 10 FEET FROM OPENINGS
 INTO A BUILDING. SUBMIT A SURVEY SHOWING THE LOCATION
 OF THE GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By rmcdouga Date 2023-01-10 Time 10:02 Rev Time 0.00
Received By rmcdouga Date 2023-01-10 Time 09:48 Sent To  
Notes
2023-01-10 10:02:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE 48
 KW GENERATOR THAT WILL BE INSTALLED. FBC 107.2.1
  
 2) THE GENERATOR PAD ENGINEERING NEEDS TO BE FOR A WIND
 SPEED OF 170 MPH VULT. FBC AMENDMENTS 120
  
 3) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE
 ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC
 61G1 OR FS 471 & FAC 61G15
  
 4) SUBMIT A SURVEY SHOWING THE LOCATION OF THE
 GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO BE AT
 LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-05 Cont ID  
Sent By jleahy Date 2022-12-05 Time 15:40 Rev Time 0.00
Received By jleahy Date 2022-12-05 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-02 Cont ID  
Sent By vbroglia Date 2023-06-02 Time 15:27 Rev Time 0.00
Received By vbroglia Date 2023-05-19 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-01 Cont ID  
Sent By vbroglia Date 2023-05-01 Time 14:32 Rev Time 0.00
Received By vbroglia Date 2023-04-25 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-10 Cont ID  
Sent By rmcdouga Date 2023-01-10 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2022-11-29 Time 07:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-19 Cont ID  
Sent By pvalenti Date 2023-05-19 Time 10:43 Rev Time 0.00
Received By pvalenti Date 2023-05-19 Time 10:43 Sent To  
Notes
2023-05-19 10:46:32PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY SUBMITTAL OF PAPER
 ORIGINAL HAND SIGNED/SEALED ENGINEERING DOCUMENT BY
 FRANK BENNARDO PE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-28 Cont ID  
Sent By rmcdouga Date 2023-04-28 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2023-04-28 Time 16:41 Sent To  
Notes
2023-04-28 16:45:31THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS NOT
 DIGITALLY SIGNED BY THE ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC
 61G1 OR FS 471 & FAC 61G15
 ELECTRICAL PAGE SIGNATURE IS APPROVED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By rmcdouga Date 2023-01-10 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2023-01-10 Time 10:03 Sent To  
Notes
2023-01-10 10:04:19ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
2022-12-05 15:41:18ELECTRICAL PAGE SIGNATURE IS APPROVED

Review Stop Z ZONING
Rev No 4 Status P Date 2023-06-08 Cont ID  
Sent By fmittner Date 2023-06-08 Time 11:20 Rev Time 0.00
Received By fmittner Date 2023-06-08 Time 11:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-06-02 Cont ID  
Sent By vbroglia Date 2023-06-02 Time 15:26 Rev Time 0.00
Received By vbroglia Date 2023-06-02 Time 15:26 Sent To  
Notes
2023-06-02 15:27:12PREVIOUS COMMENTS NOT ADDRESSED.
  
 SHOW SETBACKS FROM THE PROPERTY LINES TP GENERATOR PAD

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-01 Cont ID  
Sent By vbroglia Date 2023-05-01 Time 14:29 Rev Time 0.00
Received By vbroglia Date 2023-05-01 Time 14:29 Sent To  
Notes
2023-05-01 14:30:295/1/23 FAILED FOR THE FOLLOWING REASON(S):
  
 1. PLEASE SHOW THE SETBACKS FROM THE PROPERTY LINE TO
 THE PROPOSED GENERATOR.
  
 PLEASE NOTE:
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK.
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By vbrogila Date 2022-12-19 Time 13:34 Rev Time 0.00
Received By vbroglia Date 2022-12-19 Time 13:34 Sent To  
Notes
2022-12-19 13:35:3712/19/22 FAILED:
  
 PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE
 PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM
 BOUNDARY LINES
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  