Plan Review Stops For Permit 22110556 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-19 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-19 |
Time |
10:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-04-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-04-28 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-04-28 |
Time |
16:41 |
Sent To |
|
|
Notes |
2023-04-28 16:49:18 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE | | ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC | | 61G1 OR FS 471 & FAC 61G15 | | | | 2) THE SURVEY DOES NOT SPECIFY OR SHOW THAT THE | | GENERATOR EXHAUST IS AT LEAST 10 FEET FROM OPENINGS | | INTO A BUILDING. SUBMIT A SURVEY SHOWING THE LOCATION | | OF THE GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO | | BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-01-10 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-01-10 |
Time |
09:48 |
Sent To |
|
|
Notes |
2023-01-10 10:02:53 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE 48 | | KW GENERATOR THAT WILL BE INSTALLED. FBC 107.2.1 | | | | 2) THE GENERATOR PAD ENGINEERING NEEDS TO BE FOR A WIND | | SPEED OF 170 MPH VULT. FBC AMENDMENTS 120 | | | | 3) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE | | ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC | | 61G1 OR FS 471 & FAC 61G15 | | | | 4) SUBMIT A SURVEY SHOWING THE LOCATION OF THE | | GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO BE AT | | LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-12-05 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-12-05 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-06-02 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-06-02 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-05-19 |
Time |
10:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-05-01 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-05-01 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-04-25 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-01-10 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2022-11-29 |
Time |
07:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-19 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-19 |
Time |
10:43 |
Sent To |
|
|
Notes |
2023-05-19 10:46:32 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | SIGNATURE REVIEW APPROVED BY SUBMITTAL OF PAPER | | ORIGINAL HAND SIGNED/SEALED ENGINEERING DOCUMENT BY | | FRANK BENNARDO PE. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-04-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-04-28 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-04-28 |
Time |
16:41 |
Sent To |
|
|
Notes |
2023-04-28 16:45:31 | THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS NOT | | DIGITALLY SIGNED BY THE ENGINEER. ELECTRONICALLY | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC | | 61G1 OR FS 471 & FAC 61G15 | | ELECTRICAL PAGE SIGNATURE IS APPROVED |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2023-01-10 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2023-01-10 |
Time |
10:03 |
Sent To |
|
|
Notes |
2023-01-10 10:04:19 | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | 2022-12-05 15:41:18 | ELECTRICAL PAGE SIGNATURE IS APPROVED |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2023-06-08 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2023-06-08 |
Time |
11:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2023-06-02 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-06-02 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-06-02 |
Time |
15:26 |
Sent To |
|
|
Notes |
2023-06-02 15:27:12 | PREVIOUS COMMENTS NOT ADDRESSED. | | | | SHOW SETBACKS FROM THE PROPERTY LINES TP GENERATOR PAD |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-05-01 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-05-01 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-05-01 |
Time |
14:29 |
Sent To |
|
|
Notes |
2023-05-01 14:30:29 | 5/1/23 FAILED FOR THE FOLLOWING REASON(S): | | | | 1. PLEASE SHOW THE SETBACKS FROM THE PROPERTY LINE TO | | THE PROPOSED GENERATOR. | | | | PLEASE NOTE: | | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS | | MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED | | SIDE SETBACK. | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | PLANNER | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-12-19 |
|
|
Cont ID |
|
Sent By |
vbrogila |
Date |
2022-12-19 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-12-19 |
Time |
13:34 |
Sent To |
|
|
Notes |
2022-12-19 13:35:37 | 12/19/22 FAILED: | | | | PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE | | PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM | | BOUNDARY LINES | | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS | | MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED | | SIDE SETBACK | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | ASSOCIATE PLANNER | | [email protected] | | |
|
|