Plan Review Details - Permit 22110291
Plan Review Stops For Permit 22110291
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By jbrooks Date 2023-02-28 Time 10:57 Rev Time 0.00
Received By jbrooks Date 2023-02-28 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-09 Cont ID  
Sent By jbrooks Date 2023-02-09 Time 12:11 Rev Time 0.00
Received By jbrooks Date 2023-02-09 Time 07:57 Sent To  
Notes
2023-02-09 12:12:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL33818-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL33818-R2 SYSTEM NO. LOK-W-8 MAXIMUM DESIGN
 PRESSURE -96.75 DO NOT MEET THE MINIMUM ZONE 3 DESIGN
 PRESSURE REQUIREMENT OF -128.4 FOR EXPOSURE CATEGORY C
 AREAS HAVING GABLE/HIP ROOF WITH ROOF SLOPE BETWEEN
 2:12 & 12:12 WITH A MEAN ROOF HEIGHT 20 FEET OR LESS
 WIND SPEED 170 MPH, ENCLOSED BUILDING AS PER APPENDIX C
 PAGE #3. PROVIDE SIGNED AND SEALED ENGINEERING FOR USE
 OR SELECT A SYSTEM THAT MEETS THE ABOVE CRITERIA.
 PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
 3. FBC B 107.2.1 PLEASE NOTE: PRODUCT APPROVAL
 FL5259-R37 (NON-HVHZ) TABLES 4A & 4B, ALLOWABLE DESIGN
 PRESSURE UNDERLAYMENT CHARTS ARE REQUIRED FOR USE IN
 ROOF TILE APPLICATIONS ONLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By jbrooks Date 2022-12-12 Time 08:29 Rev Time 0.00
Received By jbrooks Date 2022-12-12 Time 07:42 Sent To  
Notes
2022-12-12 08:30:15JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL3318-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: SELECT PRODUCT TO BE USED FROM
 EVALUATION REPORT PAGES 1-6; SELECT FASTENING DETAILS
 TO BE USED FROM APPNDIX A PAGES 2-5; SELECT APPROVED
 SYSTEM NO. TO BE USED FROM APPNDIX B PAGES 1-8; SELECT
 EXPOSURE, BUILDING TYPE, ZONE, MEAN ROOF HEIGHT & RISK
 CATEGORY FROM APPENDIX C PAGES 1-3. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL
 FL5259-R34HAS BEEN REVISED TO FL5259-R36. PLEASE
 PROVIDE A COMPLETE SET; IT COVERS MULTIPLE PRODUCT
 TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL5259-R36 (NON-HVHZ).
 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH TO INDICATE THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING AND INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS
 MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-02-22 Cont ID  
Sent By amhamilt Date 2023-02-22 Time 15:16 Rev Time 0.00
Received By amhamilt Date 2023-02-22 Time 15:16 Sent To  
Notes
2023-02-22 15:17:02**SILVER GALVANIZED MILL FINISH ONLY**

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By amhamilt Date 2023-01-31 Time 15:33 Rev Time 0.00
Received By amhamilt Date 2023-01-31 Time 15:33 Sent To  
Notes
2023-01-31 15:33:43**SILVER MILL FINISH ONLY**

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 14:21 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 14:21 Sent To  
Notes
2022-12-30 14:23:52MILL FINISH/SILVER ONLY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-28 Cont ID  
Sent By jbrooks Date 2023-02-28 Time 10:57 Rev Time 0.00
Received By jbrooks Date 2023-02-14 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-09 Cont ID  
Sent By jbrooks Date 2023-02-09 Time 12:12 Rev Time 0.00
Received By jbrooks Date 2023-01-24 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-03 Cont ID  
Sent By aoliver Date 2023-01-03 Time 10:05 Rev Time 0.00
Received By aoliver Date 2022-12-09 Time 09:56 Sent To  
Notes
***NONE***