Plan Review Stops For Permit 22101345 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-03-03 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-03 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-03 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-12-07 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-12-07 |
Time |
12:21 |
Sent To |
|
|
Notes |
2022-12-07 12:47:20 | 1ST BUILDING REVIEW | | RESULTS: CORRECTIONS NEEDED | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | PLANS EXAMINER II | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NFPA 70 2017 EDITION NEC 2017 | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | NOTICE: A FEMA ELEVATION CERTIFICATE (EC) WAS SUBMITTED | | FOR REVIEW. THIS PROPERTY IS NOT LOCATED IN A SPECIAL | | FLOOD HAZARD AREA (SFHA). THE CITY DOES NOT REVIEW EC'S | | FOR PROPERTIES THAT ARE NOT LOCATED IN A SFHA. | | | | 1. N/A | | | | 2. PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. | | R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO | | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES | | (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 | | SQUARE FEET (2.8 M2). | | | | 3.PROVIDE A FLASHING DETAIL FOR WINDOWS AND EXT. DOORS | | PER R703.4 | | EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT EXTERIOR | | WINDOW AND DOOR OPENINGS SHALL EXTEND TO THE SURFACE OF | | THE EXTERIOR WALL FINISH OR TO THE WATER-RESISTIVE | | BARRIER COMPLYING WITH SECTION 703.2 FOR SUBSEQUENT | | DRAINAGE. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-02-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-02-22 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-02-22 |
Time |
08:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-11-30 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-11-30 |
Time |
13:29 |
Sent To |
|
|
Notes |
2022-11-30 15:06:16 | ELECTRIC REVIEW FAILED | | 1) ELECTRIC PANEL SHOWN IS LOCATED IN A NICHE THAT | | CONTAINS A CABINET. IT APPEARS THIS WILL NOT COMPLY | | WITH NEC 110.26 FOR CLEARANCE AROUND ELECTRIC EQIPMENT | | WHICH REQUIRES 30" OF WIDTH, 36" CLEARSPACE IN FRONT OF | | EQUIPMENT AND 6'6" HEAD ROOM. PLEASE CORRECT AS | | APPLICABLE | | 2) PLAN DETAILS LIGHT FIXTURE ABOVE MASTER BATH TUB. | | PLEASE DETAIL HOW THIS WILL COMPLY WITH NEC 410-8 | | LUMINAIRS INSTALLED IN TUB OR SHOWER AREAS. | | 3) PLEASE DETAIL LOCATION OF NEW CAR CHARGING OUTLET ON | | ELECTRIC PLAN. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-03-24 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-03-24 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-03-16 |
Time |
16:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-03-03 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-03 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-02-10 |
Time |
15:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-12-07 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-11-03 |
Time |
07:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-04-14 |
Time |
09:48 |
Sent To |
|
|
Notes |
2023-04-14 09:48:27 | 4/14/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-12-07 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-12-07 |
Time |
12:21 |
Sent To |
|
|
Notes |
2022-12-07 13:39:16 | IMPACT FEES | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-15 |
Time |
06:12 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-15 |
Time |
06:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-11-17 |
Time |
06:16 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-11-17 |
Time |
06:16 |
Sent To |
|
|
Notes |
2022-11-17 06:16:30 | 1ST REVIEW FMC | | PERMIT: 22101345 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS D-1.1 AND A2.1 INDICATE THE EXISTING AHU IS | | TO BE RELOCATED. SHEET A2.1 INDICATES THE NEW LOCATION | | IS IN THE GARAGE. SHEET M1.0 HAS THE AHU IN A CLOSET IN | | THE BATHROOM WHICH IS WHERE THE D1.1 SHEETS INDICATES | | WAS THE ORIGINAL LOCATION. PLEASE MAKE SURE THE PLANS | | MATCH. FBC 107.3.5 | | | | 2) PROVIDE THE TERMINATION LOCATIONS FOR THE BATH | | EXHAUST FANS. FRC M1506.3 | | | | 3) PROVIDE THE ANCHORAGE DETAILS FOR THE CONDENSING | | UNIT. FRC M1307.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-02-13 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-02-13 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-02-13 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2022-11-15 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2022-11-15 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2022-11-15 |
Time |
07:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-12-07 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-12-07 |
Time |
12:21 |
Sent To |
|
|
Notes |
2022-12-07 14:43:30 | PROVISO ON PLAN PAGE A2.2: A SEPERATE ROOFING PERMIT IS | | REQUIRED. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-03-03 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2023-03-03 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2023-03-03 |
Time |
16:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2022-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-12-07 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-12-07 |
Time |
12:21 |
Sent To |
|
|
Notes |
2022-11-17 06:17:51 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-03-24 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-03-24 |
Time |
16:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-02-22 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-02-22 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-02-22 |
Time |
11:43 |
Sent To |
|
|
Notes |
2023-02-22 11:45:04 | 2/22/23 FAILED | | | | PREVIOUS LANDSCAPE COMMENT NOT SATISIFIED: | | | | THE VALUE OF THE CONSTRUCTION ($215,000) EXCEEDS 50% OF | | THE STRUCTURE'S VALUE ($77,004) ACCORDING TO THE P.B.C. | | PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO | | SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE | | PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR | | ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO | | CONFORMITY | | | | REASON: | | FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE | | IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT | | VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR | | STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY | | THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN | | INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE | | CONCLUSION OF THE PROJECT. | | | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | PLANNER | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2022-11-21 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2022-11-21 |
Time |
14:32 |
Sent To |
|
|
Notes |
2022-11-21 14:35:21 | 11/21/2022 FAILED | | | | PLEASE SHOW THE WEST SIDE SETBACK, AS IT IS NOT SHOWN | | CLEARLY. | | | | PLEASE APPLY FOR A LANDSACPE PERMIT | | | | THE VALUE OF THE CONSTRUCTION ($215,000) EXCEEDS 50% OF | | THE STRUCTURE'S VALUE ($77,004) ACCORDING TO THE P.B.C. | | PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO | | SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | SITE INTO CONFORMITY. | | | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | ASSOCIATE PLANNER | | [email protected] | | |
|
|