Plan Review Stops For Permit 22101282 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-24 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-24 |
Time |
07:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-06-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-16 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-16 |
Time |
11:11 |
Sent To |
|
|
Notes |
2023-06-16 11:13:49 | WINDOWS AND DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | DRAWINGS SHOW THAT YOU ARE REMOVING AND BLOCKING UP THE | | BATHROOM WINDOW - IF THE BATHROOM HAS AN EXISTING VENT | | - PLEASE SHOW THE EXISTING VENT ON THE WINDOW | | REPLACEMENT FLOOR PLAN. | | | | 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM | | - FBC R303.3 BATHROOMS. | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN | | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), | | ONE-HALF OF WHICH MUST BE OPENABLE. | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE | | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE | | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST | | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE | | OUTDOORS. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-05-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-10 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-10 |
Time |
14:03 |
Sent To |
|
|
Notes |
2023-05-10 14:03:55 | WINDOWS AND DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM | | - FBC R303.3 BATHROOMS. | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN | | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), | | ONE-HALF OF WHICH MUST BE OPENABLE. | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE | | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE | | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST | | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE | | OUTDOORS. | | | | 2) PLEASE REVISE THE BUILDING PERMIT APPLICATION TO | | SHOW THE JOB VALUE THAT INCLUDES THE LABOR COST - | | WINDOW ESTIMATE PROVIDED SHOWS ONLY THE COST OF THE | | WINDOWS - FBC 109.3 BUILDING PERMIT VALUATION. FOR | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL ??? SWIFT, MEANS, ETC.) AS PUBLISHED | | BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-17 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-17 |
Time |
13:16 |
Sent To |
|
|
Notes |
2023-02-17 13:32:20 | WINDOWS AND DOORS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM | | - FBC R303.3 BATHROOMS. | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN | | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), | | ONE-HALF OF WHICH MUST BE OPENABLE. | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE | | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE | | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST | | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE | | OUTDOORS. |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
3 |
Status |
F |
Date |
2023-07-10 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-07-10 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-07-10 |
Time |
15:14 |
Sent To |
|
|
Notes |
2023-07-10 15:15:06 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-06-08 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-06-08 |
Time |
08:56 |
Sent To |
|
|
Notes |
2023-06-08 08:57:20 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | GRID PATTERN NEEDS TO MATCH EXISTING, NOT 6/6 AS | | PROPOSED. | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | [email protected] | | 561.822.1428 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-02-03 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-02-03 |
Time |
12:19 |
Sent To |
|
|
Notes |
2023-02-03 14:55:47 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | NEED MORE INFO ON REPLACEMENT WINDOWS--NEED TO VERIFY | | THAT GRID PATTERN WILL MATCH EXISTING, GLASS WILL BE | | CLEAR, AND FRAMES WILL BE SILVER. ADDITIONALLY, NEED | | MORE INFORMATION ON WINDOW THAT IS BEING ENCLOSED. | | | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | [email protected] | | 561.822.1428 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-07-21 |
Time |
08:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-07-10 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-07-10 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-06-15 |
Time |
08:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-09 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-09 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-05-09 |
Time |
09:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-02-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-21 |
Time |
06:56 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-01-24 |
Time |
08:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2023-07-25 |
|
|
Cont ID |
|
Sent By |
jbaker |
Date |
2023-07-25 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
jbaker |
Date |
2023-07-25 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2023-02-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-02-21 |
Time |
06:56 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-02-21 |
Time |
06:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-02-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-02-17 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-02-17 |
Time |
13:33 |
Sent To |
|
|
Notes |
|
|