Plan Review Details - Permit 22101282
Plan Review Stops For Permit 22101282
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By rmcphers Date 2023-07-24 Time 07:56 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-16 Cont ID  
Sent By rmcphers Date 2023-06-16 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2023-06-16 Time 11:11 Sent To  
Notes
2023-06-16 11:13:49WINDOWS AND DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 DRAWINGS SHOW THAT YOU ARE REMOVING AND BLOCKING UP THE
 BATHROOM WINDOW - IF THE BATHROOM HAS AN EXISTING VENT
 - PLEASE SHOW THE EXISTING VENT ON THE WINDOW
 REPLACEMENT FLOOR PLAN.
  
 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM
 - FBC R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-10 Cont ID  
Sent By rmcphers Date 2023-05-10 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2023-05-10 Time 14:03 Sent To  
Notes
2023-05-10 14:03:55WINDOWS AND DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM
 - FBC R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 2) PLEASE REVISE THE BUILDING PERMIT APPLICATION TO
 SHOW THE JOB VALUE THAT INCLUDES THE LABOR COST -
 WINDOW ESTIMATE PROVIDED SHOWS ONLY THE COST OF THE
 WINDOWS - FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL ??? SWIFT, MEANS, ETC.) AS PUBLISHED
 BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By rmcphers Date 2023-02-17 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2023-02-17 Time 13:16 Sent To  
Notes
2023-02-17 13:32:20WINDOWS AND DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM
 - FBC R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.

Review Stop HIST HISTORICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2023-07-10 Cont ID  
Sent By vbroglia Date 2023-07-10 Time 15:14 Rev Time 0.00
Received By vbroglia Date 2023-07-10 Time 15:14 Sent To  
Notes
2023-07-10 15:15:06PREVIOUS COMMENTS NOT ADDRESSED

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2023-06-08 Cont ID  
Sent By amhamilt Date 2023-06-08 Time 08:56 Rev Time 0.00
Received By amhamilt Date 2023-06-08 Time 08:56 Sent To  
Notes
2023-06-08 08:57:20THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 GRID PATTERN NEEDS TO MATCH EXISTING, NOT 6/6 AS
 PROPOSED.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-02-03 Cont ID  
Sent By amhamilt Date 2023-02-03 Time 12:19 Rev Time 0.00
Received By amhamilt Date 2023-02-03 Time 12:19 Sent To  
Notes
2023-02-03 14:55:47THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 NEED MORE INFO ON REPLACEMENT WINDOWS--NEED TO VERIFY
 THAT GRID PATTERN WILL MATCH EXISTING, GLASS WILL BE
 CLEAR, AND FRAMES WILL BE SILVER. ADDITIONALLY, NEED
 MORE INFORMATION ON WINDOW THAT IS BEING ENCLOSED.
  
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-21 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-10 Cont ID  
Sent By vbroglia Date 2023-07-10 Time 15:46 Rev Time 0.00
Received By vbroglia Date 2023-06-15 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-09 Cont ID  
Sent By aoliver Date 2023-06-09 Time 07:21 Rev Time 0.00
Received By aoliver Date 2023-05-09 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-21 Cont ID  
Sent By medwards Date 2023-02-21 Time 06:56 Rev Time 0.00
Received By medwards Date 2023-01-24 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2023-07-25 Cont ID  
Sent By jbaker Date 2023-07-25 Time 10:05 Rev Time 0.00
Received By jbaker Date 2023-07-25 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-02-21 Cont ID  
Sent By medwards Date 2023-02-21 Time 06:56 Rev Time 0.00
Received By medwards Date 2023-02-21 Time 06:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-17 Cont ID  
Sent By rmcphers Date 2023-02-17 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2023-02-17 Time 13:33 Sent To  
Notes
***NONE***