Plan Review Details - Permit 22101280
Plan Review Stops For Permit 22101280
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-23 Cont ID  
Sent By lbond Date 2023-02-23 Time 11:37 Rev Time 0.00
Received By lbond Date 2023-02-23 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 18:39 Rev Time 0.00
Received By jgomez Date 2023-01-19 Time 18:35 Sent To  
Notes
2023-01-19 18:40:15RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22101280
 616 CLEARWATER PARK RD # 1113
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 2- VALUATION:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL
 COSTS. PROVIDE COMPLETE COST BREAKDOWN.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-05 Cont ID  
Sent By jgomez Date 2023-01-05 Time 11:00 Rev Time 0.00
Received By jgomez Date 2023-01-05 Time 10:52 Sent To  
Notes
2023-01-05 11:00:43RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22101280
 616 CLEARWATER PARK RD # 1113
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 2- VALUATION:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL
 COSTS. PROVIDE COMPLETE COST BREAKDOWN.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-31 Cont ID  
Sent By cwalker Date 2023-01-31 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-06 Cont ID  
Sent By cwalker Date 2023-01-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-11-15 Cont ID  
Sent By cwalker Date 2022-11-15 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-11-15 09:38:43FIRE REVIEW COMMENTS:
  
 PROVIDE DOCUMENTATION OF THE FIRE PERFORMANCE OF THE
 PROPOSED FLOORING TO BE INSTALLED TO INCLUDE THE
 CRITICAL RADIANT FLUX OF THE TESTED MATERIALS. FLORIDA
 FIRE PREVENTION CODE, NFPA 101, LIFE SAFETY CODE 10.2.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-23 Cont ID  
Sent By lbond Date 2023-02-23 Time 11:38 Rev Time 0.00
Received By lbond Date 2023-01-30 Time 13:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 18:34 Rev Time 0.00
Received By jgomez Date 2023-01-05 Time 16:51 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-05 Time 11:00 Rev Time 0.00
Received By jgomez Date 2022-11-14 Time 09:59 Sent To I
Notes
***NONE***