Plan Review Details - Permit 22100952
Plan Review Stops For Permit 22100952
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-01-17 Cont ID  
Sent By jgomez Date 2023-01-17 Time 14:59 Rev Time 0.00
Received By jgomez Date 2023-01-17 Time 14:47 Sent To  
Notes
2023-01-17 15:00:11LUXURY VINYL OVER LV-200 UNDERLAYMENT. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-01-12 Cont ID  
Sent By jgomez Date 2023-01-12 Time 14:28 Rev Time 0.00
Received By jgomez Date 2023-01-12 Time 13:58 Sent To  
Notes
2023-01-12 14:32:14RESIDENTIAL (R2) REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 A) OK.
  
 ORIGINAL COMMENT:
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200
 UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR
 LAMINATED WOOD.
  
 ORIGINAL COMMENT:
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200
 UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR
 LAMINATED WOOD.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 17:10 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 16:42 Sent To  
Notes
2023-01-09 17:12:57RESIDENTIAL (R2) FOURTH REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 INFORMATION SUBMITTED IS FOR THE VINYL FLOORING PLANK.
 NEED THE TEST FOR THE SENTINEL PROTECT PLUS
 UNDERLAYMENT.
  
 ORIGINAL COMMENT:
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT FOR THE "SENTINEL "SENTINEL PROTECT
 PLUS UNDERLAYMENT .
 NOTE: PRODUCT SPECIFICATION SHEET FOR SENTINEL PROTECT
 PLUS UNDERLAYMENT SUBMITTED IS FOR 6" CONCRETE SLAB
 WITH DROP CEILING. THIS BUILDING DOESN'T HAVE A DROP
 CEILING. THEREFORE, NEED COPY OF TEST REPORT WITHOUT
 THE DROP CEILING.
  
 ORIGINAL COMMENT:
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT FOR THE "SENTINEL "SENTINEL PROTECT
 PLUS UNDERLAYMENT .
 NOTE: PRODUCT SPECIFICATION SHEET FOR SENTINEL PROTECT
 PLUS UNDERLAYMENT SUBMITTED IS FOR 6" CONCRETE SLAB
 WITH DROP CEILING. THIS BUILDING DOESN'T HAVE A DROP
 CEILING. THEREFORE, NEED COPY OF TEST REPORT WITHOUT
 THE DROP CEILING.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 11:15 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 09:30 Sent To  
Notes
2023-01-09 11:16:07RESIDENTIAL (R2) THIRD REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 ORIGINAL COMMENT:
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 ORIGINAL COMMENT:
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED
 ACTUAL TEST REPORT.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-04 Cont ID  
Sent By jgomez Date 2023-01-04 Time 16:47 Rev Time 0.00
Received By jgomez Date 2023-01-04 Time 16:10 Sent To  
Notes
2023-01-04 16:47:26RESIDENTIAL (R2) SECOND REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 REPEAT COMMENT. INFORMATION WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 REPEAT COMMENT. INFORMATION WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 REPEAT COMMENT. INFORMATION WAS NOT PROVIDED.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 ORIGINAL COMMENT:
 2- VALUATION:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL
 COSTS. PROVIDE COMPLETE COST BREAKDOWN.
  
 RESPONSE:
 REPEAT COMMENT. INFORMATION WAS NOT PROVIDED. NEED TO
 PROVIDE THE VALUE FOR THE FINISH FLOORING AND SOUND
 INSULATION MATERIAL TO BE INSTALLED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 13:53 Rev Time 0.00
Received By jgomez Date 2022-12-27 Time 13:28 Sent To  
Notes
2022-12-27 13:54:18RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100952
 1801 N FLAGLER DR # 309
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 2- VALUATION:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL
 COSTS. PROVIDE COMPLETE COST BREAKDOWN.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By pleduc Date 2023-01-19 Time   Rev Time 0.00
Received By pleduc Date 2023-01-19 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-30 Cont ID  
Sent By pleduc Date 2022-12-30 Time   Rev Time 0.00
Received By pleduc Date 2022-12-30 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By pleduc Date 2022-10-31 Time   Rev Time 0.00
Received By pleduc Date 2022-10-31 Time 12:00 Sent To  
Notes
2022-10-31 12:09:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF NEW FLOORING BUT THERE IS
 NO SPEC SHEET NOR A PRODUCT NAME OR FLOORING MATERIAL
 TYPE THE ACTUAL PROPOSED FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 NAME, TYPE AND THE PRODUCT SPEC SHEETS INDICATING THE
 FIRE BEHAVIOR RATING.
  
  
 2) THERE IS AN INDICATION OF NEW FLOORING BUT THERE IS
 NO SPEC SHEET NOR A PRODUCT NAME FOR THE SOUNDPROOFING
 UNDERLAYMENT.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE
 UNDERLAYMENT NAME, TYPE AND THE PRODUCT SPEC SHEETS.
  
  
 3) A SHEET WAS PROVIDED WITH SQUARES & DIMENSIONS,
 HOWEVER, A FLOOR PLAN WAS NOT PROVIDED OF THE UNIT.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE A FLOOR
 PLAN INDICATING THE LOCATIONS & LIMITS OF THE PROPOSED
 WORK.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-01-20 Cont ID  
Sent By lmarchan Date 2023-01-20 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2023-01-17 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-12 Cont ID  
Sent By jgomez Date 2023-01-12 Time 14:32 Rev Time 0.00
Received By jgomez Date 2023-01-12 Time 13:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 17:13 Rev Time 0.00
Received By jgomez Date 2023-01-09 Time 16:42 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-09 Cont ID  
Sent By jgomez Date 2023-01-09 Time 11:16 Rev Time 0.00
Received By jgomez Date 2023-01-05 Time 16:10 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-04 Cont ID  
Sent By jgomez Date 2023-01-04 Time 16:47 Rev Time 0.00
Received By jgomez Date 2022-12-29 Time 12:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 13:54 Rev Time 0.00
Received By jgomez Date 2022-10-28 Time 10:48 Sent To I
Notes
***NONE***