Plan Review Stops For Permit 22100952 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2023-01-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-17 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-17 |
Time |
14:47 |
Sent To |
|
|
Notes |
2023-01-17 15:00:11 | LUXURY VINYL OVER LV-200 UNDERLAYMENT. JG. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-12 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-12 |
Time |
13:58 |
Sent To |
|
|
Notes |
2023-01-12 14:32:14 | RESIDENTIAL (R2) REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22100952 | | 1801 N FLAGLER DR # 309 | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | | | A) OK. | | | | ORIGINAL COMMENT: | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200 | | UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR | | LAMINATED WOOD. | | | | ORIGINAL COMMENT: | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200 | | UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR | | LAMINATED WOOD. | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-09 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-09 |
Time |
16:42 |
Sent To |
|
|
Notes |
2023-01-09 17:12:57 | RESIDENTIAL (R2) FOURTH REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22100952 | | 1801 N FLAGLER DR # 309 | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | | | ORIGINAL COMMENT: | | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION | | (2020). | | | | RESPONSE: | | INFORMATION SUBMITTED IS FOR THE VINYL FLOORING PLANK. | | NEED THE TEST FOR THE SENTINEL PROTECT PLUS | | UNDERLAYMENT. | | | | ORIGINAL COMMENT: | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED | | ACTUAL TEST REPORT FOR THE "SENTINEL "SENTINEL PROTECT | | PLUS UNDERLAYMENT . | | NOTE: PRODUCT SPECIFICATION SHEET FOR SENTINEL PROTECT | | PLUS UNDERLAYMENT SUBMITTED IS FOR 6" CONCRETE SLAB | | WITH DROP CEILING. THIS BUILDING DOESN'T HAVE A DROP | | CEILING. THEREFORE, NEED COPY OF TEST REPORT WITHOUT | | THE DROP CEILING. | | | | ORIGINAL COMMENT: | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED | | ACTUAL TEST REPORT FOR THE "SENTINEL "SENTINEL PROTECT | | PLUS UNDERLAYMENT . | | NOTE: PRODUCT SPECIFICATION SHEET FOR SENTINEL PROTECT | | PLUS UNDERLAYMENT SUBMITTED IS FOR 6" CONCRETE SLAB | | WITH DROP CEILING. THIS BUILDING DOESN'T HAVE A DROP | | CEILING. THEREFORE, NEED COPY OF TEST REPORT WITHOUT | | THE DROP CEILING. | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-01-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-09 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-09 |
Time |
09:30 |
Sent To |
|
|
Notes |
2023-01-09 11:16:07 | RESIDENTIAL (R2) THIRD REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22100952 | | 1801 N FLAGLER DR # 309 | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | | | ORIGINAL COMMENT: | | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION | | (2020). | | | | RESPONSE: | | SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED | | ACTUAL TEST REPORT. | | | | ORIGINAL COMMENT: | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED | | ACTUAL TEST REPORT. | | | | ORIGINAL COMMENT: | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | SAME INFORMATION FROM LAST TIME WAS SUBMITTED. NEED | | ACTUAL TEST REPORT. | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-01-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-04 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-04 |
Time |
16:10 |
Sent To |
|
|
Notes |
2023-01-04 16:47:26 | RESIDENTIAL (R2) SECOND REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22100952 | | 1801 N FLAGLER DR # 309 | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | | | ORIGINAL COMMENT: | | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION | | (2020). | | | | RESPONSE: | | REPEAT COMMENT. INFORMATION WAS NOT PROVIDED. | | | | ORIGINAL COMMENT: | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | REPEAT COMMENT. INFORMATION WAS NOT PROVIDED. | | | | ORIGINAL COMMENT: | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | RESPONSE: | | REPEAT COMMENT. INFORMATION WAS NOT PROVIDED. | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | ORIGINAL COMMENT: | | 2- VALUATION: | | VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. | | 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL | | COSTS. PROVIDE COMPLETE COST BREAKDOWN. | | | | RESPONSE: | | REPEAT COMMENT. INFORMATION WAS NOT PROVIDED. NEED TO | | PROVIDE THE VALUE FOR THE FINISH FLOORING AND SOUND | | INSULATION MATERIAL TO BE INSTALLED. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-12-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-27 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-27 |
Time |
13:28 |
Sent To |
|
|
Notes |
2022-12-27 13:54:18 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22100952 | | 1801 N FLAGLER DR # 309 | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION | | (2020). | | | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | 2- VALUATION: | | VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. | | 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL | | COSTS. PROVIDE COMPLETE COST BREAKDOWN. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2023-01-19 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-01-19 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-01-19 |
Time |
10:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-12-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-12-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-12-30 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-10-31 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-10-31 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-10-31 |
Time |
12:00 |
Sent To |
|
|
Notes |
2022-10-31 12:09:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF NEW FLOORING BUT THERE IS | | NO SPEC SHEET NOR A PRODUCT NAME OR FLOORING MATERIAL | | TYPE THE ACTUAL PROPOSED FLOORING. | | | | VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT | | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. | | | | PER NFPA 101, CH 30 | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | ACCORDANCE WITH | | SECTION 10.2. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, | | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS | | WOULD NOT BE REQUIRED. | | | | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL | | FLOORING, WOOD/VINYL LAMINATES, ETC. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING | | NAME, TYPE AND THE PRODUCT SPEC SHEETS INDICATING THE | | FIRE BEHAVIOR RATING. | | | | | | 2) THERE IS AN INDICATION OF NEW FLOORING BUT THERE IS | | NO SPEC SHEET NOR A PRODUCT NAME FOR THE SOUNDPROOFING | | UNDERLAYMENT. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE | | UNDERLAYMENT NAME, TYPE AND THE PRODUCT SPEC SHEETS. | | | | | | 3) A SHEET WAS PROVIDED WITH SQUARES & DIMENSIONS, | | HOWEVER, A FLOOR PLAN WAS NOT PROVIDED OF THE UNIT. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE A FLOOR | | PLAN INDICATING THE LOCATIONS & LIMITS OF THE PROPOSED | | WORK. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2023-01-20 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-01-20 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-01-17 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2023-01-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-12 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-12 |
Time |
13:58 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-01-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-09 |
Time |
17:13 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-09 |
Time |
16:42 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-01-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-09 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2023-01-05 |
Time |
16:10 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-01-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2023-01-04 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-12-29 |
Time |
12:44 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-12-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2022-12-27 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2022-10-28 |
Time |
10:48 |
Sent To |
I |
|
Notes |
|
|