Plan Review Details - Permit 22100890
Plan Review Stops For Permit 22100890
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-03-23 Cont ID  
Sent By rmcphers Date 2023-03-23 Time 16:10 Rev Time 0.00
Received By rmcphers Date 2023-03-23 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-03-15 Cont ID  
Sent By rmcphers Date 2023-03-15 Time 11:17 Rev Time 0.00
Received By rmcphers Date 2023-03-15 Time 11:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-03-08 Cont ID  
Sent By rmcphers Date 2023-03-08 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2023-03-08 Time 11:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-02-13 Cont ID  
Sent By rmcphers Date 2023-02-13 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2023-02-13 Time 10:19 Sent To  
Notes
2023-02-13 10:20:04CHANGE OF OCCUPANCY CLASSIFICATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 3RD REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-18 Cont ID  
Sent By rmcphers Date 2023-01-18 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2023-01-18 Time 09:10 Sent To  
Notes
2023-01-18 09:15:43CHANGE OF OCCUPANCY CLASSIFICATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 14:53 Sent To  
Notes
2022-11-08 15:13:41CHANGE OF OCCUPANCY CLASSIFICATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE NEW OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3 (DESCRIBE THE USE FOR THE SPACE SUCH AS -
 RETAIL, OFFICE, NIGHT CLUB, THEATER ETC..) (EVENT SPACE
 - WHAT TYPE OF EVENT?)
  
 2) PLEASE SHOW THE UNIT SQUARE FOOTAGE. FBC WPB 107.2
  
 3) SHOW ALL DIMENSIONS BETWEEN WALLS. FBC WPB 107.2
  
 4) PLEASE SHOW THE STAGE OR PLATFORM DETAILS - FBC 410
  
 5) PLEASE SHOW THE KITCHEN DETAILS - FBC WPB 107.2
  
 6) SHOW THE HOURLY FIRE RATINGS FOR THE TENNANT
 SEPARATION WALLS - FBC 508
  
 7) PLEASE SHOW THE USE FOR EACH ADJACENT TENNANT - FBC
 508
  
 8) THE DRAWING PROVIDED HAS A BLACKED OUT AREA - PLEASE
 PROVIDE A DRAWING WITH OUT THE BLACKED OUT AREA.
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2023-02-22 Cont ID  
Sent By jleahy Date 2023-02-22 Time 15:57 Rev Time 0.00
Received By jleahy Date 2023-02-22 Time 15:53 Sent To  
Notes
2023-02-22 15:58:05NO ELECTRICAL WORK SHOWN JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By jleahy Date 2023-01-25 Time 16:22 Rev Time 0.00
Received By jleahy Date 2023-01-25 Time 16:22 Sent To  
Notes
2023-01-25 16:22:55SEE 11/8/22 REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By jleahy Date 2022-11-08 Time 16:13 Rev Time 0.00
Received By jleahy Date 2022-11-08 Time 16:12 Sent To  
Notes
2022-11-08 16:14:54NO ELECTRICAL WORK SHOWN PLEASE SHOW ALL ELECTRICAL
 WORK NEW AND EXISTING. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-03-14 Cont ID  
Sent By pleduc Date 2023-03-14 Time   Rev Time 0.00
Received By pleduc Date 2023-03-14 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-03-07 Cont ID  
Sent By pleduc Date 2023-03-07 Time   Rev Time 0.00
Received By pleduc Date 2023-03-07 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-02-13 Cont ID  
Sent By cwalker Date 2023-02-13 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-01-25 Cont ID  
Sent By cwalker Date 2023-01-25 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-01-25 10:35:31FIRE REVIEW COMMENTS:
  
 (1) THE OCCUPANT LOAD CALCULATIONS ARE NOT CORRECT. THE
 DANCE FLOOR SHALL BE CALCULATED AT 7 SQ. FT. PER PERSON
 NET. NFPA 101, LIFE SAFETY CODE, 7.3.1.2
  
 (2) PROVIDE A TOTAL OCCUPANT LOAD CALCULATION FOR THE
 ENTIRE SPACE. NFPA 101, LIFE SAFETY CODE, 12.1.7
  
 (3) PROVIDE EXIT DOOR HARDWARE DETAILS INCLUDING
 LOCKING DEVICES. NFPA 101, LIFE SAFETY CODE, 12.2.2
  
 (4) PROVIDE THE AISLE WIDTH SERVING SEATING AT TABLES.
 NFPA 101, LIFE SAFETY CODE 12.2.5.8
  
  
 (5) ANY CHANGES, ADDITIONS, MODIFICATIONS, ETC. TO ANY
 LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM)
 SHALL BE PERFORMED BY PROPERLY LICENSED CONTRACTORS
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS. A REVIEW OF
 LIFE SAFETY FEATURES MAY NEED TO BE CONDUCTED. NFPA
 101, LIFE SAFETY CODE, 12.4.1.3.3
  
 (6) PROVIDE DETAILS ON INTERIOR FINISHES. NFPA 101,
 LIFE SAFETY CODE, 12.3.3
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-11-03 Cont ID  
Sent By   Date 2022-11-03 Time   Rev Time  
Received By bdolan Date 2022-11-03 Time 12:18 Sent To  
Notes
2022-11-03 12:22:27THE FOLLOWING COMMENTS WERE SUBMITTED BY CAPT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 THE PLAN SET DOES NOT SPECIFY THE TYPE OF EVENTS SPACE
 IS TO BE USED FOR, PROPOSED OCCUPANT LOAD, LIFE SAFETY
 FEATURES PRESENT IN THE SPACE, A SITE PLAN FOR THE
 OVERALL PROJECT AREA, AND ANY CHANGES TO BE MADE TO
 MEET LIFE SAFETY CODE REQUIREMENTS FOR THE PROPOSED
 OCCUPANCY TYPE.
  
 PLEASE SUBMIT A MORE COMPREHENSIVE PAN SET FOR THE
 PROPOSED CHANGE OF OCCUPANCY.
  
  
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 11:39 Rev Time 0.00
Received By medwards Date 2023-03-22 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-22 Cont ID  
Sent By avolcy Date 2023-03-22 Time 10:20 Rev Time 0.00
Received By avolcy Date 2023-03-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-09 Cont ID  
Sent By avolcy Date 2023-03-09 Time 16:10 Rev Time 0.00
Received By avolcy Date 2023-03-06 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-22 Cont ID  
Sent By jleahy Date 2023-02-22 Time 15:58 Rev Time 0.00
Received By jleahy Date 2023-02-10 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-25 Cont ID  
Sent By jleahy Date 2023-01-25 Time 16:23 Rev Time 0.00
Received By jleahy Date 2023-01-17 Time 17:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By jleahy Date 2022-11-08 Time 16:14 Rev Time 0.00
Received By jleahy Date 2022-10-27 Time 07:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-03-26 Cont ID  
Sent By lmarchan Date 2023-03-26 Time 08:05 Rev Time 0.00
Received By lmarchan Date 2023-03-24 Time 12:26 Sent To  
Notes
2023-03-26 08:05:03NO IMPACT FEES DUE. LEM
2023-03-24 12:26:38EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 15:13 Sent To  
Notes
2022-11-08 15:14:30PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2023-03-24 Cont ID  
Sent By medwards Date 2023-03-24 Time 11:39 Rev Time 0.00
Received By medwards Date 2023-03-24 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2023-03-14 Cont ID  
Sent By medwards Date 2023-03-14 Time 10:05 Rev Time 0.00
Received By medwards Date 2023-03-14 Time 10:05 Sent To  
Notes
2023-03-14 10:05:555TH REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 1) MAIN ENTRY LOBBIES: 349 SQ FT 349/1000 = .349; .349
 X 10 OCCUPANT DENSITY = 3.49, ROUND UP TO 4; 4 X 5
 CFM/PERSON = 20 CFMS REQUIRED FOR THE OCCUPANTS; 349 SQ
 FT X .06 CFM/SQ.FT. = 20.94 CFM FOR THE SPACE; 20 + 21
 = 41 CFM REQUIRED FOR THE MAIN ENTRY LOBBY.
  
 2) MULTI-USE ASSEMBLY: 4,976 SQ. FT., 4976/1000 = 4.976
 OCCUPANTS ROUND UP; 5 X 100 = 500; 500 X 7.5 = 3750 CFM
 FOR OCCUPANTS; 4976 X .06 = 298.56 ROUND UP; 3750 + 299
 = 4049 CFM REQUIRED FOR MULTI-USE ASSEMBLY.
  
 3) DINING: 400 SQ. FT., 400/ 1000 = .4; .4 X 70 = 28
 OCCUPANTS; 28 X 7.5 = 210 CFM REQUIRED FOR THE
 OCCUPANTS; 400 X .18 = 72 CFM FOR THE SPACE. 210 + 72 =
 282 CFM REQUIRED FOR DINING
  
 4) THE TOTAL OUTDOOR AIR REQUIRED FOR THIS CHANGE OF
 USE IS 4,414 CFMS.
  
 4414/ 3 = 1471 CFM OF O.A. PER UNIT
 TYPICAL O.D. SUPPLIED FROM A 5-TON UNIT IS 350 CFM: SO,
 700 CFMS X 3 10-TON UNIT = 2100 CFM???S OF OUTDOOR AIR.
  
 PLEASE SHOW THAT THE EXISTING UNITS WILL BE SIZED TO
 BRING IN THE REQUIRED OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-03-07 Cont ID  
Sent By medwards Date 2023-03-07 Time 13:43 Rev Time 0.00
Received By medwards Date 2023-03-07 Time 13:43 Sent To  
Notes
2023-03-07 13:43:004TH REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WITH THIS CHANGE OF USE GOING FROM EDUCATIONAL TO AN
 ASSEMBLY OCCUPANCY THE OUTDOOR AIR CALCULATIONS MUST BE
 SUBMITTED TO SHOW THAT THE MECHANICAL SYSTEMS CAN
 HANDLE THE EXTRA LOAD OF MORE PEOPLE BEING ABLE TO
 OCCUPY THE SAME SPACE. PLEASE SUBMIT THE REQUIRED
 OUTDOOR AIR CALCULATIONS FOR THIS USE OF SPACE. THE
 OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES
 THE USE FROM TABLE 403.3.1.1 MUST BE USED FOR THE
 CALCULATIONS. THE OCCUPANT DENSITY FOR THIS OCCUPANCY
 CLASSIFICATION MUST BE USED TO FIND THE MINIMUM
 REQUIRED OCCUPANTS FOR THIS CALCULATION. FMC 403.3.1.1
 AND TABLE 403.3.1.1.
  
 2) THE DESIGNER MUST SHOW THAT THE MECHANICAL SYSTEMS
 THAT ARE EXISTING ARE SIZED CORRECTLY FOR THIS CHANGE
 OF USE. FEC C403.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-02-14 Cont ID  
Sent By medwards Date 2023-02-14 Time 14:17 Rev Time 0.00
Received By medwards Date 2023-02-14 Time 14:17 Sent To  
Notes
2023-02-14 14:17:373RD REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS CHANGE OF USE DOES REQUIRE THE SPACE TO MEET
 THE OUTDOOR AIR REQUIREMENTS FOR THIS NEW OCCUPANCY.
 PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR THIS
 NEW CHANGE OF USE. THE OUTDOOR AIR CALCULATIONS SHALL
 BE DESIGNED FROM THE OCCUPANCY CLASSIFICATION AND
 OCCUPANT DENSITY OF FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-19 Cont ID  
Sent By medwards Date 2023-01-19 Time 11:30 Rev Time 0.00
Received By medwards Date 2023-01-19 Time 11:30 Sent To  
Notes
2023-01-19 11:30:411ST REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADDRESS THE PREVIOUS MECHANICAL COMMENTS.
  
 1) PLEASE PROVIDE THE MECHANICAL DESIGN FOR THE CURRENT
 PERMITTED USE OF THIS TENANT SPACE ALONG WITH A DRAWING
 SHOWING THE PURPOSED USE. THE DRAWING SUBMITTED DOES
 NOT SHOW MUCH INFORMATION FOR THE MECHANICAL DESIGN.
 PROVIDE A COMPLETE OUTDOOR AIR CALCULATION SHOWING EACH
 USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
 2) PROVIDE MORE INFORMATION ABOUT THE STAGE ON THE
 DRAWING. FBC 410.3.7, 410.3.7.2
  
 3) PROVIDE MORE INFORMATION ABOUT THE KITCHEN AREA ON
 THE DRAWING. FMC 507
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 14:33 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 14:33 Sent To  
Notes
2022-11-08 14:34:221ST REVIEW FMC
 PERMIT: 22100890
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL DESIGN FOR THE CURRENT
 PERMITTED USE OF THIS TENANT SPACE ALONG WITH A DRAWING
 SHOWING THE PURPOSED USE. THE DRAWING SUBMITTED DOES
 NOT SHOW MUCH INFORMATION FOR THE MECHANICAL DESIGN.
 PROVIDE A COMPLETE OUTDOOR AIR CALCULATION SHOWING EACH
 USE OF SPACE IN THIS TENANT SPACE. FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
 2) PROVIDE MORE INFORMATION ABOUT THE STAGE ON THE
 DRAWING. FBC 410.3.7, 410.3.7.2
  
 3) PROVIDE MORE INFORMATION ABOUT THE KITCHEN AREA ON
 THE DRAWING. FMC 507
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2023-03-23 Cont ID  
Sent By rwbrown Date 2023-03-23 Time 06:46 Rev Time 0.00
Received By rwbrown Date 2023-03-23 Time 06:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2023-03-14 Cont ID  
Sent By rwbrown Date 2023-03-14 Time 06:56 Rev Time 0.00
Received By rwbrown Date 2023-03-14 Time 06:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-03-07 Cont ID  
Sent By rwbrown Date 2023-03-07 Time 06:59 Rev Time 0.00
Received By rwbrown Date 2023-03-07 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-13 Time 08:41 Rev Time 0.00
Received By rwbrown Date 2023-02-13 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-18 Cont ID  
Sent By jesmith Date 2023-01-18 Time 16:49 Rev Time 0.00
Received By jesmith Date 2023-01-18 Time 13:40 Sent To  
Notes
2023-01-18 16:47:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22100890 7719 S DIXIE HWY
  
 2ND REVIEW
 ELECTRONIC SIGNATURES ARE NOT VALID
  
 PLUMBING COMMENTS: DENIED
  
  
  
 1. COMPLIED
  
 2. PARTIALLY COMPLIED: BASED ON PLANS FROM PREVIOUS
 TENANT (SEE CLOSED PERMIT #02060943), IT APPEARS THERE
 ARE TO BE NO PLUMBING CHANGES FROM THE ORIGINAL
 OCCUPANCY. PLEASE CLARIFY. PLEASE PROVIDE LOCATION OF
 EXISTING WATER HEATER. WPB FBC 107.3.5.1.3
  
 3. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PLEASE
 PROVIDE NEW OCCUPANCY DESIGNATION AS SPELLED OUT IN FBC
 SECTION 302 AND PROVIDE OCCUPANCY LOAD FOR DESIGNATED
 CLASSIFICATION AS SPELLED OUT IN FBC SECTION 1004 SO
 THAT A DETERMINATION OF MINIMUM PLUMBING FIXTURE
 REQUIREMENTS CAN BE DETERMINED IN ACCORDANCE WITH FBC
 PL SECTION 403; PROVIDE PLUMBING FIXTURE SCHEDULE
 SHOWING MINIMUM FIXTURE REQUIREMENTS FOR THE OCCUPANCY
 IN ACCORDANCE WITH FBC PL TABLE 403.1 AND THE ACTUAL
 FIXTURES PROVIDED.
 TO BE CLEAR, PLEASE INDICATE BASED ON NEW OCCUPANCY AND
 FBC PL TABLE 403.1, THE MINIMUM PLUMBING FIXTURE
 REQUIREMENTS INCLUDING QUANTITIES (INCLUDE POTTY PARITY
 FBC PL 403.1.3) AND THE ACTUAL FIXTURES (QUANTITY)
 PROVIDED. FBC EX 1010.1
  
 4. SECOND REQUEST: A REVIEW OF MINIMUM PLUMBING FIXTURE
 REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE
 PLUMBING REVIEW PROCESS (SEE FBC PL 404.1) BUT IS
 TYPICALLY ADDRESSED ON THE ARCHITECTURAL PLANS. ANY
 COMMENTS CONCERNING THESE REQUIREMENTS MUST BE
 SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL; PROVIDE PLAN AND ELEVATION DETAILS FOR
 ACCESSIBLE TOILET ROOM FACILITIES, DRINKING FOUNTAIN(S)
 AND ACCESSIBLE SINKS. COMPLY WITH FBC ACC CHAPTERS 2, 3
 AND 6.
  
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA ACCESSIBILITY CODE 2020
 7TH EDITION PER FBC EX 1006.1
  
 ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL PER FBC ACC 604.3.1
 ***C) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***E) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***F) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***G) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***H) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***J) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ***K) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***L) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2.
 ***M) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ***N) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3
 ***O) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***P) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 ***Q) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
 ***R) DRINKING FOUNTAINS SHALL HAVE A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC
 ACC 602.2.
 ***S) SPOUT OUTLETS FOR ACCESSIBLE DRINKING FOUNTAINS
 SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 602.4.
 ***T) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7.
  
  
 5. N/A
  
  
 END OF COMMENTS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-02 Cont ID  
Sent By jesmith Date 2022-11-02 Time 12:06 Rev Time 0.00
Received By jesmith Date 2022-11-02 Time 10:50 Sent To  
Notes
2022-11-02 12:02:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22100890 7719 S DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. THE FLOOR PLAN WAS NOT DESIGNED BY EITHER AN
 ENGINEER OR ARCHITECT. CERTIFICATION BY CONTRACTOR. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN. WPB FBC 107.3.4.3 CERTIFICATION BY
 CONTRACTOR.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER
 PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
 PER WPB FBC 107.2.1, PLEASE REFERENCE ON THE PLANS THE
 CODES THAT APPLY (SEE LIST ABOVE)
  
 2. PROVIDE A FULL SCOPE OF WORK AND AS APPLICABLE, AN
 EXISTING/DEMOLITION PLUMBING FLOOR PLAN WITH ALL
 EXISTING PLUMBING FIXTURES AND EQUIPMENT INCLUDING
 WATER HEATERS AND A PROPOSED PLUMBING FLOOR PLAN WITH
 ALL PLUMBING FIXTURES AND EQUIPMENT INCLUDING WATER
 HEATERS. PROVIDE AS APPLICABLE, PLUMBING PLAN VIEW TO
 INCLUDE WATER AND SANITARY PIPING, PLUMBING FIXTURES,
 NEW OR EXISTING WATER SERVICE BACKFLOW PREVENTER AND
 EQUIPMENT INCLUDING WATER HEATERS AND PLUMBING
 WATER/SANITARY RISER DIAGRAMS AND DETAILS. ADDRESS AS
 APPLICABLE, THE REQUIREMENTS OF WPB FBC 107.3.5.1.3
 BELOW.
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. ROOF DRAINAGE
 8. BACKFLOW PREVENTION
 9. IRRIGATION
 10. LOCATION OF WATER SUPPLY LINE
 11. GREASE TRAPS
 12. ENVIRONMENTAL REQUIREMENTS
 13. PLUMBING RISER (SANITARY AND WATER)
 14. DESIGN FLOOD ELEVATION
  
 3. PER WPB FBC 107.2.1, PLEASE PROVIDE NEW OCCUPANCY
 DESIGNATION AS SPELLED OUT IN FBC SECTION 302 AND
 PROVIDE OCCUPANCY LOAD FOR DESIGNATED CLASSIFICATION AS
 SPELLED OUT IN FBC SECTION 1004 SO THAT A DETERMINATION
 OF MINIMUM PLUMBING FIXTURE REQUIREMENTS CAN BE
 DETERMINED IN ACCORDANCE WITH FBC PL SECTION 403;
 PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING MINIMUM
 FIXTURE REQUIREMENTS FOR THE OCCUPANCY IN ACCORDANCE
 WITH FBC PL TABLE 403.1 AND THE ACTUAL FIXTURES
 PROVIDED.
  
 4. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL; PROVIDE PLAN AND
 ELEVATION DETAILS FOR ACCESSIBLE TOILET ROOM
 FACILITIES, DRINKING FOUNTAIN(S) AND ACCESSIBLE SINKS.
 COMPLY WITH FBC ACC CHAPTERS 2, 3 AND 6.
  
 5. VALUE OF JOB MAY NEED TO BE ADJUSTED BASED UPON A
 PROPOSED SCOPE OF WORK AND RESUBMITTALS. PROVIDE AN
 ACCURATE VALUATION OF ALL WORK AND COST. WPB FBC 109.3
 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL (1) CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-03-23 Cont ID  
Sent By rwbrown Date 2023-03-23 Time 06:47 Rev Time 0.00
Received By rwbrown Date 2023-03-23 Time 06:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-03-15 Cont ID  
Sent By rmcphers Date 2023-03-15 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2023-03-15 Time 11:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-03-08 Cont ID  
Sent By rmcphers Date 2023-03-08 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2023-03-08 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-02-13 Cont ID  
Sent By rmcphers Date 2023-02-13 Time 10:20 Rev Time 0.00
Received By rmcphers Date 2023-02-13 Time 10:20 Sent To  
Notes
2023-02-13 10:20:41SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-18 Cont ID  
Sent By rmcphers Date 2023-01-18 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2023-01-18 Time 09:15 Sent To  
Notes
2023-01-18 09:16:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SIGNED AND SEALED DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By rmcphers Date 2022-11-08 Time 15:15 Rev Time 0.00
Received By rmcphers Date 2022-11-08 Time 15:15 Sent To  
Notes
2022-11-02 12:08:26PLUMBING SIGNATURES FAILED; SEE PLUMBING REVIEW-COMMENT
 #1. JS

Review Stop Z ZONING
Rev No 5 Status N Date 2023-03-22 Cont ID  
Sent By avolcy Date 2023-03-22 Time 10:19 Rev Time 0.00
Received By avolcy Date 2023-03-22 Time 10:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2023-03-09 Cont ID  
Sent By avolcy Date 2023-03-09 Time 15:55 Rev Time 0.00
Received By avolcy Date 2023-03-09 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-02-16 Cont ID  
Sent By asangele Date 2023-02-16 Time 12:33 Rev Time 0.00
Received By asangele Date 2023-02-16 Time 12:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-24 Cont ID  
Sent By ASangele Date 2023-01-24 Time 10:32 Rev Time 0.00
Received By asangele Date 2023-01-24 Time 10:32 Sent To  
Notes
2023-01-24 11:07:15FAILED
 1/24/2023
  
 IS ANY WORK BEING DOWN TO THE SPACE?
  
 IF THIS IS JUST A CHANGE OF USE THIS PROCESS IS
 COMPLETE WITH A BTR.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-11-04 Cont ID  
Sent By afowlkes Date 2022-11-04 Time 13:47 Rev Time 0.00
Received By afowlkes Date 2022-11-04 Time 13:47 Sent To  
Notes
2022-11-04 13:48:2111/04/22 FAILED
  
 IS ANY WORK BEING PROPOSED UNDER THIS PERMIT? IF THIS
 IS JUST A SIMPLE CHANGE OF USEAGE/OCCUPANCY THIS IS
 DONE THROUGH OUR BUSINESS TAX FORMS, NOT OUR BUILDING
 PERMIT PROCESS.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431


Account Summary | Usage Policy | Privacy Policy