Plan Review Details - Permit 22100692
Plan Review Stops For Permit 22100692
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-06 Cont ID  
Sent By mpeterso Date 2022-12-06 Time 16:19 Rev Time 0.00
Received By mpeterso Date 2022-12-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 15:00 Rev Time 0.00
Received By medwards Date 2022-12-09 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-06 Cont ID  
Sent By mpeterso Date 2022-12-06 Time 16:20 Rev Time 0.00
Received By mpeterso Date 2022-11-22 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 08:13 Rev Time 0.00
Received By medwards Date 2022-10-27 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 14:59 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 14:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-28 Cont ID  
Sent By medwards Date 2022-11-28 Time 13:27 Rev Time 0.00
Received By medwards Date 2022-11-28 Time 13:27 Sent To  
Notes
2022-11-28 13:31:12SHEET M-2: OUTDOOR AIR CALCULATIONS FOR THIS WAREHOUSE
 SHOULD BE CALCULATED WITH 10 CFM/PERSON.
 17 PEOPLE X 10 = 170 + 8018 X .06 = 481
 170 + 481 = 651 CFM'S OUTDOOR AIR REQUIRED FOR THIS
 WAREHOUSE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 08:03 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 08:03 Sent To  
Notes
2022-11-08 08:11:29THE REQUIRED OUTDOOR AIR FOR THESE 2 AHU'S WILL NEED TO
 MEET THE REQUIREMENTS OF FMC 405.1 FOR AIR
 CONDITIONING.
 DEFINITION OF VENTILATION AIR- THAT PORTION OF SUPPLY
 AIR THAT COMES FROM THE OUTSIDE (OUTDOORS), PLUS ANY
 RECIRCULATED AIR THAT HAS BEEN TREATED TO MAINTAIN THE
 DESIRED QUALITY OF AIR WITHIN A
 DESIGNATED SPACE.
  
 FMC 405.1: AIR-CONDITIONING SYSTEMS THAT SUPPLY
 REQUIRED VENTILATION AIR SHALL BE PROVIDED WITH
 CONTROLS DESIGNED TO AUTOMATICALLY MAINTAIN THE
 REQUIRED OUTDOOR AIR SUPPLY RATE DURING OCCUPANCY.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 15:00 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By medwards Date 2022-11-28 Time 13:37 Rev Time 0.00
Received By medwards Date 2022-11-28 Time 13:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-11-08 Cont ID  
Sent By medwards Date 2022-11-08 Time 08:13 Rev Time 0.00
Received By medwards Date 2022-11-08 Time 08:13 Sent To  
Notes
***NONE***