Plan Review Stops For Permit 22100633
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-25 Cont ID  
Sent By pvalenti Date 2023-01-25 Time 16:30 Rev Time 0.00
Received By pvalenti Date 2023-01-25 Time 16:26 Sent To  
Notes
2023-01-25 16:30:52PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
  
 1.) BUILDING REVIEW APPROVAL PENDING APPROVAL OF
 SIGNATURE REVIEW.
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PLAN SHEET TITLED, "5K-24K 4 POLE BOAT LIFT
 ENGINEERING SHEET" DOES NOT HAVE A 3RD PARTY VERIFIABLE
 DIGITAL SIGNATURE.
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
 2.) FBC B 107.2.1, PROVIDE APPROVAL/AUTHORIZATION FROM
 THE U.S. ARMY CORE OF ENGINEERS.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-07-28 Cont ID  
Sent By mpeterso Date 2023-07-28 Time 15:08 Rev Time 0.00
Received By mpeterso Date 2023-07-28 Time 15:07 Sent To  
Notes
2023-07-28 15:10:18ELECTRIC REVIEW FAILED
  
 1) PROVIDE AN ELECTRICAL DIAGRAM THAT INCLUDES
 OVERCURRENT PROTECTION SIZES, REFERENCES TO LOCATION OF
 CONDUITS , JUNCTION BOXES, DATUM PLANE HEIGHTS,
 SEAWALLS AND PILINGS, DERATING OF CONDUCTORS, SIGNS,
 AND AND ALL OTHER DETAILS INCLUDING BUT NOT LIMITED TO
 GFP FOR FEEDERS AND OTHER APPLICABLE REQUIREMENTS IN
 ACCORDANCE WITH NEC ARTICLE 555. DRAWING IS VERY
 UNCLEAR. FBC 107.2 , NEC 555
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By mpeterso Date 2023-01-10 Time 13:04 Rev Time 0.00
Received By mpeterso Date 2023-01-10 Time 13:03 Sent To  
Notes
2023-01-10 13:05:15ELECTRIC REVIEW FAILED
 1) PROVIDE AN ELECTRICAL PLAN FOR REVIEW. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-21 Cont ID  
Sent By clfranci Date 2022-11-21 Time   Rev Time 0.00
Received By clfranci Date 2022-11-21 Time   Sent To  
Notes
2022-11-21 14:25:57THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PLEASE ENSURE THAT DURING CONSTRUCTION THERE IS FREE
 EMERGENCY EGRESS ON PIER.
  
 2) PLEASE ENSURE THAT DURING CONSTRUCTION THERE IS FREE
 ACCESS FOR EMERGENCY PERSONEL.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-07-21 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-25 Cont ID  
Sent By pvalenti Date 2023-01-25 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2022-11-17 Time 09:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-25 Cont ID  
Sent By pvalenti Date 2023-01-25 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2023-01-25 Time 16:26 Sent To  
Notes
2023-01-25 16:33:22PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 THE SUBMITTED ENGINEER SHEET, DIGITAL FILE LABELED
 "PRODUCT SPECS-BOAT LIFT", DOES NOT HAVE A THIRD PARTY
 VERIFIABLE ENGINEER'S SIGNATURE.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By asangele Date 2022-12-13 Time 14:49 Rev Time 0.00
Received By asangele Date 2022-12-13 Time 14:49 Sent To  
Notes
2022-12-13 15:28:46FAILED
 12/13/2022
  
 PLEASE PROVIDE A SURVEY THAT IS IN THIRDS WITH LABELED
 SETBACKS IN ADDITION ALSO PLEASE LABEL THE DIMENSIONS
 WHERE THE BOATLIFT WILL BE LOCATED.
 ARTICLE X. SECTION 94-313
 LOCATION AND SETBACKS. DOCKS, "TEES," DOLPHINS,
 PILINGS, BOATLIFTS, AND OTHER MOORING-RELATED
 FACILITIES SHALL BE CONSTRUCTED WITHIN THE MIDDLE
 ONE-THIRD OF THE LOT ON WHICH A DOCK IS CONSTRUCTED, AS
 EXTENDED INTO THE WATERWAY. NO WATERCRAFT SHALL BE
 DOCKED OR ANCHORED IN A POSITION, OR BE OF SUCH LENGTH,
 THAT CAUSES IT TO EXTEND BEYOND THE SIDE SETBACK LINES
 REQUIRED FOR PRINCIPAL STRUCTURES ON SUCH PROPERTY, AS
 EXTENDED INTO THE WATERWAY.
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  