Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-11-14 Cont ID  
Sent By medwards Date 2022-11-14 Time 07:05 Rev Time 0.00
Received By medwards Date 2022-11-14 Time 07:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 13:37 Rev Time 0.00
Received By medwards Date 2022-11-03 Time 13:37 Sent To  
Notes
2022-11-03 13:37:532ND REVIEW FMC
 PERMIT: 22100618
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CALCULATIONS SUBMITTED ARE
 INCOMPLETE AS I DO NOT SEE THE TOTAL OCCUPANTS FOR THE
 SPACES. IT APPEARS THAT THIS IS THE MISSING PART OF THE
 PUZZLE. IF THE CALCULATIONS ARE USING THE ARCHITECT???S
 EGRESS OCCUPANT NUMBERS INSTEAD OF FMC TABLE 403.3.1.1
 TO FIND THE OCCUPANT LOAD FOR EACH SPACE THE OUTDOOR
 AIR NUMBERS WOULD BE LOW. THIS IS THE CASE IN THE
 SUBMITTED OUTDOOR AIR CALCULATIONS. PLEASE SEE BELOW
 THE REQUIRED MINIMUM OUTDOOR AIR FOR EACH SPACE,
 ACCORDING TO THE USE OF SPACE GIVEN AND THE SQUARE
 FOOTAGE OF EACH SPACE. PLEASE CORRECT THE OUTDOOR AIR
 TABLE SUBMITTED.
  
 THE CONFERENCE ROOM HAS A SQ. FOOTAGE OF 341. THIS AREA
 WOULD HAVE AN OCCUPANT COUNT OF 18, THIS WOULD REQUIRE
 111 CFM???S OF OUTDOOR AIR.
  
 THE OFFICE SPACE HAS A SQ. FOOTAGE OF 1455. THIS AREA
 WOULD HAVE AN OCCUPANT COUNT OF 8, THIS WOULD REQUIRE
 127 CFM???S OF OUTDOOR AIR.
  
 THE RECEPTION AREA HAS A SQ. FOOTAGE OF 304. THIS AREA
 WOULD HAVE AN OCCUPANT COUNT OF 10, THIS WOULD REQUIRE
 68 CFM???S OF OUTDOOR AIR.
  
 THE CORRIDOR IS REQUIRED TO HAVE 19 CFM???S OF OUTDOOR
 AIR AND THAT CALCULATION IS CORRECT.
  
 THE STORAGE ROOM HAS A SQ. FOOTAGE OF 136. THIS AREA
 OUTDOOR AIRFLOW RATE IN THE BREATHING ZONE SHOULD BE
 CALCULATED USING .12 AND NOT .06. THIS AREA WOULD BE
 REQUIRED TO HAVE 16CFM???S OF OUTDOOR AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By medwards Date 2022-10-25 Time 13:16 Rev Time 0.00
Received By pvalenti Date 2022-10-25 Time 13:16 Sent To  
Notes
2022-10-25 13:34:24PETER E VALENTI
 BUILDING/MECHANICAL PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW DENIED:
  
 FBC M 403.3.1.1, THE OUTSIDE AIR CALCULATION TABLE ON
 THE REVISED PLAN SHEET M6.1 HAS NOT BEEN UPDATED FOR
 THE CONFERENCE ROOM. THE PROVIDED OUTSIDE AIR IS STILL
 LESS THAN THE REQUIRED OUTSIDE AIR.
 PLEASE CORRECT THE OUTSIDE AIR CALCULATION TABLE AND
 RE-SUBMIT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-14 Cont ID  
Sent By medwards Date 2022-11-14 Time 07:05 Rev Time 0.00
Received By medwards Date 2022-11-14 Time 07:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 13:38 Rev Time 0.00
Received By medwards Date 2022-11-03 Time 13:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-25 Cont ID  
Sent By pvalenti Date 2022-10-25 Time 13:35 Rev Time 0.00
Received By pvalenti Date 2022-10-25 Time 13:35 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved