Plan Review Details - Permit 22100457
Plan Review Stops For Permit 22100457
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 09:08 Rev Time 0.00
Received By shill Date 2023-01-25 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-15 Cont ID  
Sent By shill Date 2022-12-15 Time 17:39 Rev Time 0.00
Received By shill Date 2022-12-15 Time 17:39 Sent To  
Notes
2022-12-15 17:44:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 THE FLAME SPREAD TEST WAS SUBMITTED FOR TILE. PROVIDE
 THE FLAME SPREAD TEST FOR LAMINATE. FLAME SPREAD FOR
 TILE IS ALWAYS ZERO.
  
 2. SUPERSIM 90 SPEC SHEET WAS SUBMITTED. PROVIDE THE
 FLAME SPREAD TEST REQUIRED, FBC B 603.1.
  
 IF YOU ARE UNABLE TO PROVIDE THE FLAME SPREAD TEST FOR
 SUPERSIM 90 (LAMINATE FLOORING), NOTE THAT WE DO HAVE
 PROFLEX LV200 TEST REPORTS ON FILE. IF YOU WISH TO USE
 THIS AS AN ALTERNATE, REVISE PLAN AND RESUBMIT WITH A
 RESUBMITTAL LETTER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 19:23 Rev Time 0.00
Received By shill Date 2022-11-16 Time 19:23 Sent To  
Notes
2022-11-16 19:29:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, SCOPE NOT CLEAR. APPLICATION PROPOSES
 LAMINATE AND TILE. FLOOR PLAN APPEARS TO PROPOSE ONLY
 HARDWOOD/LAMINATE. REVISE EITHER THE APPLICATION OR THE
 FLOOR PLAN.
  
 2. SUPERSIM 90 SPEC SHEET WAS SUBMITTED. PROVIDE THE
 FLAME SPREAD TEST REQUIRED, FBC B 603.1.
  
 IF YOU ARE UNABLE TO PROVIDE THE FLAME SPREAD TEST FOR
 SUPERSIM 90 (LAMINATE FLOORING), NOTE THAT WE DO HAVE
 PROFLEX LV200 TEST REPORTS ON FILE. IF YOU WISH TO USE
 THIS AS AN ALTERNATE, REVISE PLAN AND RESUBMIT WITH A
 RESUBMITTAL LETTER.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-05 Cont ID  
Sent By pleduc Date 2023-01-05 Time   Rev Time 0.00
Received By pleduc Date 2023-01-05 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-30 Cont ID  
Sent By pleduc Date 2022-11-30 Time   Rev Time 0.00
Received By pleduc Date 2022-11-30 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By pleduc Date 2022-10-17 Time   Rev Time 0.00
Received By pleduc Date 2022-10-17 Time 14:16 Sent To  
Notes
2022-10-17 14:22:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED LAMINATE FLOORING.
  
 LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD BUT
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-25 Cont ID  
Sent By shill Date 2023-01-25 Time 09:08 Rev Time 0.00
Received By shill Date 2023-01-04 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-15 Cont ID  
Sent By shill Date 2022-12-15 Time 17:44 Rev Time 0.00
Received By shill Date 2022-11-29 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 19:30 Rev Time 0.00
Received By shill Date 2022-10-13 Time 07:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-11-16 Cont ID  
Sent By shill Date 2022-11-16 Time 19:30 Rev Time 0.00
Received By shill Date 2022-11-16 Time 19:30 Sent To  
Notes
***NONE***