Plan Review Details - Permit 22100457
Plan Review Stops For Permit 22100457 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-01-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2023-01-25 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2023-01-25 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-12-15 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-12-15 |
Time |
17:39 |
Sent To |
|
|
Notes |
2022-12-15 17:44:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | THE FLAME SPREAD TEST WAS SUBMITTED FOR TILE. PROVIDE | | THE FLAME SPREAD TEST FOR LAMINATE. FLAME SPREAD FOR | | TILE IS ALWAYS ZERO. | | | | 2. SUPERSIM 90 SPEC SHEET WAS SUBMITTED. PROVIDE THE | | FLAME SPREAD TEST REQUIRED, FBC B 603.1. | | | | IF YOU ARE UNABLE TO PROVIDE THE FLAME SPREAD TEST FOR | | SUPERSIM 90 (LAMINATE FLOORING), NOTE THAT WE DO HAVE | | PROFLEX LV200 TEST REPORTS ON FILE. IF YOU WISH TO USE | | THIS AS AN ALTERNATE, REVISE PLAN AND RESUBMIT WITH A | | RESUBMITTAL LETTER. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-11-16 |
Time |
19:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-11-16 |
Time |
19:23 |
Sent To |
|
|
Notes |
2022-11-16 19:29:59 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 107, SCOPE NOT CLEAR. APPLICATION PROPOSES | | LAMINATE AND TILE. FLOOR PLAN APPEARS TO PROPOSE ONLY | | HARDWOOD/LAMINATE. REVISE EITHER THE APPLICATION OR THE | | FLOOR PLAN. | | | | 2. SUPERSIM 90 SPEC SHEET WAS SUBMITTED. PROVIDE THE | | FLAME SPREAD TEST REQUIRED, FBC B 603.1. | | | | IF YOU ARE UNABLE TO PROVIDE THE FLAME SPREAD TEST FOR | | SUPERSIM 90 (LAMINATE FLOORING), NOTE THAT WE DO HAVE | | PROFLEX LV200 TEST REPORTS ON FILE. IF YOU WISH TO USE | | THIS AS AN ALTERNATE, REVISE PLAN AND RESUBMIT WITH A | | RESUBMITTAL LETTER. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-01-05 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-01-05 |
Time |
14:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-11-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-11-30 |
Time |
11:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2022-10-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2022-10-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2022-10-17 |
Time |
14:16 |
Sent To |
|
|
Notes |
2022-10-17 14:22:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE | | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT | | NAME FOR THE ACTUAL PROPOSED LAMINATE FLOORING. | | | | LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD BUT | | NOT ALL ARE TESTED AND MEETING LISTED AND NFPA | | STANDARDS. | | | | PER NFPA 101, CH 30 | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | ACCORDANCE WITH | | SECTION 10.2. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL | | FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE | | PROPOSED FINISHED | | LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-01-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2023-01-25 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2023-01-04 |
Time |
13:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-12-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-12-15 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-11-29 |
Time |
09:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2022-11-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-11-16 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-10-13 |
Time |
07:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2022-11-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-11-16 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-11-16 |
Time |
19:30 |
Sent To |
|
|
Notes |
|
|
|