Plan Review Details - Permit 22100340
Plan Review Stops For Permit 22100340
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 11:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By rmcphers Date 2022-12-21 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2022-12-21 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By rmcphers Date 2022-11-01 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2022-11-01 Time 16:34 Sent To  
Notes
2022-11-01 16:37:53REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ADDED BAR AREA - (ROOM (N128) - PLEASE SHOW THE
 ACCESSIBLE BAR SEATING (COUNTER HEIGHT, KNEE AND TOE
 CLEARANCE ETC.) - FBC FHA REQUIREMENT 2
  
 2) DRAWING S-2.1.12 NEEDS TO BE
 DIGITALLY/ELECTRONICALLY SIGNED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By jleahy Date 2023-03-20 Time 12:02 Rev Time 0.00
Received By jleahy Date 2023-03-20 Time 10:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-26 Cont ID  
Sent By jleahy Date 2022-10-26 Time 09:03 Rev Time 0.00
Received By jleahy Date 2022-10-26 Time 08:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-03-13 Cont ID  
Sent By pleduc Date 2023-03-13 Time   Rev Time 0.00
Received By pleduc Date 2023-03-13 Time 12:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By pleduc Date 2022-12-21 Time   Rev Time 0.00
Received By pleduc Date 2022-12-21 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By pleduc Date 2022-10-24 Time   Rev Time 0.00
Received By pleduc Date 2022-10-20 Time 16:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2023-03-15 Cont ID  
Sent By ccole Date 2023-03-15 Time 12:19 Rev Time 0.00
Received By ccole Date 2023-03-14 Time 15:43 Sent To  
Notes
2023-03-15 12:19:29THE ARCHITECT HAS REQUESTED GAS INSTALLATIONS TO BE
 UNDER A SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:24 Rev Time 0.00
Received By ccole Date 2023-01-03 Time 13:01 Sent To  
Notes
2023-01-04 16:24:21THE ARCHITECT HAS REQUESTED GAS INSTALLATIONS TO BE
 UNDER A SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By ccole Date 2022-11-01 Time 16:32 Rev Time 0.00
Received By ccole Date 2022-10-31 Time 16:01 Sent To  
Notes
2022-11-01 16:33:131ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100340
 11/1/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1.1.0 & P-2.1.1. A GAS METER IS SHOWN ON
 THE PLANS HOWEVER NO GAS PLANS HAVE BEEN SUBMITTED.
 PLEASE PROVIDE GAS PLANS IN COMPLIANCE WITH SEC.
 107.3.5.1.5 WPB. THE SUBMITTAL SHALL INCLUDE A RISER
 DIAGRAM, PIPING LAYOUT PLANS, EQUIPMENT AND APPLIANCE
 SPECIFICATIONS, VENTING AND COMBUSTION AIR DIAGRAMS AND
 CALCULATIONS.
  
 PLEASE NOTE THAT GAS FOR THE BUILDING CAN BE UNDER A
 SEPARATE PERMIT IF REQUESTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-30 Cont ID  
Sent By aoliver Date 2023-03-30 Time 08:30 Rev Time 0.00
Received By aoliver Date 2023-03-10 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-24 Cont ID  
Sent By lmarchan Date 2023-01-24 Time 11:20 Rev Time 0.00
Received By lmarchan Date 2022-12-20 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2022-10-19 Time 13:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-03-16 Cont ID  
Sent By medwards Date 2023-03-16 Time 09:31 Rev Time 0.00
Received By medwards Date 2023-03-16 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 11:41 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By medwards Date 2022-11-07 Time 16:54 Rev Time 0.00
Received By medwards Date 2022-11-07 Time 16:54 Sent To  
Notes
2022-11-07 16:54:341ST REVIEW FMC
 PERMIT: 22100340
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.1.1, SHEET M-3.1.1: PROVIDE THE OUTDOOR
 AIR CALCULATIONS FOR THE CHANGED CFM???S IN THE CHANGED
 AREAS. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-03-15 Cont ID  
Sent By ccole Date 2023-03-15 Time 13:34 Rev Time 0.00
Received By ccole Date 2023-03-14 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:13 Rev Time 0.00
Received By ccole Date 2023-01-03 Time 13:01 Sent To  
Notes
2023-01-04 16:23:272ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100340
 1/4/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION.
 CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW
 COMMENTS
  
 1) 2ND REQUEST. SHEETS A-1.1.1 & P-2.1.1: PLUMBING
 FIXTURE CALCULATIONS NOT PROVIDED- TABLE 403.1 & SEC.
 403.1.1. PLEASE PROVIDE A SCHEDULE THAT SHOWS THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE A & B
 OCCUPANCIES AND OCCUPANT LOADS SHOWN ON THE PLAN. IT
 APPEARS THE SINGLE-OCCUPANT TOILET ROOM SHOWN ON THE
 PLAN WITH ONE WATER CLOSET AND ONE LAVATORY MAY MEET
 THE REQUIRMENT HOWEVER THE REQUIRED DRINKING FOUNTAINS
 AND SERVICE SINK ARE NOT ACCOINTED FOR OR SHOWN ON THE
 PLANS.
  
 2) 2ND REQUEST. AT A MINIMUM, PERMIT APPLICATIONS FOR
 THE POTABLE WATER BACKFLOW PREVENTER AND GREASE
 INTERCEPTOR ARE S REQUIRED FOR THE PLUMBING PLAN REVIEW
 TO BE APPROVED.
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 POTABLE WATER BACKFLOW PREVENTER, GREASE INTERCEPTOR,
 IRRIGATION, IRRIGATION BACKFLOW, AND POOL. IF REQUESTED
 GAS CAN ALSO BE UNDER A SEPARATE PERMIT. DUE TO A
 CHANGE IN PROCESS, THE BACKFLOW AND GREASE INTERCEPTOR
 PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL
 OF THE PLUMBING REVISION. YOU CAN SUBMIT AN APPLICATION
 TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
 P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THE POTABLE WATER BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW.
 PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST
 FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB.
 DEPARTMENT, (561) 822-2062 OR [email protected].
  
 5) 2ND REQUEST. P-2.1.1 & P-6.2.1. THE DETAILS DO AND
 NOTES DO NOT INDICATE THE ALARMS WILL BE PROVIDED: THE
 ELEVATOR AND TRASH ROOM SUMP PUMPS SHALL BE EQUIPPED
 WITH OIL ALARMS OR THE SUMP DISCHARGE SHALL BE CONVEYED
 TO AN OIL SEPARATOR(S)- SEC. 1003.4 FBC P.
  
 6) 2ND REQUEST. THE DETAIL ON P-6.1.1 SHOWS A 2-INCH
 CONDENSATE PIPE DISCHARGING ONTO GRADE 8-INCHES AWAY
 FROM THE BUILDING. THIS IS NOT AN APPROVED PLACE OF
 DISPOSAL PER SEC. 314.2.1. PLEASE PROVIDE PIPE
 CONNECTION TO STORM DRAIN OR DISCHARGE TO DRYWELL.
 P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE
 CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF
 DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC.
 314.2.1 FBC P.
  
  
 14) 2ND REQUEST TO SHOW LOCATIONS OF STORM DRAIN
 CLEANOUTS. P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6:
 PROVIDE CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE
 THEY EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC.
 1101.8 FBC P.
  
 18) 2ND REQUEST. THE WATER HEATER DETAILS ON P-6.1.2
 ARE THE APARTMENT WATER HEATERS WHICH ARE APPROVED.
 PROVIDE THE GROUND FLOOR STORAGE AND TANKLESS WATER
 HEATER DETAILS P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE
 EQUIPMENT SCHEDULES AND INSTALLATION DETAILS FOR THE
 GROUND FLOOR WATER HEATERS SHOWN ON THE ISO- SEC.
 107.2.1 WPB. THE DETAIL SHOULD SHOW THE MEANS OF
 LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER
 PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC
 P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A
 BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE
 MAKER- SEC. 608.3 FBC P.
  
 19) 2ND REQUEST. P-5.1.7 & P-6.1.2: SHOW THE MEANS OF
 PROVIDING TEMPERED WATER DELIVERY FROM THE GROUND FLOOR
 LAVATORY IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE
 THAT TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL
 BE ASSE 1070 LISTED- SEC. 607.1.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By ccole Date 2022-11-01 Time 16:36 Rev Time 0.00
Received By ccole Date 2022-10-31 Time 11:30 Sent To  
Notes
2022-11-01 16:38:171ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100340
 11/1/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW
 COMMENTS
  
 1) A-1.1.1 & P-2.1.1: PLUMBING FIXTURE CALCULATIONS NOT
 PROVIDED- TABLE 403.1 & SEC. 403.1.1. PLEASE PROVIDE A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES FOR THE OCCUPANCIES. IT IS ACKNOWLEDGED THAT
 THE OCCUPANT LOADS OF THE RESIDENTIAL (APARTMENTS) AND
 THE S-2 PARKING GARAGE CAN BE EXCLUDED FROM THE MIXED
 OCCUPANCY CALCULATION HOWEVER THAT RESULTS WITH AN
 OCCUPANT LOAD OF 124 TO PROVIDE PLUMBING FIXTURES FOR.
 THE NUMBER CAN BE REDUCED FURTHER DOWN TO 68 IF THE
 OCCUPANTS OF THE M FUTURE RETAIL ARE REMOVED HOWEVER
 THAT WILL HAVE TO BE CLARIFIED ON THE PLAN BECAUSE NO
 FUTURE SANITARY LINE IS SHOWN ON THE PLUMBING PLANS.
 PLEASE NOTE THERE IS ONLY ONE SINGLE-OCCUPANT TOILET
 ROOM SHOWN ON THE PLAN WITH ONE WATER CLOSET AND ONE
 LAVATORY WHICH IS DEFICIENT FOR THE MINIMUM 68
 OCCUPANTS OR THE MAXIMUM 124 OCCUPANTS. ALSO MISSING
 ARE THE REQUIRED DRINKING FOUNTAINS AND SERVICE SINK-
 TABLE 403.1.
  
 2) P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THE POTABLE WATER BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW.
 PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST
 FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB. PLEASE
 NOTE THAT A GAS METER IS SHOWN ON P-1.1.0 HOWEVER NO
 GAS PLANS HAVE BEEN PROVIDED. WILL GAS ALSO BE UNDER
 SEPARATE PERMIT?
  
 3) P-2.1.1, P-5.1.6: THE WASTEWATER FROM THE FOUNTAIN
 IS DRAINING INTO THE SUMP PIT AND THEN DISCHARGING INTO
 THE STORM SYSTEM. PLEASE NOTE CHLORINATED POOL OR
 FOUNTAIN WASTE WATER SHALL NOT DRAIN INTO THE STORM
 SYSTEM UNLESS IT HAS BEEN DECHLORINATED PER SEC. 90-205
 (1) WPB CODE OF ORDINANCES. PLEASE REVIEW THE FOLLOWING
 INFORMATION CONCERNING THE FOUNTAIN WASTEWATER.
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 ??? THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 ??? NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 ??? WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 ??? DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 ??? FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 ??? FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) P-2.1.1 & P-6.2.2: PLEASE PROVIDE AN EQUIPMENT
 SCHEDULE FOR THE COURTYARD SUMP PUMP LISTING MAKE AND
 MODEL AND ELECTRICAL DATA- SEC. 712.3 FBC P.
  
 5) P-2.1.1 & P-6.2.1: THE ELEVATOR AND TRASH ROOM SUMP
 PUMPS SHALL BE EQUIPPED WITH OIL ALARMS OR THE SUMP
 DISCHARGE SHALL BE CONVEYED TO AN OIL SEPARATOR(S)-
 SEC. 1003.4 FBC P.
  
 6) P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE
 CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF
 DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC.
 314.2.1 FBC P.
  
 7) P-2.1.1: PROVIDE A NOTE TO SHOW THE LOCATIONS OF THE
 WATER HEATER DRAIN PAN LINE TERMINATION LOCATIONS- SEC.
 504.7.2 FBC P.
  
 8) P-6.1.2: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 LINE SUPPLY LINE TO THE TRASH CHUTE- SEC. 608.3 FBC P.
 PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR THE DEVICE ON
 SHEET P-6.2.2.
  
 9) P-5.1.1, P-6.2.2: PROVIDE A BACKFLOW PREVENTER FOR
 THE WATER LINE SUPPLY LINE TO THE TRASH CHUTE- SEC.
 608.3 FBC P. PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR
 THE DEVICE ON SHEET P-6.2.2.
  
 10) P-5.1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE SPEARS PERFORATED CAPS. THE CAPS WILL BE INSTALLED
 IN PLENUM ENCLOSURES AND SHALL BE NONCOMBUSTIBLE OR
 SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E84 OR UL 723- SEC. 602.2.1 FBC M. IT APPEARS THE CAPS
 WILL BE VENTING THE TRAPS WHICH IS PROHIBITED IN PLENUM
 ENCLOSURES- SECS. 903.5, 905.1 & 918.8.
  
 11) P-5.1.4: IT APPEARS THAT THERE ARE MISSING VENT
 STACKS THAT ARE REQUIRED TO BE CONNECTED AT THE BASE OF
 THE SOIL STACKS (#2, 5, 6, 9, & 11). THE VENT STACK
 POINTS OF CONNECTION SHALL BE DOWNSTREAM OF THE SOIL
 STACK BASES WITHIN A DISTANCE OF 10 TIMES THE DIAMETER
 OF THE SOIL STACK. PLEASE NOTE P-5.1.4 SHOWS STACK #12
 WHICH IS NOT SHOWN ON THE RISER DRAWINGS- P-5.1.2 &
 P-5.1.3.
  
 12) P-5.1.4: THE DRAWING SHOWS MANY STACKS COMBINED
 TOGETHER BEFORE CONNECTING TO THE BUILDING DRAIN SUCH
 AS (1&2), (4&5), (1&10), (11,3,4). WASTE AND SOIL
 STACKS CANNOT BE COMBINED TOGETHER BECAUSE EACH
 REQUIRES A SEPARATE VENT, AND EACH STACK SHALL CONNECT
 SEPARATELY TO THE BUILDING DRAIN- SEC. 913.2 FBC P.
  
 13) P-2.1.1 & P-5.1.4: THE REVISED PLANS SHOW A
 BAR/CAFE WITH THE DRAINAGE FROM THE SINK AND DISHWASHER
 DISCHARGING TO THE SANITARY WHICH MAY BE PROHIBITED IF
 THE DRAINAGE IS GREASE LADEN- SEC. 1003.3.1 FBC P. MORE
 INFORMATION WILL BE REQUIRED CONCERNING THE FOOD AND
 DRINK OPERATIONS IN THE BAR/CAFE. A) DRAINAGE FROM THE
 ICEMAKER IN THE BAR DISCHARGE TO THE SANITARY.
  
 14) P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6: PROVIDE
 CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE THEY
 EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC.
 1101.8 FBC P.
  
 15) P-2.1.6, P-5.1.5 & P-5.1.6: ROOF DRAINAGE VERTICAL
 AND HORIZONTAL DRAIN PIPE SIZES ARE DETERMINED BY GPM
 FLOW. PLEASE CONVERT THE SQUARE FOOTAGE TOTALS ON THE
 DRAWINGS TO GPM TO VERIFY VERTICAL LEADERS AND
 HORIZONTAL DRAINS ARE SIZED IN COMPLIANCE WITH TABLES
 1106.2 & 1006.3 FBC P.
  
 A) P-2.1.6, P-2.1.4G: PLEASE PROVIDE ADDITIONAL ROOF
 DRAINAGE INFORMATION FOR THE MAIN BUILDING AND LEVEL 5
 TERRACE OF THE GARAGE INCLUDING RAINFALL RATE, SQUARE
 FOOTAGE BREAKDOWN THAT INCLUDES THE PARAPET WALLS, AND
 AN EMERGENCY SCUPPER DETAIL- SECS. 1106.1, 1106.4, AND
 1106.5 FBC P.
  
 B) P-2.1.4G: PLEASE DETAIL EMERGENCY (OVERFLOW)
 DRAINAGE FOR THE TERRACE AND DISPOSAL LOCATION- SEC.
 1106.5 FBC P.
  
 16) P-5.1.1, P-5.1.7: SHOW THE LOCATIONS OF FULL-OPEN
 VALVES AT THE BASES OF THE WATER RISERS. THE NOTE ON
 P-5.1.1 REFERENCING THE WATER HEATER DETAIL FOR
 LOCATION DOES NOT APPEAR RELEVANT TO THE CODE
 REQUIREMENT- SEC. 606.1(4) FBC P.
  
 17) P-2.1.1: TO HELP EXPEDITE THE REVIEW PLEASE NOTE &
 LABEL THE WATER SERVICE ENTRANCE INTO THE BUILDING AND
 LABEL THE LOCATION OF THE DOMESTIC BOOSTER PUMP- SEC.
 107.2.1 WPB.
  
 18) P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE EQUIPMENT
 SCHEDULES AND INSTALLATION DETAILS FOR THE GROUND FLOOR
 WATER HEATERS SHOWN ON THE ISO- SEC. 107.2.1 WPB.
 IDENTIFY THE FIXTURE BEING SUPPLIED HOT WATER FROM THE
 TANKLESS WATER HEATER SHOWN IN THE AREA OF THE TRASH
 ROOM AND BOOSTER. THE DETAIL SHOULD SHOW THE MEANS OF
 LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER
 PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC
 P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A
 BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE
 MAKER- SEC. 608.3 FBC P.
  
 19) P-5.1.7 & P-6.1.2: SHOW THE MEANS OF PROVIDING
 TEMPERED WATER DELIVERY FROM THE GROUND FLOOR LAVATORY
 IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE THAT
 TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL BE
 ASSE 1070 LISTED- SEC. 607.1.2.
  
 20) P-6.1.2: PLEASE SEE NOTE #8 AT THE WATER HEATER
 DETAILS AND PROVIDE THE HW PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC ENERGY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:25 Rev Time 0.00
Received By ccole Date 2023-01-04 Time 16:25 Sent To  
Notes
2023-01-04 16:26:29A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 INSTALLATION OF THE GREASE INTERCEPTOR.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By ccole Date 2023-01-04 Time 16:26 Rev Time 0.00
Received By ccole Date 2023-01-04 Time 16:26 Sent To  
Notes
2023-01-04 16:27:20A SEPARATE PERMIT AND PLAN SUBMITTAL ARE REQUIRED FOR
 INSTALLATION OF THE IRRIGATION SYSTEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 11:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By rmcphers Date 2022-12-21 Time 12:56 Rev Time 0.00
Received By rmcphers Date 2022-12-21 Time 12:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-02 Cont ID  
Sent By rmcphers Date 2022-11-02 Time 07:58 Rev Time 0.00
Received By rmcphers Date 2022-11-02 Time 07:58 Sent To  
Notes
2022-11-02 08:00:17SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S-2.1.12 DOES NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-29 Cont ID  
Sent By cibaven Date 2023-03-29 Time 16:42 Rev Time 0.00
Received By cibaven Date 2023-03-29 Time 16:42 Sent To  
Notes
2023-03-29 16:46:31PROVISO: APPROVAL IS ONLY FOR WORK ON THE NORTH
 BUILDING LOCATED AT 840 N DIXIE HWY. SHEETS SHOWING
 WORK ON THE SOUTH BUILDING ARE NOT PART OF THIS
 APPROVAL.

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-24 Cont ID  
Sent By cibaven Date 2023-01-24 Time 11:12 Rev Time 0.00
Received By cibaven Date 2023-01-24 Time 11:12 Sent To  
Notes
2023-01-24 11:12:45ZONING AND PLANNING
 PROJECT: CIELO 840 N DIXIE HWY
 PERMIT NO. 22100340
 DATE: JANUARY 24, 2023
 CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT
 561-822-1402 OR VIA [email protected].
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 AS THE DESIGN CHANGED FOR THE PRIVATE OPEN SPACE
 COURTYARD LOCATED IN THE NORTH BUILDING, AND OTHER
 MINOR CHANGES ALTERED OTHER OPEN SPACE CONFIGURATIONS
 IN THE PROJECT, PLEASE SUBMIT THE FOLLOWING REVISED
 OPEN SPACE DIAGRAM SHEETS INDICATING WITH CLOUDS
 CHANGES FROM WHAT WAS APPROVED ON THE MASTER PERMIT NO.
 21100764:
 - 009 SHEET A-0.3
 - 050 SHEET L1-6-01
 - 051 SHEET L1-6-02
  
 SHEET A-2.1.1 NORTH BUILDING GROUND LEVEL
 THANK YOU FOR CLARIFYING THE CHANGE ON THE GROUND FLOOR
 STOREFRONT DOOR THAT WAS REPLACED WITH A WINDOW TO
 ACCOMMODATE MEDIATION LOUNGE.
 PLEASE CLARIFY IF CLOUD HIGHLIGHTING THE CORNER ON N
 DIXIE HWY AND EUCALYPTUS STREET AFFECTED ANY ELEVATIONS
 OR SITE PLAN SHEETS.
  
 SHEET A-3.1.1
 WEST ELEVATION
 - PLEASE CLARIFY IF WINDOW???S MULLIONS BETWEEN GRIDS 9
 & 11 ARE DIFFERENT FROM THE ELEVATION APPROVED IN
 MASTER PERMIT 21100764.
  
 NORTH ELEVATION
 - PLEASE CLARIFY IF WINDOW???S MULLION AT GRID N.M. ON
 THE 8TH FLOOR IS DIFFERENT FROM THE ELEVATION APPROVED
 IN MASTER PERMIT 21100764.
  
 SHEET A-3.1.3 & A-3.1.4
 - REGARDING THE PICKLEBALL ENCLOSURE, PLEASE CLARIFY
 ANY CHANGES ON WHICH SHEETS COMPARED TO SHEETS
 SUBMITTED WITH MASTER PERMIT 21100764.
  
 NOTE, SHEET A-3.1.2 WAS NOT SUBMITTED, IF ANY CHANGES
 HAVE BEEN MADE, PLEASE SUBMIT SHEET WITH NOTING CHANGES
 WITH CLOUDS.
  
 OTHER COMMENTS:
 HAS ANY OF THE MATERIALS LISTED IN THE ELEVATION LEGEND
 CHANGED FROM WHAT WAS ORIGINALLY APPROVED BY DAC?
 PLEASE CONFIRM THAT MECHANICAL EQUIPMENT ON ROOF IS
 SCREENED WITH A WALL OR SCREENING AS TALL AS THE
 EQUIPMENT.
  
 --END OF COMMENTS--

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-05 Cont ID  
Sent By ckimmerl Date 2022-12-05 Time 08:46 Rev Time 0.00
Received By aaponte Date 2022-12-05 Time 08:46 Sent To  
Notes
2022-12-05 08:48:04PLEASE PROVIDE A NARRATIVE INDIATING IF THERE ARE ANY
 CHANGES TO THE BUIDLING ELEVATION. SOME FLOOR PLANS
 INDICATE CHANGES TOT HE WINDOWS. LIST EACH SHEET AND
 CAHNGES INCLUDED.