Plan Review Details - Permit 22100217
Plan Review Stops For Permit 22100217
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2022-12-07 Time 13:09 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:53 Sent To  
Notes
2022-11-14 14:57:02PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-22 Cont ID  
Sent By rmcphers Date 2022-12-22 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2022-12-22 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2022-12-07 Time 13:05 Sent To  
Notes
2022-12-07 13:06:29BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE CEILING HEIGHT - FBC 1208.2
  
 2) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE DIMENSION
 FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3) ACCESSIBLE RESTROOM = THE CLEAR FLOOR SPACE FOR THE
 INSWING DOOR IS SHOWN ON TOP OF THE TOILET - SHOULD BE
 CLEAR FLOOR SPACE - FBC 603.2.3 (2) WHERE THE TOILET
 ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE AND A CLEAR
 FLOOR SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE
 ROOM BEYOND THE ARC OF THE DOOR SWING, DOORS SHALL BE
 PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE.
  
 4) ACCESSIBLE RESTROOM = PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE INSIDE THE RESTROOM TO EXIT THE
 RESTROOM - FBC 404.2.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 15:11 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:57 Sent To  
Notes
2022-11-14 15:09:53BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE CEILING HEIGHT - FBC 1208.2
  
 2) THE DOOR SCHEDULE SHOWS THE FRONT DOOR AND THE
 RESTROOM DOOR TO BE THE SAME - GLASS DOORS - PLEASE
 CLARIFY.
  
 3) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE DIMENSION
 FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) ACCESSIBLE RESTROOM = THE CLEAR FLOOR SPACE FOR THE
 INSWING DOOR IS SHOWN ON TOP OF THE TOILET - SHOULD BE
 CLEAR FLOOR SPACE - FBC 603.2.3 (2) WHERE THE TOILET
 ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE AND A CLEAR
 FLOOR SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE
 ROOM BEYOND THE ARC OF THE DOOR SWING, DOORS SHALL BE
 PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE.
  
 5) ACCESSIBLE RESTROOM = PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE TO EXIT THE RESTROOM - FBC
 404.2.4

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-25 Cont ID  
Sent By fgiaquin Date 2022-10-25 Time 22:34 Rev Time 0.00
Received By fgiaquin Date 2022-10-25 Time 20:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-28 Cont ID  
Sent By   Date 2022-12-28 Time   Rev Time  
Received By bdolan Date 2022-12-28 Time 12:54 Sent To  
Notes
2022-12-28 12:54:55PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND TESTING FOR FINAL APPROVAL.
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By   Date 2022-10-17 Time   Rev Time  
Received By bdolan Date 2022-10-17 Time 10:36 Sent To  
Notes
2022-10-17 10:37:26PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-29 Cont ID  
Sent By aoliver Date 2022-12-29 Time 09:09 Rev Time 0.00
Received By aoliver Date 2022-12-21 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2022-12-02 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-17 Cont ID  
Sent By aoliver Date 2022-11-17 Time 15:10 Rev Time 0.00
Received By aoliver Date 2022-10-11 Time 07:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 15:14 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-10-18 Cont ID  
Sent By rwbrown Date 2022-10-18 Time 12:35 Rev Time 0.00
Received By rwbrown Date 2022-10-18 Time 12:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-22 Cont ID  
Sent By rmcphers Date 2022-12-22 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2022-12-22 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By rmcphers Date 2022-12-07 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2022-12-07 Time 13:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 15:12 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By jroach Date 2022-11-17 Time 12:23 Rev Time 0.00
Received By jroach Date 2022-11-17 Time 12:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved