Plan Review Details - Permit 22100154
Plan Review Stops For Permit 22100154
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By cpuell Date 2023-02-28 Time 09:13 Rev Time 0.00
Received By cpuell Date 2023-02-28 Time 09:13 Sent To  
Notes
2023-02-28 09:13:51ADDRESS ISSUES BEING ADDRESSED UNDER PERMITS 22120608
 AND 23021456

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-14 Cont ID  
Sent By cpuell Date 2023-02-14 Time 16:20 Rev Time 0.00
Received By cpuell Date 2023-02-14 Time 16:20 Sent To  
Notes
2023-02-14 16:22:44CURRENTLY THERE ARE 5 ADDRESSES ASSOCIATED WITH THIS
 PARCEL (320 SUNSET RD 1 2 3 4 5) THE PLANS APPEAR TO BE
 FOR A 2 STORY SINGLE FAMILY HOME AND A CABANA, PLEASE
 HAVE OWNER CONTACT [email protected] TO DISCUSS
 ADDRESS ISSUES ON PARCEL OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 11:34 Rev Time 0.00
Received By rmcphers Date 2023-04-21 Time 11:34 Sent To  
Notes
2023-04-21 11:56:09NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 COMMENTS ARE FOR PLANS FOR 22100154 AND 23021456
  
 1) DRAWING A-4.0 THE CABANA SHOWS A FOAM INSULATION -
 PLEASE PROVIDE THE TEST REPORTS (ICC EVALUATION REPORT)
 FOR THE FOAM SPRAY INSULATION FBC R316.3 SURFACE
 BURNING CHARACTERISTICS.
 UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM
 PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN
 MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND
 SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
 2) THE PROVIDED ENERGY CALCS. (FORM R405) WILL NEED TO
 BE REVISED FOR THE CABANA - INSULATION AT THE CEILING
 AND ATTIC VENTING DOES NOT MATCH THE DRAWINGS FOR THE
 CABANA.
  
 3) DRAWINGS S3.01, A-5.0, A-4.0 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-04-07 Cont ID  
Sent By rmcphers Date 2023-04-07 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2023-04-07 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 12:45 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 11:55 Sent To  
Notes
2023-04-04 12:45:34NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF
 ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL
 AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT -
 THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL
 PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF
 TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
 FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED
  
 2) THE PROVIDED PRODUCT APPROVALS IN PROJECTDOX WILL
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD.
  
 3) DRAWING T-1.0 HAS A LIST OF DEFERRED SUBMITTALS -
 THE ABOVE ITEMS CAN BE DEFERRED. FBC WPB 107.3.4.1
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-20 Cont ID  
Sent By rmcphers Date 2023-03-20 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2023-03-20 Time 15:39 Sent To  
Notes
2023-03-20 15:50:22NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DOOR NUMBER 7 ENTRY TO THE BEDROOM WILL ALSO NEED TO
 MEET THE 29" CLEAR OPENING TO HAVE ACCESS TO THE
 BATHROOM INSIDE - FBC R320.1.1 ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND
 TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED
 WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE
 PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29-INCH (737 MM) CLEAR OPENING. FBC 404.2.3 CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 2) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF
 ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL
 AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT -
 THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL
 PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF
 TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
  
 3) MULTIPLE ROOF NOTES ON THE DRAWINGS SHOW SHINGLES
 FOR THE ROOF SYSTEM.
  
 4) THE 2ND FLOOR BEDROOM #2 - THE WINDOWS DO NOT SEEM
 TO MEET THE EMERGENCY ESCAPE REQUIREMENT OF 5.7 SQUARE
 FEET - FBC R310.2.1 MINIMUM OPENING AREA.
 EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET
 CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530
 M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS
 SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF
 THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE
 INSIDE.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-27 Cont ID  
Sent By rmcphers Date 2023-02-27 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2023-02-27 Time 10:57 Sent To  
Notes
2023-02-27 13:48:12NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE - FBC
 R807.1
  
 2) FBC R320.1.1 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES,
 TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT
 LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE
 PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE
 GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM)
 CLEAR OPENING. FBC 404.2.3 CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
  
 3) PLEASE SHOW THE STAIR HAND RAIL DETAILS - FBC
 R311.7.8
  
 4) PLEASE SHOW THE GUARD RAIL DETAILS - FBC R312.1
  
 5) PRODUCT APPROVAL PROVIDED FOR THE ROOF TILE - PLEASE
 CIRCLE THE ROOF TILE ATTACHMENT TYPE IN THE PRODUCT
 APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE
 ADHESIVE PRODUCT APPROVAL.
  
 6) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 7) THE WINDOW SCHEDULE ON DRAWING A-5.0 SHOWS - DOUBLE
 HUNG WINDOWS, CASEMENT WINDOWS, PUSH OUT FRENCH
 CASEMENT WINDOWS - PLEASE PROVIDE PRODUCT APPROVALS FOR
 ALL WINDOW TYPES SHOWN ON THE WINDOW SCHEDULE.
  
 8) DRAWING C-1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-24 Cont ID  
Sent By rperdomo Date 2023-03-24 Time 14:20 Rev Time 0.00
Received By rperdomo Date 2023-03-24 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By rperdomo Date 2023-02-17 Time 15:00 Rev Time 0.00
Received By rperdomo Date 2023-02-16 Time 12:10 Sent To  
Notes
2023-02-17 15:02:20FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. THE PERMIT APPLICATION READS NEW BUILD. THE
 SUBMITTAL HAS 2 SEPARATE STRUCTURES, A HOUSE AND A
 CABANA. THE PERMIT APPLICATION SHOULD REFLECT WHICH
 STRUCTURE IT IS REFERRING TO AND THE OTHER STRUCTURE
 WILL REQUIRE A SEPARATE PERMIT. ONLY 1
 SET OF DOCUMENTS WILL BE REQUIRED FOR BOTH STRUCTURES
 WHICH HAD BEEN SUBMITTED.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By rrossano Date 2023-03-20 Time   Rev Time 0.00
Received By rrossano Date 2023-03-20 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-02-13 Cont ID  
Sent By parking Date 2023-02-13 Time   Rev Time 0.00
Received By rrossano Date 2023-02-13 Time   Sent To  
Notes
2023-02-13 11:56:45SHOW EXISTING CITY WATER & SEWER INFRASTRUCTURE ON
 DRAWINGS. IT APPEARS THAT PROPOSED CONSTRUCTION IS IN
 VICINITY OF CITY OWNED WATER UTILITIES. CALL 811 TO
 HAVE ONE CALL UTILITIES LOCATE THE UTILITY LINE AND
 THEN MEET WITH APPROPRIATE CITY OF WPB O&M PERSONNEL
 FOR THE SPECIFIC UTILITY TO DETERMINE AMOUNT OF
 CLEARANCE NEEDED.
  
 SANITARY: CHARLES PHOENIX 561-822-2181 [email protected]
 WATER: COURTNEY MOORE 561-822-2174 [email protected]
 STORMWATER: STEPHON HARRIS 822-2185 [email protected]
  
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-04-07 Cont ID  
Sent By ccole Date 2023-04-07 Time 12:22 Rev Time 0.00
Received By ccole Date 2023-04-07 Time 11:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 15:07 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 13:24 Sent To  
Notes
2023-03-17 15:09:012ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22100154
 3/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2: THE NEW PLAN SHEET SHOWS THE GALVANIZED
 METAL GAS PIPING TO RUN UNDERGROUND BELOW THE HOUSE
 UNPROTECTED. PLEASE REFER TO SECS G2415.11.1-
 G2415.11.4 FBC RES. AND INDICATE HOW THE PIPE WILL BE
 PROTECTED AGAINST CORROSION. PLEASE NOTE ZINC COATING
 SHALL NOT BE DEEMED ADEQUATE PROTECTION- SEC.
 G2415.11.2.
  
 2) P2: THE NEW PLAN SHEET DOES NOT PROVIDE VENTING
 DETAILS FOR THE NEW GAS FIREPLACE. PLEASE PROVIDE A
 VENTING DIAGRAM SHOWING THE TYPE AND SIZE OF VENT FLUE,
 THE TOTAL VENT RUN AND TERMINATION LOCATION- SECS.
 G2427.1, G2434.1, & G2435,1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By ccole Date 2023-02-15 Time 09:14 Rev Time 0.00
Received By ccole Date 2023-02-13 Time 17:35 Sent To  
Notes
2023-02-15 09:15:291ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22100154
 2/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: IN ORDER TO HELP EXPEDITE THE REVIEW OF
 THE GAS PIPING SYSTEM, PLEASE IDENTIFY THE TYPE OF PIPE
 AT EACH SECTION OR BRANCH SHOWN IN THE RISER, AND
 PROVIDE A SEPARATE FLOOR PLAN DRAWING THAT THAT SHOWS
 THE EXTERIOR AND INTERIOR GAS PIPING RUNS AND APPLIANCE
 LOCATIONS- SEC. 107.2.1 WPB AND SEC. G2413.1 FBC RES.
 A) FLOOR PLAN DRAWING: PLEASE SHOW THE LOCATIONS AND
 TERMINATION POINTS OF ALL SLEEVES AND CONDUITS INTERIOR
 AND EXTERIOR OF THE BUILDING AND HOW THE OPEN ENDS WILL
 BE SEALED AND VENTED WHERE REQUIRED- SEE SECS.
 G2415.14.1- G2415.14.2 FBC RES.
  
 2) P1: PE PIPING IS RATED AND LABELED FOR DIRECT
 UNDERGROUND BURIAL AND DOES NOT REQUIRE A PVC CONDUIT
 OR SLEEVE. PLEASE CORRECT THE NOTE ON THE DRAWING, AND
 NOTE THAT PE PIPING SHALL NOT BE INSTALLED UNDER THE
 BUILDING WHETHER SLEEVED OR NOT AND REQUIRES
 INSTALLATION OF A TRACER WIRE- SEE SECS. G2417.1-
 G2417.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-04-04 Cont ID  
Sent By fmittner Date 2023-04-04 Time 14:28 Rev Time 0.00
Received By fmittner Date 2023-04-04 Time 14:28 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-03-30 Cont ID  
Sent By fmittner Date 2023-03-30 Time 14:15 Rev Time 0.00
Received By fmittner Date 2023-03-30 Time 14:15 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-03-10 Cont ID  
Sent By fmittner Date 2023-03-10 Time 08:35 Rev Time 0.00
Received By fmittner Date 2023-03-10 Time 08:35 Sent To  
Notes
2023-03-10 08:36:15PER DECISION LETTER FROM HPB OVERALL HEIGHT NEEDS TO BE
 REDUCED BY TWO ADDITIONAL INCHES.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2023-04-25 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 12:29 Rev Time 0.00
Received By rmcphers Date 2023-04-20 Time 16:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-13 Cont ID  
Sent By aoliver Date 2023-04-13 Time 08:51 Rev Time 0.00
Received By aoliver Date 2023-04-10 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-04-07 Time   Rev Time 0.00
Received By lmarchan Date 2023-04-03 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-31 Cont ID  
Sent By aoliver Date 2023-03-31 Time 08:04 Rev Time 0.00
Received By aoliver Date 2023-03-15 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By aoliver Date 2023-03-13 Time 08:41 Rev Time 0.00
Received By aoliver Date 2023-02-09 Time 11:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-04-13 Cont ID  
Sent By lmarchan Date 2023-04-13 Time 15:43 Rev Time 0.00
Received By lmarchan Date 2023-04-07 Time 15:23 Sent To  
Notes
2023-04-13 15:43:18NO IMPACT FEES DUE. LEM
2023-04-07 15:23:464/7/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-27 Cont ID  
Sent By rmcphers Date 2023-02-27 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2023-02-27 Time 13:49 Sent To  
Notes
2023-02-27 13:49:40PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-17 Cont ID  
Sent By medwards Date 2023-03-17 Time 05:32 Rev Time 0.00
Received By medwards Date 2023-03-17 Time 05:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-17 Cont ID  
Sent By medwards Date 2023-02-17 Time 09:36 Rev Time 0.00
Received By medwards Date 2023-02-17 Time 09:36 Sent To  
Notes
2023-02-17 09:36:191ST REVIEW FMC
 PERMIT: 22100154
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION READS NEW BUILD. THE
 SUBMITTAL HAS 2 SEPARATE STRUCTURES, A HOUSE AND A
 CABANA. THE PERMIT APPLICATION SHOULD REFLECT WHICH
 STRUCTURE IT IS REFERRING TO AND THE OTHER STRUCTURE
 WILL REQUIRE A SEPARATE PERMIT. ONLY 1 SET OF DOCUMENTS
 WILL BE REQUIRED FOR BOTH STRUCTURES WHICH HAS BEEN
 SUBMITTED.
  
 2) SUBMIT A MANUAL J FOR EACH STRUCTURE. FEC R101.3
  
 3) SUBMIT AN ENERGY CALCULATION FOR EACH STRUCTURE. FEC
 R101.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-07 Cont ID  
Sent By ccole Date 2023-04-07 Time 12:22 Rev Time 0.00
Received By ccole Date 2023-04-07 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-17 Cont ID  
Sent By ccole Date 2023-03-17 Time 15:07 Rev Time 0.00
Received By ccole Date 2023-03-17 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-02-15 Cont ID  
Sent By ccole Date 2023-02-15 Time 09:15 Rev Time 0.00
Received By ccole Date 2023-02-13 Time 17:35 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By dbattles Date 2023-04-10 Time 12:42 Rev Time 0.00
Received By dbattles Date 2023-04-10 Time 12:42 Sent To  
Notes
2023-04-10 12:43:09PRIVATE PROVIDER INSPECTIONS.
 DOCUMNETS IN FILENET

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2023-04-07 Cont ID  
Sent By rmcphers Date 2023-04-07 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2023-04-07 Time 13:32 Sent To  
Notes
2023-04-07 13:33:09ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 13:04 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 13:03 Sent To  
Notes
2023-04-04 13:04:16SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-03-20 Cont ID  
Sent By rmcphers Date 2023-03-20 Time 15:50 Rev Time 0.00
Received By rmcphers Date 2023-03-20 Time 15:50 Sent To  
Notes
2023-03-20 15:51:03SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-02-27 Cont ID  
Sent By rmcphers Date 2023-02-27 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2023-02-27 Time 13:49 Sent To  
Notes
2023-02-27 13:50:09SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-04-26 Cont ID  
Sent By rmcphers Date 2023-04-26 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2023-04-26 Time 10:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 12:29 Rev Time 0.00
Received By rmcphers Date 2023-04-21 Time 12:28 Sent To  
Notes
2023-04-21 12:29:12SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS S3.01, A-5.0, A-4.0 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 13:03 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 13:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-20 Cont ID  
Sent By rmcphers Date 2023-03-20 Time 15:56 Rev Time 0.00
Received By rmcphers Date 2023-03-20 Time 15:56 Sent To  
Notes
2023-03-17 15:11:49PLUMBING AND GAS (P) PLANS PASSED.
2023-03-17 05:33:19MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-27 Cont ID  
Sent By rmcphers Date 2023-02-27 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2023-02-27 Time 14:05 Sent To  
Notes
2023-02-27 14:06:53SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING C-1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2023-02-17 09:37:00MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-04-04 Cont ID  
Sent By fmittner Date 2023-04-04 Time 14:28 Rev Time 0.00
Received By fmittner Date 2023-04-04 Time 14:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-30 Cont ID  
Sent By fmittner Date 2023-03-30 Time 14:13 Rev Time 0.00
Received By fmittner Date 2023-03-30 Time 14:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By fmittner Date 2023-03-10 Time 08:35 Rev Time 0.00
Received By fmittner Date 2023-03-10 Time 08:35 Sent To  
Notes
***NONE***