Plan Review Details - Permit 22100137
Plan Review Stops For Permit 22100137
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-10-17 Cont ID  
Sent By pleduc Date 2022-10-17 Time   Rev Time  
Received By bdolan Date 2022-10-17 Time 10:57 Sent To  
Notes
2022-10-17 11:25:17THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.8,
 ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO
 SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED
 AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE
 WITHOUT LOSS FOR 2 HOURS.
  
 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN
 EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE
 NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS
 THAN 200 PSI (13.8 BAR) FOR 2 HOURS.
  
 PLEASE ENSURE THAT A MECHANICAL INSPECTION # 603 - FIRE
 SPRINKLER PIPE IS CALLED IN WITH FIRE SPRINKLER #310
 ??? FIRE SPRINKLER HEAD AND # 311 - PRESSURE TEST
 INSPECTIONS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-18 Cont ID  
Sent By mpeterso Date 2022-10-18 Time 10:17 Rev Time 0.00
Received By mpeterso Date 2022-10-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-10-18 Cont ID  
Sent By mpeterso Date 2022-10-18 Time 10:17 Rev Time 0.00
Received By mpeterso Date 2022-10-18 Time 10:17 Sent To  
Notes
***NONE***