Plan Review Details - Permit 22100111
Plan Review Stops For Permit 22100111
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 10:51 Rev Time 0.00
Received By lbond Date 2023-07-17 Time 10:50 Sent To  
Notes
2023-07-17 10:47:06FPB 107.2.1 CLARIFY
 PREVIOUS COMMENTS NOT ADDRESSED - PROVIDE FULL NOA
 SPECS FOR ALL NEW PROPOSED WINDOWS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-06-29 Cont ID  
Sent By eroseber Date 2023-06-29 Time 17:36 Rev Time 0.00
Received By eroseber Date 2023-06-29 Time 17:35 Sent To  
Notes
2023-06-29 17:38:55PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
 ***PRIMARY CONTACT IS EMAIL***
  
 1. PLEASE SUBMIT FBC/NOA FOR ALL REPLACEMENT
 FENESTRATION AND MULLIONS, WITH SPECIFIC MODELS, SIZES,
 AND DESIGN PRESSURE TABLES HIGHLIGHTED. FBC 107.2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-20 Cont ID  
Sent By pvalenti Date 2023-03-20 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2023-03-20 Time 06:25 Sent To  
Notes
2023-03-20 07:24:40PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE
 REVIEW.
  
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 PLAN SHEET A-1 ARCHITECT'S SIGNATURE IS NOT A
 VERIFIABLE DIGITAL SIGNATURE. THE SIGNATURE APPEARS TO
 BE A SCANNED COPY OF AN ORIGINAL HAND SIGNATURE.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 2. SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-31 Cont ID  
Sent By eroseber Date 2022-12-31 Time 21:54 Rev Time 0.00
Received By eroseber Date 2022-12-31 Time 21:54 Sent To  
Notes
2022-12-31 21:55:341. PREVIOUS REVIEW COMMENTS NOT ADDRESSED. FBC 107.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 12:02 Rev Time 0.00
Received By eroseber Date 2023-06-29 Time 17:34 Sent To  
Notes
2022-11-07 12:09:521. PLEASE SPECIFY WINDOW REPLACEMENT SIZE AT OPENINGS
 SHOWN AS EGRESS. FBC 107.2
 2. PLANS ARE NOT LEGIBLE. PLEASE SUBMIT LEGIBLE PLANS
 OR DETAILS. FBC 107.2
 3. INFILL DETAIL IS NOT LEGIBLE. PLEASE RESUBMIT
 LEGIBLE DETAILS. FBC 107.2
 4. PLEASE SUBMIT FLOOR PLAN SHOWING ALL OPENINGS MARKED
 EXISTING TO REMAIN OR MARKED WITH REPLACEMENT. FBC
 107.2
 5. PLEASE SUBMIT WINDOW SCHEDULE. FBC 107.2
 6. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO
 THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR
 FBC B 1405.4. THIS IS ON PLANS BUT NOT LEGIBLE. FBC
 107.2
 DIGITAL SIGNATURE-DISAPPROVED
 1. NEW INFILL AND DETAILED PLANS MUST BE SEALED BY
 EOR/AOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 10:51 Rev Time 0.00
Received By lbond Date 2023-07-11 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date 2023-06-29 Cont ID  
Sent By eroseber Date 2023-06-29 Time 17:43 Rev Time 0.00
Received By eroseber Date 2023-06-28 Time 18:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-20 Cont ID  
Sent By pvalenti Date 2023-03-20 Time 07:27 Rev Time 0.00
Received By pvalenti Date 2023-03-15 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2022-12-31 Cont ID  
Sent By eroseber Date 2022-12-31 Time 21:56 Rev Time 0.00
Received By eroseber Date 2022-12-12 Time 08:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 12:15 Rev Time 0.00
Received By eroseber Date 2022-10-21 Time 08:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-07-17 Cont ID  
Sent By lbond Date 2023-07-17 Time 10:51 Rev Time 0.00
Received By lbond Date 2023-07-17 Time 10:48 Sent To  
Notes
2023-07-17 10:50:31PROVIOUS SIGNATURE COMMENTS NOT ADDRESSED-UPLOAD
 DIGITALLY SIGNED AND SEALED OR COME IN PERSON TO CITY
 HALL SO WE CAN PROCEED TO THE ARCHIVE OF THE ORIGIAL
 SHEET

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-06-29 Cont ID  
Sent By eroseber Date 2023-06-29 Time 17:40 Rev Time 0.00
Received By eroseber Date 2023-06-29 Time 17:40 Sent To  
Notes
2023-06-29 17:43:25PLAN REVIEWER: ED ROSEBERRY PX2909
 EMAIL: [email protected]
 PH: 772-359-3502
 ***PRIMARY CONTACT IS EMAIL***
  
 1. AS PREVIOUSLY COMMENTED, ELECTRONIC SUBMITTALS MUST
 HAVE A VERIFIABLE SEAL. PLEASE PROPERLY RESPOND TO
 PREVIOUS SIGNATURE COMMENTS. FBC 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-20 Cont ID  
Sent By pvalenti Date 2023-03-20 Time 07:25 Rev Time 0.00
Received By pvalenti Date 2023-03-20 Time 06:25 Sent To  
Notes
2023-03-20 07:26:52SIGNATURE REVIEW DENIED:
  
 PLAN SHEET A-1 DOES NOT HAVE A VERIFIABLE ARCHITECTS
 DIGITAL SIGNATURE.
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-31 Cont ID  
Sent By eroseber Date 2022-12-31 Time 21:56 Rev Time 0.00
Received By eroseber Date 2022-12-31 Time 21:55 Sent To  
Notes
2022-12-31 21:56:40PREVIOUS COMMENTS NOT ADDRESSED. FBC 107.2

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-07 Cont ID  
Sent By eroseber Date 2022-11-07 Time 12:10 Rev Time 0.00
Received By eroseber Date 2022-11-07 Time 12:10 Sent To  
Notes
2022-11-07 12:11:28SEE BUILDING COMMENTS
  